ASAC-0 

 

 

7.3

 

General Technical Data 

Mains Supply 

Mains voltage (L1, L2, L3) 

 

4  ................................................................................................................................   3 x 200 VAC ~ 440 VAC (+ 10% / - 15%) 

 

5  ................................................................................................................................   3 x 200 VAC ~ 575 VAC (+ 10% / - 15%) 

Mains frequency (at start)    ..........................................................................................................................................   45 Hz to 66 Hz 

Rated insulation voltage    .....................................................................................................................................................   600 VAC 

Form designation .............................................................................................................. Bypassed semiconductor motor starter form 1 

 

Control voltage (01, 02) 

ASAC-0/xxx/x/1   ...................................................................................................................................  110-240 VAC (+ 10% / - 15%) 

 

 .................................................................................................................................................... or 380-440 VAC (+ 10% / - 15%) 

ASAC-0/xxx/x/2   ...............................................................................................................................................   24 VAC/VDC (± 20%) 

Current consumption (during run)   ......................................................................................................................................   < 100 mA 

Current consumption (inrush) 

 

ASAC-0/xxx/x/1  .................................................................................................................................................................   10 A 

 

ASAC-0/xxx/x/2  ...................................................................................................................................................................   2 A 

 

Inputs 

Start (terminal 01)   ......................................................................................................................................................   Normally open 

 

 ........................................................................................................................... 150 k

 @ 300 VAC and 5.6 k

 @ 24 VAC/VDC 

Stop (terminal 02)   ....................................................................................................................................................  Normally closed 

 

 ........................................................................................................................... 150 k

 @ 300 VAC and 5.6 k

 @ 24 VAC/VDC 

 

Outputs 

Main contactor (terminals 13, 14)   ................................................................................................................................   Normally open 

 

 ............................................................................................................................................. 6 A, 30 VDC / 6 A, 250 VAC resistive 

Run relay (terminals 23, 24)  .........................................................................................................................................   Normally open 

 

 ............................................................................................................................................. 6 A, 30 VDC / 6 A, 250 VAC resistive 

 

Environmental 

Degree of Protection ASAC-0/007 to ASAC-0/055   ......................................................................................................................   IP20 

Degree of Protection ASAC-0/075 to ASAC-0/110   ......................................................................................................................   IP00 

Operating temperature   .........................................................................................................................................   - 10 °C to + 60 °C 

Storage temperature   ............................................................................................   -25 °C~+ 60 °C (to +70 °C for less than 24 hours) 

Humidity   .................................................................................................................................................  5%~95% Relative Humidity 

Pollution degree   ...................................................................................................................................................   Pollution Degree 3 

Vibration   .............................................................................................................................................   IEC 60068 Test Fc Sinusoidal 

 

 ........................................................................................................................................  4 Hz to 13.2 Hz: ± 1 mm displacement 

 

 ..........................................................................................................................................................   13.2 Hz to 200 Hz: ± 0.7 g 

 

EMC Emission 

Equipment class (EMC)    ........................................................................................................................................................   Class B 

Conducted radio frequency emission  .......................................................................................   0.15 MHz to 0.5 MHz: < 56-46 dB (µV) 

 

 .................................................................................................................................................   0.5 MHz to 5 MHz: < 46 dB (µV) 

 

 ..................................................................................................................................................   5 MHz to 30 MHz: < 50 dB (µV) 

Radiated radio frequency emission .............................................................................................   30 MHz to 230 MHz: < 30 dB (µV/m) 

 

 ......................................................................................................................................   230 MHz to 1000 MHz: < 37 dB (µV/m) 

 

EMC Immunity 

Electrostatic discharge   .....................................................................................................   4 kV contact discharge, 8 kV air discharge 

Radio frequency electromagnetic field   ......................................................................................   0.15 MHz to 1000 MHz: 140 dB (µV) 

Rated impulse withstand voltage (Fast transients 5/50 ns)   ..............................................................   2 kV line to earth, 1 kV line to line 

