11

Control system (S1-1)

[Function]

This makes a selection of phase control or cycle control. The phase control is to control the
phase of half-cycle by means of its effective value.
The cycle control is to control the number of turning ON in one cycle during a certain con-
stant period by means of its effective value. Changeover between phase and cycle controls
is not possible during output operation. Changeover between phase and cycle controls is
possible only while the power is turned off.
Use the S1-4 switches to change the setting of intermittent type/continuous type for cycle
control. However, changeover of the control system is not made during output operation. 
A system is provided to prevent the changeover of control system during its operation.

Type of temperature control unit (S1-2, 3)

[Function]

This changes the signal levels sent from the temperature control unit, and selects the two-
position control. Changeover of the operating conditions of temperature control unit is pos-
sible only while the power is at a standstill, but such changeover is not possible during out-
put operation.
However, changeover of the type of the temperature control unit is not possible during out-
put operation. A system is provided to prevent the changeover of the type of temperature
control unit during operation.

Cycle control (S1-4)

[Function]

This makes a selection of intermittent type or continuous type for cycle control.
Use the S1-1 switch to change the setting of phase control or cycle control.
However, changeover of the cycle control is not possible during output operation. A system
is provided to prevent the changeover of cycle control during output operation.

Setting of dip switch S3

S3 is a switch to change the setting of the unit address when an optional RS485 communication unit is
installed. Therefore, leave the setting of the switch as initially set.

Phase control waveform 
(In the case of 3 arm unit)

Output voltage

Cycle control waveform 
(In the case of 3 arm unit)

Output cycles
(Effective value)

25

50

75

100

25

(50

)

50

(70

)

75

(86

)

100

Continuous type waveform 
(In the case of 3 arm unit)

Intermittent type waveform 
(In the case of 3 arm unit)

Output cycles
(Effective value)

Output cycles
(Effective value)

Period  1 second

25

50

75

100

(50

)

(70

)

(86

)

25

(50

)

50

(70

)

75

(86

)

100

Summary of Contents for UF-3 Series

Page 1: ...AL In order to operate this product properly operators and other persons concerned are all requested to read the Safety Precautions in this INSTRUCTION MANUAL thoroughly before using the product Stric...

Page 2: ...OF UNIT 8 Connection diagram for each setting system 8 How to connect unit control cables 9 HOW TO SET UNIT 10 setting of dip switch S1 10 setting of dip switch S3 11 FUNCTION CHARACTERISTICS 12 DETE...

Page 3: ...from Thyristor ele ments and obtained user s enjoyment and satisfaction on our various products Now we introduce our Thyristor Type Power Adjusting Unit UF3 Series that we have developed with confiden...

Page 4: ...in death or serious injury To secure safety this unit must be installed wired maintained inspected and repaired by qualified persons or persons who are familiar with this unit In the event of any fai...

Page 5: ...nstallation Locate the unit at a well ventilated and dust free place to the extent possible Secure spaces necessary for discharging heat on the top and bottom and both sides of the main body When stac...

Page 6: ...e Select the input and output cables of gauges suitable for this unit Excessively small gauges of cables may cause overheating or fire Use the cables of a dielectric strength suitable for the circuit...

Page 7: ...on the power distribution panel in order to prevent others than the workers from touching the switch Not doing so may cause electric shock or injury Before maintaining inspecting or repairing this un...

Page 8: ...d items Q ty 1 UF3 unit body 1 unit 2 Screws nuts and others for the connection of output wires a Screw 25A 250A only 6 pcs b Bolt 350A and 450A only 6 pcs c Washer 350A and 450A only 12 pcs d Spring...

Page 9: ...2 CT1 CT2 CT3 F1 TF1 TF2 TF3 F3 F2 RA SA TA I 2 V3 I 3 V1 D1 I 1 D2 1C HA HC 1A RT AT HL GT ST PH PS S VE3 VF2 VL 2 VH 2 VE1 D3 CN1 UF RS485 UF DN UF CL UF PR CN2 CN3 CN5 V2 THS FAN Snubber circuit Sn...

Page 10: ...nd Lower Point is selectively available The setting of Grade and Lower Point is selectively available Automatic adjustment DC 4 to 20mA 1 to 5V Note 1 Note 2 Automatic adjustment DC 0 to 5V Two positi...

Page 11: ...or failure output minor fail ure output external input and output terminals and conversion board of the unit 1 Fix the easy locks on the unit 2 Bind the control cables with the easy locks Separate the...

Page 12: ...part of the unit to change the setting of dip switch S1 located on the printed circuit Setting of dip switch S1 Control system Phase control Type of temperature control unit DC4 20mA or DC1 5V Cycle...

Page 13: ...ll but such changeover is not possible during out put operation However changeover of the type of the temperature control unit is not possible during out put operation A system is provided to prevent...

Page 14: ...istic 0 Linear characteristic Characteristic 1 1 6th root characteristic Characteristic 2 1 8th root characteristic Characteristic 3 2 0th root characteristic Characteristic 4 2 2th root characteristi...

Page 15: ...and operation stops To resume operation turn off the control power supply TMP This detects temperature rise abnormality when the temperature of a cooling fin has been increased abnormally On detectio...

Page 16: ...elf diagnostic function is provided to detect load open or short On detection of load open or short an LOD indication flickers Operation continues in the event of load open Operation stops in the even...

Page 17: ...LOD on the upper part simultaneously flicker for about 1 minute If the control power supply is turned off and then on during compulsory release of self diagnostic function the settings are stored duri...

Page 18: ...ties listed below when detected causes a minor failure relay in the unit to activate Power supply undervoltage Abnormal frequency Load open to be detected by self diagnostic function Detection of heat...

Page 19: ...6 174 M6 UF3 0075 F 75A Self cooling 200 180 240 256 270 230 7 252 M6 UF3 0100 F 100A Air cooling 230 210 240 256 270 230 10 312 M6 UF3 0150 F 150A Air cooling 230 210 350 366 380 260 13 522 M8 UF3 0...

Page 20: ...8 FUSE TO BE USED Unit current Fuse 200V 400V 25A 660GH 50S F 35A 660GH 63S F 50A 660GH 100S F 75A 660GH 125S F 100A 660GH 160S F 150A 660GH 250S F 250A 660GH 350S F 350A 660GH 500S F 450A 660GH 710S...

Page 21: ...an attachment space secured as instructed in the Precautions in Installation Attaching the unit in the horizontal direction or reduc ing the attachment space will adversely affect a cooling effect an...

Page 22: ...uble is suspected read this INSTRUCTION MANUAL carefully to inspect the fol lowing items If the trouble is not solved yet be sure to turn off the power supply of the unit and contact our distributors...

Page 23: ...inear type One of seven types allows arbitrary setting of input output characteristics Additionally the value once set is stored even after power is turned off Conversion board Model UF TB Function Us...

Page 24: ...of 90 RH or below Storage temperature 20 C 70 C Applicable load Phase control resistive load inductive load transformer primary side control Cycle control resistive load Control signal Current signal...

Page 25: ...MEMO...

Page 26: ...852 2785 6009 SANREX ASIA PACIFIC PTE LTD Singapore 25 Tagore Lane 04 02B Singapore Godown 787602 Singapore Tel 65 6457 8867 65 6459 6426 Fax 65 6459 6425 FOSHAN CITY SHUNDE SANREX LIMITED China Dazh...

Reviews: