5
NO.
Name
Description
Range
Default
28
A11Tx
Alarm 1 transmit message, CAN network
0-255
29
A1Tx
Alarm 1 transmit message, CAN network
0-255
30
A2Tx
Alarm 2 transmit message, CAN network
0-255
2
31
A2Tx
Alarm 2 transmit message, CAN network
0-255
32
BiTx
Binary input transmit message, CAN network
0-255
33
A3Tx
Alarm 3 transmit message, CAN network
0-255
0
34
A3Tx
Alarm 3 transmit message, CAN network
0-255
35
A3Tx
Alarm 3 transmit message, CAN network
0-255
List of General Settings
NO.
Name
Description
Range
Default
36
R1Rx
Receive message to relay 1, CAN network
0-255
0
37
R2Rx
Receive message to relay 2, CAN network
0-255
2
38
R3Rx
Receive message to relay 3, CAN network
0-255
3
39
Adr
Sensor identification address, CAN network
0-32
0
40
AnZA
Adjustment for analog zero outpot (4ma or 2V) Sensor A to tweak
output of controller input errors. Accessing this output low for testing
41
AnSA
Adjustment for analog span output (20ma or 10V) sensor A to tweak
output for controller input errors. Accessing this option forces output
high for testing.
42
AnZB
Adjustment for analog zero output (4ma or 2V) sensor B to tweak
output for controller input errors. Accessing this option forces output
low for testing
43
AnSB
Adjustment for analog span output (20ma or 10V) sensor B to tweak
output for controller input errors. Accessing this option forces output
high for testing
44
Temp
Temperature delay enable off/on
0/1
0
45
Aud
Local audio alarm enable on alarm 3
0/1
1
46
BAC
BACnet MSTP mode select
0 = BACnet communication disabled
1 = BACnet communication enabled
2 = BACnet communication enabled and display all sensors on CAN
network
0/1/2
0
47
BMA
BACnet MAC address
127
0
48
BBR
BACnet baud rate
0 = 9600
1 = 19200
2 = 38400
3 = 76800
0/1/2/3
3
49
KBL
Keyboard lock
0/1
0
50
TMod
Temperature modify/calibrate
-9/+9° C
0
51
ATHi
High temperature alarm limit used for summer ventilation. Alarm 1 is
activated when temperature exceeds option disables alarms (seconds)
0-99° C
60
52
W/U
Warm up delay disables alarms
0-255
60
53
BMM
BACnet maximum MAC address when polling for master
0-127
127
59
FltTx
Fault alarm transit message, CAN network
0-255
0
60
ADTxA
Analog drive transmit message, sensor A (top) CAN network
0-255
0
61
AMinA
Analog drive. Minimum percent of scale for zero output. Sensor A
0-100
0
62
AMaxA
Analog drive. Maximum percent of scale for full scale output. Sensor
A
0-100
100
63
ADRxA
Receive message code to control local analog output
0-255
0
64
ADTxB
Analog drive transmit message, sensor B (bottom) CAN
network
0-255
0