START-UP & OPERATION
MEASURING AIRFLOW
EQUIPMENT REQUIRED
• A magnehelic gauge or other device capable of
measuring 0 to 1.5 in. water of differential pressure.
• 2 pieces of natural rubber latex tubing, 1/8" ID,
1/16" Wall works the best.
NOTE
: Be sure to
remove cap from pressure port before inserting
tubing. Ensure tubing is well seated in pressure
ports.
NOTE:
The tubing should extend in the
pressure port approx. 1 inch.
DIFFERENTIAL STATIC ACROSS CORE DSP VS. CFM
DSP
0.20
0.30
0.40
0.50
0.60
0.70
0.80
TRC1600
Fresh Air (FA)
CFM
570
850
1130
1420
1700
1980
2270
Room Air (RA)
CFM
540
810
1080
1350
1620
1890
2170
F3
AIRFLOW DIAGRAM TRC1600
• The individual differential static pressures (DSP)
can be measured using the installed pressure
ports located in the front of the units core
access doors.
NOTE:
These ports have been
carefully located on the unit as to give you the
most accurate airflow measurement. NOTE: Do
not relocate pressure ports.
• To read SCFM of Fresh Air (FA) install the “high”
pressure side (+) of your measuring device to
the Outside Air (OA) port and the “low” pressure
side (-) to the Fresh Air (FA) port.
• To read SCFM of Room Air (RA) install the “high”
pressure side (+) of your measuring device to
the Room Air (RA) port and the “low” pressure
side (-) to the Exhaust Air (EA) port.
• Use the reading displayed on your measurement
device to cross reference the CFM output using
the conversion chart.
NOTE:
Be sure to replace
cap into pressure port when air flow measuring
is completed.
CROSS CORE STATIC PRESSURE MEASUREMENT INSTRUCTIONS
OA
RA
EA
FA
Pressure
Ports (4) Typ.
The proper operating airflow
range for this model is 500 -
2200 CFM.
CAUTION