6
Coil section
In this product range there are not two sides of connections. All units are supplied with
batteries on the right side (viewed from the front). Once on site it is possible to change
the connections side. See point 7.4.2.
Water coils
In the section it can be included one cooling coil or two water coils (one heating or one
cooling coil). All units have condensate drip tray made for stainless steel AISI 304 with
condensate outlet on the side of the equipment.
UTV-ECOWATT
Model
Maximum airfl ow
(m
3
/h)
Fans
Cold / Direct
expansion coil
(DX)
Hot water
coil
Quan-
tity
Supply
voltage
Rpm
Motor
power
(kW)
Max. abs.
current
(A)
2
2150
1950
1
230/I/50
2850
0,45
2
3
4400
3750
2
230/I/50
2850
2 x 0,45kW
3,9
6
6000
5600
2
230/I/50
2830
2 x 0,85 kW
7,2
8
8000
7600
2
400/III/50
2600
2 x 1 kW
3,6
Model
Air fl ow
(m
3
/h)
Cooling Power
(kW)*
Water
(7ºC/12ºC)
Water
(8ºC/13ºC)
Water
(9ºC/14ºC)
UTV-2
1.650
8
6,9
5,8
UTV-3
3.000
15,8
13,6
11,3
UTV-6
4.900
25,4
22
18,2
UTV-8
6.300
33,3
28,9
24,2
* Air inlet temperature: 25ºC 50%
Model
Air fl ow
(m
3
/h)
Cooling Power
(kW)*
Water
(50ºC/45ºC)
Water
(45ºC/40ºC)
UTV-2
1.650
13,7
11,4
UTV-3
3.000
26,4
21,9
UTV-6
4.900
43
35,8
UTV-8
6.300
55,1
45,8
* Air inlet temperature: 18ºC 50%