S&C Vista Series Instruction Sheet Download Page 27

S&C Instruction Sheet 681-510    27

Dielectric Testing

Resistance Measurement

 DANGER

De-energize the Vista Underground Distribution 
Switchgear before performing the resistance 
measurements described in this procedure. Follow all 
applicable safety procedures. Failure to de-energize 
the Vista switchgear before taking resistance 
measurements can result in serious injury or death.

Resistance measurements are used to look for areas of 
the gear that may exhibit poor contact between current 
carrying parts. See Figure 46.

Resistance measurements are taken using a four- 

terminal measuring device that provides at least 100 
amperes of current to the main circuit. Resistance mea-
surements should be taken from the bushing conductor 
across each Way to the same phase on each Way of the 
unit. For example, a measurement would be taken from 
Way 1 Phase A to Way 2 Phase A, from Way 2 Phase A to 
Way 3 Phase A, from Way 1 Phase A to Way 3 Phase A, from  
Way 1 Phase B to Way 2 Phase B; etc.

To measure resistance, perform the following procedure:

STEP  1.  

Clamp the two current-carrying probes of the 
resistance-measuring device to the bushing 
conductors of the current-carrying path to be 
measured. See Figure 46. In this example 

 

the resistance is being taken between Way 1 
Phase A and Way 2 Phase A.

STEP  2.  

NOTICE

DO NOT take resistance measurements 
from the threaded area of the bushing stud. 
Resistance measurements taken through 
the threads of the bushing stud will be 

 

inaccurate.

 

 

Clamp or touch the voltage-carrying probes 

of the resistance measuring device to the flat 
conductive surface of the bushings that make up 
the current carrying path. Make sure the mea-
surement probe is in contact with the current-
carrying flat face of the bushing conductor rod. 
If using clamp-style probes, slide the clamp all 
the way up against the current-carrying face to 
get a good connection. See Figure 47. 

STEP  3.  

Record the resistance measurement. Acceptable 
resistance values are:

• Under 500 microohms

• Under 600 microohms for tie switches

Figure 46. Connecting the resistance measuring device.

Figure 47. Take the measurement from the flat current-carrying 
surface of the bushing.

 Adhere to your company’s standards in regards to using hand PPE 

when taking resistance measurements.

Current-carrying surface

Summary of Contents for Vista Series

Page 1: ...ns from Rapid Ambient Temperature Changes 8 Operation Pre Operation Checks 9 Operating from Closed to Open Position 11 Operating from Open to Grounded Position 12 Operating from Grounded to Open Posit...

Page 2: ...roper Application WARNING The equipment in this publication must be selected for a specific application The application must be within the ratings furnished for the equipment Ratings for this gear are...

Page 3: ...ot followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you do not und...

Page 4: ...Always Consider Circuits and Components Live G 6700 C DANGER Never Drill Into Tank Hazardous Voltage Contains Pressurized SF6 Gas G 6682 D DANGER Keep Away Hazardous Voltage Mr Ouch G 6699 E WARNING C...

Page 5: ...upter is grounded 7 BACKFEED Bushings cables load interrupter switches and fault interrupters may be energized by backfeed 8 DE ENERGIZING TESTING AND GROUNDING Before touching any bushings or compone...

Page 6: ...al or single pole load switching and fault interruption through 12 5 kA symmetrical for other possible ratings refer to the nearest S C Sales Office Fault interruption is initiated by a programmable o...

Page 7: ...en Manual operating handle Viewing window under the VOLTAGE indicator Trip indicators for single pole fault interrupters can be seen through the viewing window TRIP indicator for three pole fault inte...

Page 8: ...nal gas pressure gauge for Vista switchgear models rated 15 kV 12 5 kA sym short circuit that have catalog numbers ending with R1 suffix Green zone Red zone Green Yellow zone Orange zone Gauge Needle...

Page 9: ...isconnect switch blade through the viewing window See Figures 9 and 10 Also inspect the current carrying components inside the tank specifically for dislodged hardware signs of arcing and significant...

Page 10: ...Closed and Open positions Operation Selector Operation Selector Figure 12 Rotating the OPERATION selector out of the way Operating disk Operating disk STEP 3 If the OPERATION selector is blocking the...

Page 11: ...rrupter See Figures 15 and 16 STEP 4 When operating from the Closed to Open position the operating handle must be rotated all the way to the Stop position as shown on the label to open and recharge th...

Page 12: ...ndicator optionsuffix L1 or L2 as instructed under the Checking for Voltage Using Optional Voltage Indicator section on page 17 or use an alternate method STEP 3 Insert the manual operating handle int...

Page 13: ...pages 9 and 10 are completed STEP 2 Insert the manual operating handle into the notch of the operating mechanism STEP 3 Rotate the manual operating handle in the clockwise direction to a stop in the...

Page 14: ...ting handle into the notch of the operating mechanism STEP 3 Rotate the manual operating handle in the clockwise direction to a stop in the Closed position to close the load interrupter switch or faul...

Page 15: ...3 and 24 When operating from the Closed to the Open position the operating handle must be rotated all the way to the Stop position as shown on the label to recharge the mechanism See Figure 25 For thr...

Page 16: ...ctor and the left side hole of the locking collar See Figure 27 Locking In Closed Open or Grounded Position To lock a load interrupter switch or fault interrupter into position insert a padlock throug...

Page 17: ...window STEP 2 Test the VOLTAGE indicator complete voltage indication circuit and phasing circuit if furnished for proper operation as follows a Shine a flashlight approximately 4 inches 102 mm above t...

Page 18: ...test circuit If the dot or any of the flashing lightning bolts still do not appear the VOLTAGE indicator may be damaged Test for voltage using an alternate method See Figures 34 and 35 PHASE indicato...

Page 19: ...either There is no voltage at the bushing The VOLTAGE indicator is malfunctioning Flashing lightning bolt indicates presence of voltage at the associated bushing A blank LCD panel indicates an absence...

Page 20: ...40 c Place the other test probe on each of the phasing pins in turn of the two ways to be phased and measure the phase to ground voltage See Figure 38 d If the voltage measured at each phasing pin is...

Page 21: ...ting that the cables are in phase c Keep the test probe on Phasing Pin 1 of the second way and move the other test probe to Phasing Pin 2 of the first way Measure the phase to phasevoltage SeeFigure42...

Page 22: ...rrupterswitchandfault interrupter grounding means are removed STEP 2 Make certain the load interrupter switches and fault interrupters are in the correct positions Open or Closed STEP 3 If a pad mount...

Page 23: ...itches and fault interrupters from all power sources including backfeed test for voltage and properly ground 4 Always assume the bushings are energized unless proved otherwise by test by visual eviden...

Page 24: ...enclosure must be refinished by the user before the finish has weathered for example to match other equipment a special precaution must be taken The entire surface must be sanded to provide a tooth t...

Page 25: ...g or performance requirements for the switch gear A dc withstand design test is specified for new equip ment because the switchgear may be subjected to dc test voltage when connected to the cable The...

Page 26: ...0 Hertz Impulse BIL 12 15 5 95 30 15 24 27 125 40 20 36 38 150 40 20 The dc cable thumping voltage is 50 of the dc cable test voltage because of voltage doubling that will occur at the open end of the...

Page 27: ...1 Clamp the two current carrying probes of the resistance measuring device to the bushing conductors of the current carrying path to be measured See Figure 46 In this example the resistance is being t...

Reviews: