background image

8    S&C Instruction Sheet 681-510

Components

Figure 6. Internal gas-pressure gauge for most Vista 
switchgear models.

Red

zone

Orange

zone

Green

zone

Green/Yellow 

zone

Understanding the Gas Pressure Gauge

Vista switchgear incorporates a temperature-compensated 
gas pressure gauge inside the tank to provide indication 
of the SF

6

-gas pressure gauge is in the green and yellow-

striped zone gas pressure. The gas pressure gauge includes 
four distinct color-coded zones. See Figure 6.

If the needle is within a particular zone as described 

below, it indicates the following:

Green zone:

The Vista switchgear unit is OK to operate.

Green/Yellow zone:

The Vista switchgear unit may have lost some gas but is still 
OK to operate. The unit should be evaluated to determine 
whether it needs to be refi lled with SF

6

 gas and repaired 

accordingly. Contact S&C for assistance.

Red zone:

The SF6 gas may be below the minimum operating 
pressure for the gear. 

Vista switchgear should not be 

operated if the needle is in the red zone.

 Contact S&C 

for assistance.

Orange zone:

The Vista switchgear unit has been overfi lled in the fi eld 
or has a defective pressure gauge. An external gauge can 
be used instead to verify the gas pressure before operation 
of the device. Contact S&C for assistance.

Figure 7. Internal gas-pressure gauge for Vista switchgear 
models rated 15 kV, 12.5 kA sym. short circuit that have catalog 
numbers ending with “-R1” suffix.

Green

zone

Red

zone

Green/Yellow

zone

Orange

zone

Gauge Needle Fluctuations from Rapid 

Ambient Temperature Changes

When the Vista switchgear tank experiences rapid changes 
in ambient temperature, the gas pressure gauge needle may 
temporarily move to indicate a higher gas pressure when 
the tank is rapidly cooled or a lower gas pressure when 
the tank is rapidly heated. This phenomenon may occur, 
for instance, with sudden, direct exposure to intense 
sunlight. The gas pressure gauge uses a small reference 
gas chamber fi lled with helium to compensate for ambient 
temperature and altitude without applying correction 
factors. The gauge indicates tank pressure by measuring 
the pressure differential between the gas in the tank and 
the gas in the gauge. When the tank experiences rapid 
ambient temperature changes, the smaller volume of gas 
inside the gauge can change temperature more quickly 
than the larger volume of gas in the tank, which can lead to 
temporary movement of the needle. When the temperature 
stabilizes, the needle will return to its previous position 
within 1-2 hours.  

If a sudden drop or increase in pressure is seen on 

the gauge, S&C recommends checking with an external 
gauge or waiting for ambient temperature conditions to 
stabilize to confirm that the needle has returned to its 
nominal position.

Summary of Contents for Vista Series

Page 1: ...ns from Rapid Ambient Temperature Changes 8 Operation Pre Operation Checks 9 Operating from Closed to Open Position 11 Operating from Open to Grounded Position 12 Operating from Grounded to Open Posit...

Page 2: ...roper Application WARNING The equipment in this publication must be selected for a specific application The application must be within the ratings furnished for the equipment Ratings for this gear are...

Page 3: ...ot followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you do not und...

Page 4: ...Always Consider Circuits and Components Live G 6700 C DANGER Never Drill Into Tank Hazardous Voltage Contains Pressurized SF6 Gas G 6682 D DANGER Keep Away Hazardous Voltage Mr Ouch G 6699 E WARNING C...

Page 5: ...upter is grounded 7 BACKFEED Bushings cables load interrupter switches and fault interrupters may be energized by backfeed 8 DE ENERGIZING TESTING AND GROUNDING Before touching any bushings or compone...

Page 6: ...al or single pole load switching and fault interruption through 12 5 kA symmetrical for other possible ratings refer to the nearest S C Sales Office Fault interruption is initiated by a programmable o...

Page 7: ...en Manual operating handle Viewing window under the VOLTAGE indicator Trip indicators for single pole fault interrupters can be seen through the viewing window TRIP indicator for three pole fault inte...

