8

light will blink. If system pause occurred in release delay status (pause on the main panel is pressed), it will
exit release delay status and the light is out.
Note: The reason that can

t enter release startup status after release delay includes:

1.

Other area is starting electromagnetic valve, wait till other area finished the act, and then enter
release startup status. Considering system power (only support the act of release valve in one
area) and practical situation of multi-area agent releasing control panel (it

s rare that many areas

simultaneously start agent releasing), in this situation, the startup will be performed in the order of
priority, the act of each electromagnetic valve is10s;

2.

When release trouble occurs in the area, it can

t enter release startup status.

RELEASE STARTUP

When system starts the electromagnetic valve of the area, it enters release startup status, and the light is on.

RELEASE CONFIRM

If the system detects that electromagnetic valve has send a drive signal, this light will be on.

Note: If the system hasn

t start e

lectromagnetic

valve, while it receives the signal from external

electromagnetic

valve the startup signal, this light will be on, together with the trouble alarm of the system.

VI. Description of the Keyboard Operation

There are 9 function keys on the main panel of JB-QB-QM200/4 (shown in figure 10); functions below.

KEY ON/OFF

A keyboard lock is set in the system to avoid mis-operation.
To unlock the keyboard, presses the KEY ON/OFF on the keyboard, then the keyboard is unlocked and

KEY

ON/OFF

light will be on. To lock the keyboard, press the KEY ON/OFF key and the

KEY ON/OFF

light will be out.

After the keyboard is on, with no operation for over 4 minutes, the keyboard will automatically turnoff and the light
will go out. When the keyboard is locked, other keys are invalid except SILENCE key,

SILENCE

Eliminate current audible alarms of the system, and the light will be on. When new alarm occurs, it will go out.

SYSTEM RESET

This key pressed, the system will clear all alarms, troubles, exit pause status and initialize all the outputs.

SYSTEM TEST

Press this key to run a system self-testing. During the test, all the indicator lights and delay digital clocks will be on,
the digital clock repeatedly indicates 0-4 rapidly, and the audible alarm changes in the following sequence: trouble
sound

fire alarm sound

release countdown sound

release alarm sound.

MANUAL/AUTO

Press this key to switch between automatic and manual mode.

PAUSE

This key pressed, the system will switch to the pause mode and the indicator light will be on.
When any area of the system is in release delay status, the keyboard lock doesn

t limit the key. That is, whether the

keyboard is on or off, the key PAUSE is effective all the time. In this case, PAUSE pressed, all areas in release
delay status will stop countdown immediately and exit release delay status.

Note: When the system is in the pause mode, it will sound once every minute to prompt the users that it has lost the
function of fire extinguishing. This prompted sound can

t be eliminated by silence.

HOUR

This key pressed once, the hour will be increased by one.

MINUTE

This key pressed once, the minute will be increased by one, meanwhile, the second will be set to 0.

QUERY

This key pressed once, query release startup time of one area. The delay digital clock of corresponding area
display will show

CH

, which means it

s querying release startup time of the area. The digital clock of the main

display will show release startup time of the area and will have no display when the release hasn

t start in the area.

It will automatically restore normal status with no operation in 10secs.

JB-QB-QM200/4 panel of area n (n=1-4) has one emergent release key (see figure 10), functions below:

EMERGENT RELEASE

To press this button, you must break the crash switch on the panel, and press heavily on the central point as

pointed by the red arrow to touch the protected micro switch and hold for 1-2 seconds. This button pressed, the
system will start the electromagnetic valve after a delay 20 seconds and gives off audible/visible alarm
correspondingly, then start corresponding output signal.

VII. Power Management for the Control Panel

JB-QB-QM200/4 has adopted the advanced power management system to guarantee stable and reliable

operation of the system.

When the AC input is between AC187V-AC242V, the AC-DC power module can operate properly. At this stage,

the system will output DC24V-DC27.6V to ensure that the electromagnetic valve and other equipments with low
impedance can operate properly even when the line loss is removed.

When the AC input exceeds the range of AC187V-AC242V, the system will seamlessly switch to DC power

supply and alarm for AC TROUBLE. Meanwhile the system output depends on the voltage of the battery. The

Summary of Contents for JTW-ZD-01K

Page 1: ...Multi Area Agent Releasing Control System ...

Page 2: ...Keyboard Operation 8 VII Power Management for the Control Panel 8 VIII System Adjustment 9 IX System Maintenance 10 X General Troubleshooting 10 Warning The system may be damaged in the area where the input of AC power supply is beyond AC 270V for long time unless AC 220V is connected with the voltage stabilizer Power for the voltage stabilizer must be over 300W ...

