Air Conditioner Service Manual
10
In defrosting, LED showing by winking.
No matter AC come into or out of defrosting, indoor fan motor speed is the same as Cold
Air Prevention C
ontrol.
While one of the following conditions satisfied, unit comes out of defrosting and shifts to
heating mode:
a. Outdoor coil Temperature (OPT)
≥15
℃
.
b. The time of defrosting keeps for more than 10 minutes.
(5) Indoor exchanger overheat protection
When IDU Pipe (
exchanger
) Temperature (IPT) is higher than 55
℃
, unit comes into indoor
exchanger overheat protection. The compressor drops its frequency toward to F1 level until
IPT
≤52
℃
If IPT
≤52
℃
and keep for 5 minutes,
control system doesn’t limit running frequency.
If IPT>62
℃
, control system shut down compressor, and recover while IPT drop less than 50
℃
.
4.7
“SLEEP” mode
When the SLEEP button is pressed, the AC operates as following:
The indoor fan speed is set at low speed, the power lamp and the sleep lamp is on,
the display of temperature will close after 30 seconds.
When selecting COOLING/DRY operation with SLEEP mode, the set temperature will
be raised by 1
℃
after 1 hour later and by 2
℃
2 hour later.
When selecting HEATING operation with SLEEP mode, the set temperature will be
dropped by 1
℃
1 hour later and 2
℃
2 hours later.
After the System operates in SLEEP mode for 8 hours, it will stop automatically.
4.
8
EMERGENCY Operation
When the EMERGENCY switch is pressed one time, COOLING mode is selected and if the
switch press again within 3s, HEATING mode selected, while press third times, the unit will
switch off.
When the remote controller missing, failed or the batteries run down, press the
EMERGENCY Operation switch on front of the indoor unit for function test.
NOTE: Do not press the EMERGEMCY Operation switch during normal operation.
4.
9
AUTO-RESTART Function (Option)
While air conditioner is operating in one mode, all of its operation data, such as working
mode, preset temperature etc. would be memorized into EEPROM. If power supply cut off
due to reasons and recover again, the AUTO-RESTART function will set synchronously
and the air conditioner would work at the same mode as before.