background image

Calibration Procedure
Use certified precision mixtures to adjust the sensitivity of the sensor due to normal wear and aging and guarantee that the designed alarm 
set points are respected.  It will also indicate the general condition of a sensor that is due for replacement.  So called “automatic calibration” 
or “self-test” will not provide this level of security.

Calibration Procedure for Electro-chemical and Catalytic sensors (CO NO2 CH4 NH3 CL2)
1.  Use certified bottled calibration gas mixtures only.  Ensure that sensors are powered on for a minimum of the break-in period for the 

sensor.  For electro-chemical type sensors, this is only a few minutes.

2.  Press the right arrow to enter settings
3.  Press the 

 and 

 at the same time to enter calibration mode. SAZ (sensor A zero) will display and the current gas reading on the top 

line

4.  Inject bottled zero gas into first sensor.  Use a flow rate of 0.1 LPM to 1 LPM.  The gas fitting to sensor should not be sealed tight.  If it is 

the pressure will increase and distort the reading (high).

5.  Adjust gas reading to zero with the 

 and 

 buttons

6.  Press

 ↑

 and 

 at the same time to save.

7.  Press 

→ 

 the display will show SAS (sensor A span) and the current gas reading

8.  Inject bottled span gas into first sensor and wait until the gas reading stops going up.  The span gas should must be within the range of 

sensor’s scale.

9.  Adjust the reading to match the concentration in the bottle
10.  Press 

 and 

 at the same time to save

11.  If second sensor installed press

 → 

and repeat steps 4 to 10 for sensor B

12.  Press left arrow several times to return to settings and home.

Calibration Procedure for Refrigerant (type 13, 20) and VOC (type 01) sensors

1.0 Use certified bottled calibration gas mixed with air only, not nitrogen. Ensure that sensors are powered on for a minimum of the break-in 
period for the sensor.  For these types sensors, this is two days.
2.0 Inject bottled span gas
3.0 Adjust the blue potentiometer on the module to set the sensor reading displayed to that of the bottle mix.  Do not change the factory 
calibration constants in calibration mode as above.
4.0 Remove span gas mix and supply air.  Sensor will return to zero.
5.0 If sensor does not return to zero, it needs replacement

BACnet Network Configuration

Setting 46

Bacnet Mode select
0 = communication disabled
1 = communication enabled
2 = communication enabled and display all 
sensors on CAN network

0, 1, 2

Default 0

Setting 47

BMA MAC address

0-127

0

Setting 48

Baud rate

0 = 9600
1 = 19200
2 = 38400
3 = 76800

3

Setting 53

Max Master

1-127

127

Setting 54

Diagnostic tool to test MSTP 
communication. Format XXXYYZZ where 
YY= ID of device that passed token to 
current sensor and  YY = ID if device that 
received token.

Setting 70

Device ID

4,194,304

50,000+BMA

Summary of Contents for 6002

Page 1: ...Gas Detectors READ AND SAVE THESE INSTRUCTIONS The purpose of this manual is to aid in the proper installation and operation of fans manufactured by Soler Palau USA These instructions are intended to supplement good general practices and are not intended to cover detailed instruction procedures because of the wide variety and types of fans manufactured by Soler Palau USA ...

Page 2: ......

Page 3: ...ated plug and play sensor modules Impact resistant water resistant enclosure Specifications Supply 24 vac 50 60 hz 17 28 vac 0 21 amps 5 va Relays 1 or 2 SPDT 5 amp 125 vac non inductive On delay 0 999 seconds 16 minutes Off delay 0 999 seconds 16 minutes Operating temperature 20º C to 50º C 4º F to 122º F For indoor use Flame resistant Polycarbonate ABS enclosure rated UL94 V0 5VB and 5VA Standar...

Page 4: ... configuration Make all chain connections at the sensors to avoid T connections 6 Move the end of line jumper the one above terminal 1 1 12 to the on position UP on the first sensor or controller on the chain and the last sensor controller on the chain A controller can be located anywhere on the chain Ensure its EOL jumper is off down if it is in the middle Any sensor controller address can be in ...

Page 5: ...stalled at 50 of the ceiling height and above the vehicle height If the exhaust pipes of diesel vehicles are below the vehicles then the nitrogen dioxide detectors should be installed at 3 to 5 feet 1 to 1 5 meters from the floor In all cases the detectors must be installed above obstructions blocking circulation of air in front of the detectors example maintenance garages in automobile dealership...

Page 6: ...ay on seconds 0 999 30 5 A2Off Alarm 2 Delay off seconds 0 999 20 6 AL3 Alarm 3 threshold sounder and strobe by sensor 7 A3Del Alarm 3 Delay on seconds 0 999 180 8 A3Off Alarm 3 Delay off seconds 0 999 20 9 A1Tx Alarm 1 transmit message CAN network 0 255 1 10 A1Tx Alarm 1 transmit message CAN network 0 255 1 1 A1Tx Alarm 1 transmit message CAN network 0 255 12 A2Tx Alarm 2 transmit message CAN net...

Page 7: ...a or 10V sensor B to tweak output for controller input errors Accessing this option forces output high for testing 44 Temp Temperature delay enable off on 0 1 0 45 Aud Local audio alarm enable on alarm 3 0 1 1 46 BAC BACnet MSTP mode select 0 BACnet communication disabled 1 BACnet communication enabled 2 BACnet communication enabled and display all sensors on CAN network 0 1 2 0 47 BMA BACnet MAC ...

Page 8: ...rises above the alarm setting 8 When the Delay Off Timer times out the relay 1 will de energize the Alarm 1 LED will turn off and the Relay 1 Transmit message will stop being sent thereby de energizing relays on other units 9 If the temperature exceeds the Hi Temperature Alarm setting 51 relay 1 will activate the Alarm 1 LED will turn on and the Alarm 1 Transmit message will be sent via the CAN ne...

Page 9: ...groups To control multiple zones on the same network set the transmit message on each sensor to different messages for different zones The default transmit messages are 1 2 3 for alarm levels 1 2 3 for zone 1 Set zone 2 sensors to transmit messages to 4 5 6 Set zone 3 sensors to transmit 7 8 9 and so on Addresses Set each sensor and controller to a different address setting 39 1 2 3 4 etc It is im...

Page 10: ...ng stops going up The span gas should must be within the range of sensor s scale 9 Adjust the reading to match the concentration in the bottle 10 Press and at the same time to save 1 1 If second sensor installed press and repeat steps 4 to 10 for sensor B 12 Press left arrow several times to return to settings and home Calibration Procedure for Refrigerant type 13 20 and VOC type 01 sensors 1 0 Us...

Page 11: ...when returned to our factory transportation prepaid Deterioration or wear by heat abrasive action chemicals improper installation or operation or lack of normal maintenance shall not constitute defects and are not covered by warranty The motor is warranted by the motor manufacturer for one 1 year If the motor becomes defective in the warranty period it should be taken to the nearest authorized mot...

Page 12: ...l or consequential damages including but not limited to loss of profits or revenue loss of use of the equipment or any associated equipment cost of capital cost of substitute equipment facilities or services down time costs or claims of customers of the purchaser for such damages Soler Palau USA neither assumes nor authorizes any persons to assume for it any other liability in connection with the ...

Reviews: