2) Connect the output wire of the parallel UPSs to an output terminal
block, load connect to the output terminal block via load wire.
Note: Strictly follow the wire requirement of single UPS to perform The
wiring of each UPS.The distance between the UPSs in parallel is less than
20 meters. The difference between the wires of input and output of the
UPSs is required to be less than 20%.The distance between the UPSs in
parallel is more than20 meters. The difference between the wires of input
and output of the UPSs is required to be less than 10%.
3) The parallel UPS input terminal panel and output terminal panel
see below, the wires of each parallel UPS must follow the wire
requirement for single UPS. Wire connection diagram see next