Page 8: ...nal gas pressure gauge for Vista switchgear models rated 15 kV 12 5 kA sym short circuit that have catalog numbers ending with R1 suffix Green zone Red zone Green Yellow zone Orange zone Gauge Needle...

Page 9: ...isconnect switch blade through the viewing window See Figures 9 and 10 Also inspect the current carrying components inside the tank specifically for dislodged hardware signs of arcing and significant...

Page 10: ...Closed and Open positions Operation Selector Operation Selector Figure 12 Rotating the OPERATION selector out of the way Operating disk Operating disk STEP 3 If the OPERATION selector is blocking the...

Page 11: ...rrupter See Figures 15 and 16 STEP 4 When operating from the Closed to Open position the operating handle must be rotated all the way to the Stop position as shown on the label to open and recharge th...

Page 12: ...ndicator optionsuffix L1 or L2 as instructed under the Checking for Voltage Using Optional Voltage Indicator section on page 17 or use an alternate method STEP 3 Insert the manual operating handle int...

Page 13: ...pages 9 and 10 are completed STEP 2 Insert the manual operating handle into the notch of the operating mechanism STEP 3 Rotate the manual operating handle in the clockwise direction to a stop in the...

Page 14: ...ting handle into the notch of the operating mechanism STEP 3 Rotate the manual operating handle in the clockwise direction to a stop in the Closed position to close the load interrupter switch or faul...

Page 15: ...3 and 24 When operating from the Closed to the Open position the operating handle must be rotated all the way to the Stop position as shown on the label to recharge the mechanism See Figure 25 For thr...

Page 16: ...ctor and the left side hole of the locking collar See Figure 27 Locking In Closed Open or Grounded Position To lock a load interrupter switch or fault interrupter into position insert a padlock throug...

Page 17: ...window STEP 2 Test the VOLTAGE indicator complete voltage indication circuit and phasing circuit if furnished for proper operation as follows a Shine a flashlight approximately 4 inches 102 mm above t...

Page 18: ...test circuit If the dot or any of the flashing lightning bolts still do not appear the VOLTAGE indicator may be damaged Test for voltage using an alternate method See Figures 34 and 35 PHASE indicato...

Page 19: ...either There is no voltage at the bushing The VOLTAGE indicator is malfunctioning Flashing lightning bolt indicates presence of voltage at the associated bushing A blank LCD panel indicates an absence...

Page 20: ...40 c Place the other test probe on each of the phasing pins in turn of the two ways to be phased and measure the phase to ground voltage See Figure 38 d If the voltage measured at each phasing pin is...

Page 21: ...ting that the cables are in phase c Keep the test probe on Phasing Pin 1 of the second way and move the other test probe to Phasing Pin 2 of the first way Measure the phase to phasevoltage SeeFigure42...

Page 22: ...rrupterswitchandfault interrupter grounding means are removed STEP 2 Make certain the load interrupter switches and fault interrupters are in the correct positions Open or Closed STEP 3 If a pad mount...

Page 23: ...itches and fault interrupters from all power sources including backfeed test for voltage and properly ground 4 Always assume the bushings are energized unless proved otherwise by test by visual eviden...

Page 24: ...enclosure must be refinished by the user before the finish has weathered for example to match other equipment a special precaution must be taken The entire surface must be sanded to provide a tooth t...

Page 25: ...g or performance requirements for the switch gear A dc withstand design test is specified for new equip ment because the switchgear may be subjected to dc test voltage when connected to the cable The...

Page 26: ...0 Hertz Impulse BIL 12 15 5 95 30 15 24 27 125 40 20 36 38 150 40 20 The dc cable thumping voltage is 50 of the dc cable test voltage because of voltage doubling that will occur at the open end of the...

Page 27: ...1 Clamp the two current carrying probes of the resistance measuring device to the bushing conductors of the current carrying path to be measured See Figure 46 In this example the resistance is being t...

Reviews: