The siphon supplied with the RHE unit is designed for a pressure available on the supply system of 300
Pa maximum. Pass the threaded pipe through the condensates dip tray and the bottom of the RHE unit
and then tighten the nut below. Fit the siphon in the threaded pipe.
The minimum drain slope must be 5 / 1000.
To size a siphon: H min (mm) = 4 + pressure drop of the air injection network (da Pa).
Thermostat change over (reversible water coil DFR version HD only)
A thermostat change over (THCO PROBE) is installed on the hydraulic network and connected to the
unit’s electrical box. It allows reversing the mixing valve control in installations with only one coil according
to the temperature of fluid detected in the valve inlet.
Technical data
Inverter contact output: 240 VAC, 3 A
AC contact calibration open: 30 ± 4°C
AC contact closed: 15 ± 4 °C
Attachment by spring on the pipe
3-wire electric connection length: 1 500 mm
Degree of protection: IP 65
Valves connection
4.2
Motorized 3-way valves are not delivered mounted. They are proposed as accessories by S&P.
Respect the positioning of the mixing valve on the network and the water inlet and outlet directions.
Electric connection on the RHE box: see subsection “Inputs – Outputs”
RED (hot)
BROWN (hot)
BLACK (cold)