Installation, Operation & Maintenance Manual                                                                  Merlin Detector i-S 

 

 

 Iss: 1  170322 

7  

Wiring: Alarm Relays 

These are volt free connections to a BMS (building management systems) or Merlin panel to send an alarm signal 

upon pre/alarm levels of gas. Max 1A load @ 12/24V DC or AC. 

 
If you are connecting detector(s) via a GDP panel you will need to use the [C/L]

 

terminal as an alarm relay. A relay will 

change state when in alarm or pre-alarm when gas is detected and if wired/configured to do so.  

These terminals can be used in conjunction with other external relays that affect other devices and controls such as 

purge fans and audible alarms etc. 

 

Alarm Relay Setting Switch 

 Latch On/Off 

 

It is recommended to leave the alarm relay setting switch on, particularly for flammable detectors! 

 

The switch is left on as a factory set condition! 

 
This switch is used to latch/unlatch an alarm relay. 
When turned on the Detector relay will latch permanently on (until Reset) in the event of the detector detecting gas 
and entering an alarm state.  

 
The detector will indicate a red dot on the screen when the alarm relay has latched. 
The alarm will beep every 10 seconds to alert the user that the detector entered an alarm state. 
 
To reset the Detector, press and hold the touch button for ~3 seconds. 
 

Wiring: 0-10V Analogue Output 

This connection is used to regulate external fan speed controllers (supplied separately). Connect direct to fan speed 

controllers or via your Merlin panel [0-10V] terminal if available. 0-10V output is driven by the status of gas

 

concentrations detected. 

 

0-10 Volt Output Range 

Gas & Measurement 

 

1V 

2V 

3V 

4V 

5V 

6V 

7V 

8V 

9V 

10V 

NG/CH

4

 

Methane: %LEL

 

1%  

2%  

3%  

4%  

5%  

6%  

7%  

8%  

9%  

10%  

LPG 

Propane: %LEL

 

H

2

 

Hydrogen: %LEL

 

CO 

Carbon Monoxide: ppm

 

30  

60  

90 

120 

150 

180 

210 

240 

270 

300 

See section: 

CO2 Selection Switches

 

CO

 

0-5000ppm Range 

Carbon Dioxide: ppm 

500 

1000 

1500 

2000 

2500 

3000 

3500 

4000 

4500 

5000 

CO

2

 

 

0-2000ppm Range 

Carbon Dioxide: ppm 

200 

400 

600 

800 

1000 

1200 

1400 

1600 

1800 

2000 

 

CO

2

 Selection Switches 

These switches configure alarm thresholds of CO

2

 (carbon dioxide) only. 

There is a legend on the board for quick reference.  

X = OFF / O = ON 

 

S1 

S2 

Pre-Alarm 

Alarm 

S3 

0-10V Output Range 

 O 

2800ppm 

4500ppm 

0 - 5000ppm 

 X 

1500ppm 

2800ppm 

1200ppm 

1500ppm 

0 - 2000ppm (Default) 

800ppm (Default) 

1000ppm (Default) 

 

Summary of Contents for Merlin Detector i-S

Page 1: ...170322 1 Merlin Gas Detector i S Installation Operation Maintenance Please read this manual carefully and retain for future use For specific requirements that may deviate from the information in this...

Page 2: ...Power Input 6 Wiring Alarm Relays 7 Alarm Relay Setting Switch Latch On Off 7 Wiring 0 10V Analogue Output 7 CO2 Selection Switches 7 Audible Buzzer Switch 8 Factory Set Condition 8 Operation 8 Initia...

Page 3: ...nufacturer s Warranty Warranty coverage The manufacturer warrants to the original consumer purchaser that this product will be free of defects in material and workmanship for a period of three 3 years...

Page 4: ...is also relevant to toxic gas detection Recommended heights may vary based on air flow and temperature conditions in addition to the proposed application and location Locations for detectors will var...

Page 5: ...wo gang electrical box Restrain the hazardous live wiring from accidental loosening to prevent wires from moving after installation and touching parts of opposite polarity or at low voltages Isolate t...

Page 6: ...d any warranty Wiring Power Input Standalone Power 12 24V power inputs can be either AC or DC Terminals are pluggable type to ease connections Merlin GDP Power Connection Power is supplied via the GDP...

Page 7: ...a red dot on the screen when the alarm relay has latched The alarm will beep every 10 seconds to alert the user that the detector entered an alarm state To reset the Detector press and hold the touch...

Page 8: ...tors are shipped pre calibrated and configured Buzzer On Off Switch On Alarm Relay Setting Switch On CO2 Selection Pre Alarm 800ppm Alarm 1000ppm 0 2000ppm 0 10V Output Range Operation Initial Power U...

Page 9: ...rly using a slightly damp cloth Never use detergents or solvents to clean your device Never spray air fresheners hair spray paint or other aerosols near the device Never paint the device Paint will se...

Page 10: ...uld always be given to any applicable national local law and industry codes Generally the gas concentration should be greater than the alarm threshold of the device Always remove the regulator valve a...

Page 11: ...Evaluated Operating 10 50 C 20 90 RH non condensing Storage 0 50 C 30 80 RH no condensation Altitude Rating 2000m Wiring Typical Min 2 5mm2 75 C min Tinned copper Approvals Electrical Safety and Elec...

Page 12: ...om any unforeseen damage caused by transit installation Every effort is made to ensure the accuracy of this document however S S Northern can assume no responsibility for any errors or omissions in th...

Reviews: