S&P LPD Installation, Operation And Maintenance Manual Download Page 5

REPAIR PARTS:

3.  Fan Blades – Repair of individual fan blades or propeller assemblies is not recommended. Contact factory 

with blade size, number of blades, bore size, motor HP, air flow direction, rotation, fan RPM or sheave sizes 

and any order/tag information that is available for replacement.

4.  Misc. Parts – Not available from local trade channels should be returned for repair or replacement. Be sure to 

obtain return tags or authorization before shipment.

5.  Electric Motors – Repair or replacement of motors is normally performed by a repair station authorized by the 

manufacturer. Contact your representative or the factory for locations nearest to you. 

DO NOT

 ship motor to 

the factory without specific authorization. 

FAN TROUBLE-SHOOTING CHART

PROBLEM

POSSIBLE CAUSES

Excessive Vibration

Propeller, wheel or sheaves loose on shaft

Out of balance propeller

Excessive buildup of dirt/dust on propeller

Bent shaft

Weak mounting base for fan

Fan mounting bolts loose

Loose or worn bearings 

Bearing or drive misalignment

Structures not crossbraced (wall fans)

Curb not flat and level

Excessive Horsepower

Static pressure higher than design

Wheel or propeller rotating in wrong direction

Fan speed higher than design

Too Little Air

Restricted fan inlet or outlet

Filters are dirty or clogged

Wheel or propeller rotating in the wrong direction

System is more restrictive (more static pressure) than expected

Fan speed lower than design

Inlet or Outlet screens clogged

Too Much Air

Filters not in place

Fan speed higher than design

System is less restrictive (less static pressure) than expected

Fan Does Not Operate

Wrong voltage

Electricity turned off or note wired properly

Blown fuses

Overload protector has broken circuit

Excessive Noise

Propeller, wheel or sheaves loose

Accumulation of material on propeller

Worn or corroded propeller

Wheel or propeller out of balance

Wheel or propeller hitting housing

Bent shaft

Loose fan mounting bolts

Rattle of components in high velocity airstream

Electrical noise

Noise from high velocity air system

Vibrating parts not isolated from building

Vibrating duct work

4

Summary of Contents for LPD

Page 1: ...f Sidewall and Roof Downblast READ AND SAVE THESE INSTRUCTIONS The purpose of this manual is to aid in the proper installation and operation of fans manufactured by Soler Palau USA These instructions are intended to supplement good general practices and are not intended to cover detailed instruction procedures because of the wide variety and types of fans manufactured by Soler Palau USA ...

Page 2: ...n housing only DO NOT LIFT FANS BY THE MOTOR BASE PROP WHEEL OR FLANGES Roof ventilators should be lifted by using straps around the fan housing or base only Spreader bars should also be used to avoid damage to stack caps or hoods DO NOT LIFT ROOF VENTILATORS BY THE STACK CAP OR HOOD On hooded units disassemble the stack from hood when lifting Upblast models may be lifted assembled STORAGE If fans...

Page 3: ...iring clear of rotating or moving parts 10 WARNING Before starting the fan turn the wheel to assure it rotates freely If needed adjust the wheel shaft motor position as required to achieve necessary clearances 11 WARNING Check all setscrews and keys Tighten as necessary prior to fan startup 12 On roof units anchor the fan securely to the curb Anchoring through the vertical portion of the curb cap ...

Page 4: ...t blade pitch or fan RPM If sheaves are replaces use only sheaves of identical size and type 7 During the first few months of operation it is recommended that the setscrews be checked to assure they are tight 8 The rotating wheel or propeller requires particular attention in most applications since materials in the air being handled can build up on the blades to cause destructive vibration and may...

Page 5: ...ts loose Loose or worn bearings Bearing or drive misalignment Structures not crossbraced wall fans Curb not flat and level Excessive Horsepower Static pressure higher than design Wheel or propeller rotating in wrong direction Fan speed higher than design Too Little Air Restricted fan inlet or outlet Filters are dirty or clogged Wheel or propeller rotating in the wrong direction System is more rest...

Page 6: ...0 600005 1 3 4 2 5 6 7 Replacement Parts Model LPD Model LPD Cover Dome 1 Welded Base 2 Motor Bracket w Isolators 2 Required 3 Part Part Part 6 101101 101107 101103 105744 8 101101 101102 101103 105744 Model LPD Disconnect Switch 6 1 Speed Control 6 2 Motor 115V or 230V 50 60Hz Wheel 1 PC Assembly 7 Capacitor 8 Conduit Assembly Conduit compression fitting sealing nut 9 Part Part Part Part Part 6 2...

Page 7: ... the products and parts covered by this proposal acknowledgement order or from the performance or breach of any contract pertaining to such sale or purchase or from the design manufacture sale delivery resale installation technical direction of installation inspection repair operation or use of any products or parts covered by this proposal acknowledgement order or furnished by seller shall in no ...