Voltage dip and short time interruption   ..............................................................................................   100 ms (at 40% nominal voltage) 

Harmonics and distortion   ......................................................................................................   IEC61000-2-4 (Class 3), EN/IEC61800-3 

 

 

 .................................................................................................................................................................   EAC TR TC 020/2011 

 

Short Circuit 

Rated short-circuit current ASAC-0/007 to ASAC-0/022   .............................................................................................................   5 kA 

1

 

Rated short-circuit current ASAC-0/030 to ASAC-0/110   ...........................................................................................................   10 kA 

1

 

1

 These short circuit ratings are with fuses used as given in the table under Semiconductor Fuses on page 9. 

 

Heat Dissipation 

During Start   ............................................................................................................................................................   3 watts / ampere 

During Run   ...............................................................................................................................................................  10 watts typical 

 

Standards Approvals 

CE     ..............................................................................................................................................................................   EN 60947-4-2 

EAC (formerly GOST)   ............................................................................................................   TR TC 004/2011 and TR TC 020/2011 

RoHS  ..................................................................................................................................  Compliant with EU Directive 2011/65/EU 

UL / C-UL  ................................................................................................................................................................................   UL 508 

 

Operational Life 

ASAC-0/007~055   .............................................................................................................................................   1,000,000 operations 

ASAC-0/075~110   ..................................................................................................................................................  30,000 operations 

 

Summary of Contents for ASAC-0

Page 1: ...resulting by the use of non original spare parts Enertronica Santerno reserves the right to make any technical changes to this manual and to the device without prior notice If printing errors or simil...

Page 2: ...ected to mains voltage Only a qualified electrician should carry out the electrical installation Improper installation of the motor or the soft starter may cause equipment failure serious injury or de...

Page 3: ...090 200 160 240 216 214 114 5 51 6 1 ASAC 0 110 7 87 6 30 9 44 8 50 8 43 4 5 2 0 13 5 2 2 Physical Installation 1 2 3 4 15757 A 1 ASAC 0 007 ASAC 0 055 Allow 100 mm 3 9 inch between soft starters ASA...

Page 4: ...24 VAC VDC A1 A2 WARNING Always apply control voltage before or with mains voltage CAUTION With 24 VAC VDC use contacts rated for low voltage and low current gold flash or similar 3 3 Control Circuits...

Page 5: ...3 4 2 Run Output The run output relay terminals 23 24 can be used to signal run status This relay is normally open The relay operates when the soft start is complete the bypass relays are closed and f...

Page 6: ...time the motor will take to reach full speed 1 Set the start ramp time to 20 seconds 2 Set the initial start voltage as required for the application 3 Attach a current monitoring device to output T1 4...

Page 7: ...than five seconds while the soft starter is running These trip points are not adjustable In pre start starting and stopping modes the high and low frequency limits both apply with no time delay A supp...

Page 8: ...support network communication via easy to install communications modules Each soft starter can support one communications module at a time Available protocols Ethernet Profinet Modbus TCP Ethernet IP...

Page 9: ...age to SCRs from transient overload currents and for Type 2 coordination ASAC 0 soft starters have been tested to achieve Type 2 coordination with semiconductor fuses Suitable Bussmann and Ferraz Mers...

Page 10: ...60068 Test Fc Sinusoidal 4 Hz to 13 2 Hz 1 mm displacement 13 2 Hz to 200 Hz 0 7 g EMC Emission Equipment class EMC Class B Conducted radio frequency emission 0 15 MHz to 0 5 MHz 56 46 dB V 0 5 MHz t...

Page 11: ...SAC 0 11 12 7 4 Model Code ASAC 0 Control voltage 1 110 240 VAC 380 440 VAC 2 24 VAC VDC Mains voltage 4 200 440 VAC 5 200 575 VAC Nominal kW rating 400 VAC 007 030 AC53b 4 6 354 037 110 AC53b 4 6 594...