![S&P CADB/T-HE PRO-REG Series Instruction Manual Download Page 12](http://html1.mh-extra.com/html/sandp/cadb-t-he-pro-reg-series/cadb-t-he-pro-reg-series_instruction-manual_3141826012.webp)
12
ENGLISH
Avoid condensations in electrical cabinet
In units located in outdoor installation where the heat recovery units stop during the night or
during long intervals of time, it is necessary to:
a) Install isolation dampers in air inlet and air outlet.
b) Add anticondensation devices in the electrical cabinet as: cabinet heating elements that pre-
vent condensation formation on cabinet surfaces and electronic components.
6.2. DIMENSIONS AND FREE SPACE FOR MAINTENANCE
a) Horizontal versions of CADB/T HE 04 to 21 (False ceiling installation)
Distances for maintenance in installations with access from the lateral panels
Conf. LH
Conf. RH
Access to fi lters and heat exchanger
Access to control panel, fans and coils/battery
connections (DI/DC versions)
Distances for maintenance in installations with access from the inferior panels
L
Conf. LH
Conf. RH
Access to fi lters and heat exchanger
Access to fi lters and fan
Access to control panel, fans and coils/battery
connections (DI/DC versions)
Access to heat exchanger
Model
W
H
L
A
B
C
D
Ø
E
F
Weight
(kg)
04
760
375
1520
400
400
700
350
200
350
920
147
08
910
425
1750
450
400
860
400
250
400
950
183
12
1050
425
1700
500
400
1000
400
315
400
900
190
16
1240
450
1950
600
500
1190
425
315
400
1150
235
21
1640
550
2300
800
700
1590
525
400
500
1300
333
33
1640
650
2300
800
700
1590
625
400
500
1300
420
Summary of Contents for CADB/T-HE PRO-REG Series
Page 1: ...CADB T HE PRO REG EN...
Page 2: ......
Page 63: ...63 23 WIRING DIAGRAMS 23 1 MAIN UNIT...
Page 64: ...64...
Page 65: ...65...
Page 66: ...66...
Page 67: ...67...
Page 68: ...68...
Page 69: ...69...
Page 70: ...70 23 2 REWIRING TO MANAGE EXTERNAL MODULES Accessories...
Page 71: ...71...