background image

Installation & Operation Manual                                                                         Merlin Gas Detector 

 

 

Rev: 18   03-20

 

6  

 

   Trouble Shooting 

 

Fault. 

Possible Cause/Correction. 

Detector not responding. 

o

 

Incorrect wiring. 

o

 

Exceeded zone detector capacity. 

o

 

Sensor exceeded expected life span. 

LED flashing and alarm beep. 

o

 

Sensor fault. Contact your supplier 

 

   Specification 

 

Product:

  Gas Detector 

Model:  CO / NG / LPG / H2  

Visual Indicators 

Power (Green),  
Low gas concentration (Amber) 
High gas concentration (Red) 

Initial Stabilisation Time 

60 Seconds approx. 

Power Input Voltage  

12-24V / 7-30VDC 

Relay Output  

0.5A Switching Current (resistive load). 

Consumption 

90mA Max (24V) 

Accuracy @ 25°C / 77°F 

± <10% 

Fuses 

N/A 

Operating Temp 

0 – 50°C  30-85%RH Non-Condensing 

Test Conditions 

25° ±5°C  /  77° ±41°F 

Audible Alarm Buzzer (dB) 

65 dB (300mm distance in quiet conditions)

 

 

 

Gas Sensor Type 

NG: Semi-conductor 

Measuring Range 

NG: 300-10,000 PPM 

 

LPG:  Semi-conductor 

 

LPG: 300-10,000 PPM 

 

H: Semi-conductor 

 

H: 100-10,000 PPM 

 

CO: Electro-Chemical 

 

CO: 10-10,000 PPM 

 

 

 

 

 

 

 

 

Gas Level Pre- Alarm  

NG: 8% LEL  

Gas Level Alarm  

NG: 10% LEL 

 

LPG: 8% LEL 

 

LPG: 10% LEL 

 

H: 8% LEL 

 

H: 10% LEL 

 

CO: 20 PPM 

 

CO: 30 PPM @ 2 HOURS 

 

O2: 18.5 – 19.5% 

 

50 PPM @ 1 HOUR 

 

 

 

100 PPM @ 10 MINS 

Expected Sensor Life 

NG: 10 Years 

 

300 PPM @ 1 MINS 

 

LPG: 10 Years 

 

 

 

H: 10 Years 

 

 

 

CO: 5 Years 

 

 

 

 

 

 

 

 

 

 

Dimensions

 (H x W x D)

 

95.3 x 133 x 38mm / 3.75 x 5.23 x 1.5” 

 

 

 
 
 
 
 
 

Summary of Contents for Merlin CO Detector

Page 1: ...we supply a full range of remote gas detectors including carbon monoxide CO natural gas NG and liquid petroleum gas LPG that are compatible with our range of Merlin control panels The information con...

Page 2: ...tion and Positioning 3 Fixing 4 Board Overview 4 Wiring the Detector 5 Audible Alarm Switch 5 Testing the system 5 Trouble Shooting 6 Specification 6 OPERATION 7 First Power Up 7 Service Maintenance 7...

Page 3: ...Positioning Locations for detectors will vary based on the intended application and target gas they should be located near identified sources of a potential gas leaks pockets where hazardous gas could...

Page 4: ...the wall surface is flat to prevent base distortion 3 There is a pre fractured area for cable entry provided on the inside of the rear cover which may be cut away as required 4 After executing the mo...

Page 5: ...ms etc Audible Alarm Switch There is a switch on the Detector circuit board The user can choose whether to have an audible alarm when dangerous gas levels are detected The alarm will continuously soun...

Page 6: ...put 0 5A Switching Current resistive load Consumption 90mA Max 24V Accuracy 25 C 77 F 10 Fuses N A Operating Temp 0 50 C 30 85 RH Non Condensing Test Conditions 25 5 C 77 41 F Audible Alarm Buzzer dB...

Page 7: ...any accumulated dust from the outer enclosure once a month NEVER use detergents or solvents to clean your device this may permenantly or temporarily damage the gas sensing elements NEVER spray air fre...

Page 8: ...sually appear in good order but its sensitivity can be inhibited by external factors Dust humidity temperature fluctuations cleaning products contaminants or sensor drift ageing can cause a decline in...

Page 9: ...Installation Operation Manual Merlin Gas Detector Rev 18 03 20 9 NOTES...

Page 10: ...Installation Operation Manual Merlin Gas Detector Rev 18 03 20 10 NOTES...

Page 11: ...nty coverage The manufacturer warrants to the original consumer purchaser that this product will be free of defects in material and workmanship for a period of three 3 years from date of purchase or o...

Page 12: ...anisation Stamp Signature of the installer Replacement Date For all correspondence S S Northern Head Office Tel 44 0 1257 470 983 Fax 44 0 1257 471 937 www snsnorthern com info snsnorthern com South E...

Reviews: