background image

Wiring for Model 60xx-A

Wiring - Model 60xx-B

Summary of Contents for 6002-A

Page 1: ...022020 Gas Detectors READ AND SAVE THESE INSTRUCTIONS The purpose of this manual is to aid in the proper installation and operation of fans manufactured by Soler Palau USA These instructions are inten...

Page 2: ...ct resistant water resistant enclosure Specifications Supply 24 vac 50 60 hz 17 28 vac 0 21 amps 5 va Relays 1 or 2 SPDT 5 amp 125 vac non inductive 6002 A and 6002 14A have 1 Relay and accept 4 20mA...

Page 3: ...Wiring for Model 60xx A Wiring Model 60xx B...

Page 4: ...configuration Make all chain connections at the sensors to avoid T connections 6 Move the end of line jumper the one above terminal 1 1 12 to the on position UP on the first sensor or controller on th...

Page 5: ...d be installed at 50 of the ceiling height and above the vehicle height If the exhaust pipes of diesel vehicles are below the vehicles then the nitrogen dioxide detectors should be installed at 3 to 5...

Page 6: ...2 threshold activates relay 2 by sensor 4 A2Del Alarm 2 Delay on seconds 0 999 30 5 A2Off Alarm 2 Delay off seconds 0 999 20 6 AL3 Alarm 3 threshold sounder and strobe by sensor 7 A3Del Alarm 3 Delay...

Page 7: ...ing this option forces output low for testing 43 AnSB Adjustment for analog span output 20ma or 10V sensor B to tweak output for controller input errors Accessing this option forces output high for te...

Page 8: ...start The timer will clear if the gas rises above the alarm setting 8 When the Delay Off Timer times out the relay 1 will de energize the Alarm 1 LED will turn off and the Relay 1 Transmit message wi...

Page 9: ...he relays usually level 1 This is a configuration for one ventilation zone Creating Zones or groups To control multiple zones on the same network set the transmit message on each sensor to different m...

Page 10: ...span and the current gas reading 8 Inject bottled span gas into first sensor and wait until the gas reading stops going up The span gas should must be within the range of sensor s scale 9 Adjust the...

Page 11: ...hen returned to our factory transportation prepaid Deterioration or wear by heat abrasive action chemicals improper installation or operation or lack of normal maintenance shall not constitute defects...

Page 12: ...or consequential damages including but not limited to loss of profits or revenue loss of use of the equipment or any associated equipment cost of capital cost of substitute equipment facilities or se...

Reviews: