GUIDE TO THE
REGENERATIVE APPLICATION
SINUS PENTA
121/
150
5.8.
Digital Outputs Menu
5.8.1. Overview
Digital outputs MDO1 and MDO2, Push-Pull and Open Collector outputs respectively, can be set up with the
parameters contained in the Digital Outputs menu.
MDO3 cannot be set up because it is assigned to the closure of the pre-charge contactor.
MDO4 is assigned to the motor drive activation; its activation logic can be programmed through
C503
.
5.8.2. List of Programmable Parameters P580 and P581
Parameter
FUNCTION
User Level
MODBUS
Address
DEFAULT
VALUES
P580
MDO1 Digital Output Function
BASIC
700
1: Run OK
P581
MDO2 Digital Output Function
BASIC
701
2: Mains Fault
Table 21: List of parameters P580 and P581
P580, P581 MDO1, MDO2 Digital Output Function
P580, P581
Range
0
11
0: Synchronization OK
1: Run OK
2: Mains Fault
3: Drive OK
4: Drive in Alarm
5: W40 Fan Fault
6: Pre-charge OK
7: Command 1 from Fieldbus
8: Command 2 from Fieldbus
9: Command 3 from Fieldbus
10: Command 4 from Fieldbus
11: Fan ON
Default
1
(P580)
2
(P581)
1: Run OK (
P580
)
2: Mains Fault (
P581
)
Level
BASIC
Address
700 701
Function
These parameters set the functions implemented by digital outputs
MDO1 and MDO2.
See Table 22 for more details.