Page 3: ...s and resumes automatically when trouble is solved n Full electrical switch of AC and DC power supply n Monitor the status of backup batteries against overcharge and overdischarge Low consumption design 7 0 AH battery the system can work on up to 48 hours n Protect the keyboard by a lock to prevent wrong operation n HFC 227ea Low poison efficient extinguishing with no impact on ozonosphere n HFC 2...

Page 4: ...g surface with the hanging hole in the back of the box and ensure there is enough room for the wiring and the opening of the control panel The installation dimension is shown in figure 1 size unit mm Note l At least the space of 1 meter needs to be saved for the operation on the front of the control panel l For the outlet hole on the top of the box at least the space of 0 3 meter needs to be saved...

Page 5: ...x the storage steel cylinder in the cabinet l Connections between pipes and pipe accessories have been installed before leaving factory as is shown in figure 4 Note that the outlet of pipes should be aligned with the hole in the spray head on the panel of cabinet l Install the spray head a screwdriver can be used to tighten the spray head into the small hole l Confirm the place of the agent releas...

Page 6: ... AC220V 50Hz JTY GD 01K 1 2 3 10K 1 2 3 10K JTW ZD 01K JTW ZD 01K 1 2 3 1 2 3 Figure 8 11 Figure 7 Area control board input output terminal 1 2 4 3 6 5 7 8 9 10 11 13 12 15 14 16 17 22 19 18 20 21 24 23 25 30 27 26 28 29 31 32 3 2 1 4 3 4 2 1 3 4 2 1 3 1 4 2 3 1 4 2 3 1 4 2 JTY GD 01K JTW ZD 01K Terminal load 10K Terminal load 10K Alarm Bell Eelectromagnetic valve ...

Page 7: ...elayed for 20 seconds Non pause status Note When the release is completed the main panel will display the time of release in blinking blinking 00 on the area panel shows release is completed in the area l Schematic diagram of the control panel s inside connection is shown in figure 7 l Inside structure of the control panel is shown in figure 8 the meaning of each is as follows 6 The Connection of ...

Page 8: ... power module DC TROUBLE The light is on when the battery connection is in open circuit or DC voltage is lower than 22V SYSTEM RELEASE When anyone area enters release status and start up the electromagnetic valve this light will be on SYSTEM FIRE When any detector zone finds fire alarms this light will be on SYSTEM TROUBLE When the system detects abnormity such as AC DC trouble release trouble zon...

Page 9: ...MANUAL AUTO SILENCE SYSTEM RESET SYSTEM TEST MANUAL AUTO PAUSE HOUR QUERY MINUTE ZONE1 FIRE ZONE1 TROUBLE ZONE2 FIRE ZONE2 TROUBLE EMERGENT STOP RELEASE TROUBLE INPUT TROUBLE OUTPUT TROUBLE MANUAL RELEASE RELEASE DELAY RELEASE STARTUP RELEASE CONFIRM DELAY TIME EMERGENT RELEASE ZONE1 FIRE ZONE1 TROUBLE ZONE2 FIRE EMERGENT STOP RELEASE TROUBLE INPUT TROUBLE OUTPUT TROUBLE MANUAL RELEASE RELEASE DEL...

Page 10: ...udible alarm changes in the following sequence trouble sound fire alarm sound release countdown sound release alarm sound MANUAL AUTO Press this key to switch between automatic and manual mode PAUSE This key pressed the system will switch to the pause mode and the indicator light will be on When any area of the system is in release delay status the keyboard lock doesn t limit the key That is wheth...

Page 11: ...isconnect the detector fix the base and then rotate the detector counter clockwise to an angle The installation is just contrary but attention needs to be paid to the inhibiting device between the detector and the base the position should not be exceeded when rotating the detector 5 Turn on the power supply of the control panel turn on the AC DC switch on the power module and check whether the con...

Page 12: ...c The system components should have no collision distortions and other mechanic damages without rust on the surface The coating should be perfect the nameplate should be clear shield lead sealing and safety mark of the manual equipment should be complete 3 Pointer on the pressure gauge of the storage device should be in the green zone please pressurize or report to us if the pointer is lower than ...

Page 13: ...ck whether the keyboard lock is on and the keyboard light is on when the keyboard lock is off keys are invalid except the key silence and emergent release the key pause is controlled by the keyboard lock except when the control panel is in the state of release countdown Symptom On the control panel AC DC indicator lights are on at the same time When AC has no input or exceed the range of safety vo...

Reviews: