background image

ERV

TRC1600

13

WWW.SOLERPALAU-USA.COM  

INSTALLATION, OPERATION AND MAINTENANCE MANUAL 

1.800.961.7370

CONTROL WIRING  
SCHEMATICS

INSTALLATION

Make sure the control provides 
no voltage or current at its output 
terminals.

CAUTION

Supply only 24VAC (not VDC) from 
a Class II Power Source.

CAUTION

NOTE: 

The simplified schematics below show only the relevant portions of the low-voltage  

control circuit in the ERV unit and representational external control approaches. See the complete  
unit wiring schematics elsewhere in this manual.

CONTROL WIRING EXAMPLES BY TYPE OF APPLICATION

A.

 

 Single 2-wire Control, unpowered:

  Use schematic below if the control requires no power from the 

unit to operate and acts like a simple on/off switch. The control must not supply any power to the ERV 
unit. Install jumper (provided) between terminals 2 & 3. Connect the control’s contacts to terminals  
1 & 4 to operate the ERV’s Isolation Relay for OA/FA Blower. Install jumper between terminals 4 & 5 to 
operate the ERV’s Isolation Relay for the RA/EA Blower.   

C.  Control Sending 24VAC “On” Signal (from an external power source) to ERV:

 Make sure jumper 

is NOT installed between Terminals 2 & 3. Now you safely can apply 24VAC to the Terminals 3 & 4 to 
operate the ERV’s Isolation Relay for OA/FA Blower. Install jumper (provided) between terminals 4 & 5 
to operate the ERV’s Isolation Relay for the RA/EA Blower.  

B.  Single 2-wire Control on separate Power Supply, no power present at Control Output:

  

Wire as shown for the Single 2-wire control (A. above). 

D.  Control operating on Unit’s 24VAC Power Supply:

 24VAC power is available at the Terminals 1 & 2. 

CAUTION: 

external control system should not draw more than 8VA. Install jumper (provided) between 

terminals 2 & 3. 
 
Connect the switched output of the Control to Terminal 4 to operate the ERV’s Isolation Relay for OA/FA Blower. 
Install jumper between terminals 4 & 5 to operate the ERV’s Isolation Relay for the RA/EA Blower.  

D

AN EXTERNAL CONTROL USING  

UNIT’S 24VAC POWER SUPPLY

C

24VAC FROM AN EXTERNAL SOURCE

A

A SWITCH OR NON-POWERED CONTROL  

USING UNIT’S 24VAC POWER SUPPLY

Summary of Contents for ERV TRC1600 P1

Page 1: ...INSTALLATION OPERATION MAINTENANCE MANUAL ENERGY RECOVERY VENTILATOR TRC1600 WWW SOLERPALAU USA COM...

Page 2: ...the very highest standards of customer service is key to our company strategy Soler Palau Ventilation Group is the world s leading fan manufacturer It celebrated its 50th anniversary in 2001 Soler Pa...

Page 3: ...xlsx 2 Cores IOM 30 50 70 90 500 1000 1500 2000 Effectiveness Airflow CFM CORE PERFORMANCE ELECTRICAL DATA Standard Electrical Specifications HP Volts HZ Phase FLA per motor Min Cir Amps Max Overcurre...

Page 4: ...ERV TRC1600 4 WWW SOLERPALAU USA COM INSTALLATION OPERATION AND MAINTENANCE MANUAL 1 800 961 7370...

Page 5: ...de of the building should be at least ten feet apart to avoid cross contamination The exhaust outlet should not dump air into an enclosed space or any other structure The inlets and outlets should be...

Page 6: ...TIONS See figure F2 for examples of some common installation approaches F2 Common Installation Approaches www renewaire com 800 627 4499 support renewaire com www renewaire com 800 627 4499 support re...

Page 7: ...ace Fresh Air from the TRC1600 often can be ducted into an existing HVAC air distribution system Sometimes however it is more practical to install a separate distribution system for the Fresh Air The...

