ASAC-0 

5/12 

 

3.4

 

Outputs 

3.4.1

 

Main Contactor Output 
The Main Contactor output (terminals 13, 14) closes as soon as the soft starter receives a start command and remains closed while the 

soft starter is controlling the motor (until the motor starts a coast to stop, or until the end of a soft stop).  The Main Contactor output will 

also open if the soft starter trips. 
The Main Contactor output can be used to directly control a main contactor coil. 

 

3.4.2

 

Run Output 
The run output relay (terminals 23, 24) can be used to signal run status.  This relay is normally open. 
The relay operates when the soft start is complete, the bypass relays are closed and full voltage is being applied to the motor.  The 

relay can be used to operate a contactor for power factor correction capacitors, or to signal soft starter run status to an automation 

system. 

3.5

 

Electrical Schematics 

Soft starter installed with fuses, a main contactor and overload protection. 

 

6/T3

4/T2

2/T1

5/L3

3/L2

1/L1

13

14

M

K1

23

24

K1

03238.

F

 

 

Motor (three phase) 

K1 

Main contactor   

13, 14  Main contactor output 

23, 24  Run contactor output 

 

Summary of Contents for ASAC-0

Page 1: ...resulting by the use of non original spare parts Enertronica Santerno reserves the right to make any technical changes to this manual and to the device without prior notice If printing errors or simil...

Page 2: ...ected to mains voltage Only a qualified electrician should carry out the electrical installation Improper installation of the motor or the soft starter may cause equipment failure serious injury or de...

Page 3: ...090 200 160 240 216 214 114 5 51 6 1 ASAC 0 110 7 87 6 30 9 44 8 50 8 43 4 5 2 0 13 5 2 2 Physical Installation 1 2 3 4 15757 A 1 ASAC 0 007 ASAC 0 055 Allow 100 mm 3 9 inch between soft starters ASA...

Page 4: ...24 VAC VDC A1 A2 WARNING Always apply control voltage before or with mains voltage CAUTION With 24 VAC VDC use contacts rated for low voltage and low current gold flash or similar 3 3 Control Circuits...

Page 5: ...3 4 2 Run Output The run output relay terminals 23 24 can be used to signal run status This relay is normally open The relay operates when the soft start is complete the bypass relays are closed and f...

Page 6: ...time the motor will take to reach full speed 1 Set the start ramp time to 20 seconds 2 Set the initial start voltage as required for the application 3 Attach a current monitoring device to output T1 4...

Page 7: ...than five seconds while the soft starter is running These trip points are not adjustable In pre start starting and stopping modes the high and low frequency limits both apply with no time delay A supp...

Page 8: ...support network communication via easy to install communications modules Each soft starter can support one communications module at a time Available protocols Ethernet Profinet Modbus TCP Ethernet IP...

Page 9: ...age to SCRs from transient overload currents and for Type 2 coordination ASAC 0 soft starters have been tested to achieve Type 2 coordination with semiconductor fuses Suitable Bussmann and Ferraz Mers...

Page 10: ...60068 Test Fc Sinusoidal 4 Hz to 13 2 Hz 1 mm displacement 13 2 Hz to 200 Hz 0 7 g EMC Emission Equipment class EMC Class B Conducted radio frequency emission 0 15 MHz to 0 5 MHz 56 46 dB V 0 5 MHz t...

Page 11: ...SAC 0 11 12 7 4 Model Code ASAC 0 Control voltage 1 110 240 VAC 380 440 VAC 2 24 VAC VDC Mains voltage 4 200 440 VAC 5 200 575 VAC Nominal kW rating 400 VAC 007 030 AC53b 4 6 354 037 110 AC53b 4 6 594...

Page 12: ...12 12 ASAC 0...

Reviews: