6.4. RANGE SPECIFICATIONS
D Models: without heater battery
Model
Complete unit
Fan
Weight
(kg)
Air
connections
diameter
(mm)
Nominal
airfl ow
(m
3
/h)
Effi ciency*
(%)
Electrical
supply
Max.
abs.
power
(kW)
Maximum
current
(A)
Speed
(r.p.m.)
Maximum
current
(A)
CADB-HE D 04 PRO-REG
200
450
87
1/230V, 50Hz
0,2
2,2
3700
0,95
147
CADB-HE D 08 PRO-REG
250
800
86,4
1/230V, 50Hz
0,4
2,9
2650
1,3
183
CADB-HE D 12 PRO-REG
315
1.200
85,3
1/230V, 50Hz
0,95
3,5
2550
1,6
190
CADB-HE D 16 PRO-REG
315
1.600
85,5
1/230V, 50Hz
0,95
4,3
2845
2,0
235
CADB-HE D 21 PRO-REG
400
2.100
86,7
1/230V, 50Hz
0,9
4,7
1580
2,2
333
CADT-HE D 33 PRO-REG
400
3.300
85,9
3+N/400V, 50Hz
2,2
4,3
2600
2,0
420
CADB-HE D 40 PRO-REG
450
4.000
86,8
1/230V, 50Hz
2,5
15,1
2340
7,4
597
CADB-HE D 54 PRO-REG
500
5.400
87,1
1/230V, 50Hz
3,4
20,3
2110
10
730
* Humid efficiency referring to nominal airflow, outdoor conditions (-5ºC / 80% RH) and indoor (20ºC / 50% RH)
DC Models: with built-in hot water coil
Model
Complete unit
Fan
Hot water coil
Weight
(kg)
Air
connections
diameter
(mm)
Nominal
airfl ow
(m
3
/h)
Effi ciency*
(%)
Electrical
supply
Max.
abs.
power
(kW)
Maximum
current
(A)
Speed
(r.p.m.)
Maximum
current
(A)
Heat
power
T.water
80/60ºC
(kW)
Heat
power
T.water
50/45ºC
(kW)
CADB-HE DC 04 PRO-REG
200
450
87,0
1/230V, 50Hz
0,2
2,2
3700
0,95
2,7
1,6
149
CADB-HE DC 08 PRO-REG
250
800
86,4
1/230V, 50Hz
0,4
2,9
2650
1,3
5,1
3,1
186
CADB-HE DC 12 PRO-REG
315
1.200
85,3
1/230V, 50Hz
0,95
3,5
2550
1,6
7,1
4,3
193
CADB-HE DC 16 PRO-REG
315
1.600
85,5
1/230V, 50Hz
0,95
4,3
2845
2,0
8,6
5,3
239
CADB-HE DC 21 PRO-REG
400
2.100
86,7
1/230V, 50Hz
0,9
4,7
1580
2,2
12,6
7,8
338
CADT-HE DC 33 PRO-REG
400
3.300
85,9
3+N/400V, 50Hz
2,2
4,3
2600
2,0
18,2
11,1
427
CADB-HE DC 40 PRO-REG
450
4.000
86,8
1/230V, 50Hz
2,5
15,1
2340
7,4
23,9
14,4
606
CADB-HE DC 54 PRO-REG
500
5.400
87,1
1/230V, 50Hz
3,4
20,3
2110
10
32,1
19,5
742
* Humid efficiency referring to nominal airflow, outdoor conditions (-5ºC / 80% RH) and indoor (20ºC / 50% RH)
DI Models: with built-in electric heater battery
Model
Complete unit
Fan
Electrical heater
battery
Weight
(kg)
Air
connections
diameter
(mm)
Nominal
airfl ow
(m
3
/h)
Effi ciency*
(%)
Electrical
supply
Max.
abs.
power
(kW)
Maximum
current
(A)
Speed
(r.p.m.)
Maximum
current
(A)
Power
(kW)
Maximum
current
(A)
CADB-HE DI 04 PRO-REG
200
450
87,0
1/230V, 50Hz
1,2
6,7
3700
0,95
1
4,5
148
CADB-HE DI 08 PRO-REG
250
800
86,4
1/230V, 50Hz
2,4
12,0
2650
1,3
2
9,1
185
CADB-HE DI 12 PRO-REG
315
1.200
85,3
1/230V, 50Hz
4,0
14,9
2550
1,6
3
11,4
192
CADB-HE DI 16 PRO-REG
315
1.600
85,5
1/230V, 50Hz
4,5
20,2
2845
2,0
3,5
15,9
237
CADB-HE DI 21 PRO-REG
400
2.100
86,7
3+N/400V, 50Hz
6,9
13,8
1580
2,2
6
9,11
336
CADT-HE DI 33 PRO-REG
400
3.300
85,9
3+N/400V, 50Hz
9,7
15,7
2600
2,0
7,5
11,4
424
CADB-HE DI 40 PRO-REG
450
4.000
86,8
3+N/400V, 50Hz 11,5
28,8
2340
7,4
9
13,7
602
CADB-HE DI 54 PRO-REG
500
5.400
87,1
3+N/400V, 50Hz 15,4
38,5
2110
10
12
18,2
737
* Humid efficiency referring to nominal airflow, outdoor conditions (-5ºC / 80% RH) and indoor (20ºC / 50% RH)
Summary of Contents for CADB/T-HE PRO-REG Series
Page 1: ...CADB T HE PRO REG EN...
Page 2: ......
Page 63: ...63 23 WIRING DIAGRAMS 23 1 MAIN UNIT...
Page 64: ...64...
Page 65: ...65...
Page 66: ...66...
Page 67: ...67...
Page 68: ...68...
Page 69: ...69...
Page 70: ...70 23 2 REWIRING TO MANAGE EXTERNAL MODULES Accessories...
Page 71: ...71...