Page 8: ...ct switch may be required to de energize the equipment for servicing 2 This installation manual shows the suggested installation method Additional measures may be required by local codes and standards...

Page 9: ...ws should not penetrate further than into case Make sure your fasteners don t damage internal parts Do not screw into the door Note that leveling legs supplied with TRC1600 can be removed and replaced...

Page 10: ...upply M Supply Fan Input Power 115 VAC 1 Phase 208 230 VAC 1 Phase L1 L2 L3 GND Transformer COM 24V Relay 24 VAC 13 14 8 12 4 Exhaust Contactor Overload 24 VAC A1 A2 95 96 1L1 3L2 5L3 2T1 4T2 6T3 Supp...

Page 11: ...upply M Supply Fan Input Power 208 230 VAC 3 Phase 460 VAC 3 Phase L1 L2 L3 GND Transformer COM 24V Transformer COM 24V Contactor Overload 24 VAC A1 A2 95 96 1L1 3L2 5L3 2T1 4T2 6T3 Supply Relay 24 VA...

Page 12: ...nit consult the wiring schematics and connect the external power only to the specified terminals in order to avoid damaging the unit or external controls Connect only CLASS II power to the control ter...

Page 13: ...ll jumper between terminals 4 5 to operate the ERV s Isolation Relay for the RA EA Blower C Control Sending 24VAC On Signal from an external power source to ERV Make sure jumper is NOT installed betwe...

Page 14: ...r make sure the polarity of each wire connected to Terminal 3 is the same G Control System Operating Isolation Dampers with End Switches Use Isolation Dampers with electrically separate end switches T...

Page 15: ...the room is closer to room temperature than to the outside temperature energy is being recovered OPERATING CONTROLS A wide variety of control schemes may be selected by the engineer installer or owne...

Page 16: ...at the contactors are closed and or that the Overload Relays have tripped The Overload Relay output contacts 95 96 must remain in series with the low voltage control circuit Altering this will create...

Page 17: ...static pressures DSP can be measured using the installed pressure ports located in the front of the units core access doors NOTE These ports have been carefully located on the unit as to give you the...

Page 18: ...nit shipped with MERV 8 Filters Minimum recommended effectiveness MERV 6 Pleated_Filter_PD_APR16 2 20x20x2 MERV 8 IOM 0 0 0 1 0 2 0 3 0 4 500 1000 1500 2000 Clean filter Pressure Drop in w g Unit Airf...

Page 19: ...ERV TRC1600 19 WWW SOLERPALAU USA COM INSTALLATION OPERATION AND MAINTENANCE MANUAL 1 800 961 7370 SERVICE PARTS MAINTENANCE TRC1600 www renewaire com 800 627 4499 support renewaire com...

Page 20: ...tall securing screw BLOWER INSPECTION Inspect Blowers every time you change the filters 1 Confirm bearings are still secure to blower shaft It should not be possible to move the blower shaft back and...

Page 21: ...ERV TRC1600 21 WWW SOLERPALAU USA COM INSTALLATION OPERATION AND MAINTENANCE MANUAL 1 800 961 7370 NOTES...

Page 22: ...ERV TRC1600 22 WWW SOLERPALAU USA COM INSTALLATION OPERATION AND MAINTENANCE MANUAL 1 800 961 7370 NOTES...

Page 23: ...ERV TRC1600 23 WWW SOLERPALAU USA COM INSTALLATION OPERATION AND MAINTENANCE MANUAL 1 800 961 7370 NOTES...

Page 24: ...8 USA 800 961 7370 FAX 800 961 7379 6393 POWERS AVE JACKSONVILLE FLORIDA 32217 USA WWW SOLERPALAU USA COM CANADA 416 744 1217 FAX 416 744 0887 5600 AMBLER DRIVE MISSISSAUGA ON L4W 2K9 CANADA WWW SOLER...

Reviews: