S&C Instruction Sheet 695-505
23
Installation
Closing the Doors and the Hinged Roof
STEP 1.
Lift door-holder mechanism up to allow left-hand
door to swing closed. See Figure 22. Make sure
the fi nger latch engages the pin. See Figure 15 on
page 17.
STEP 2.
Lift the door-holder mechanism up to allow
right-hand door or the center door to swing
closed. See Figure 22. Close the door completely.
Make sure the latch handle drops down fully to
engage the door latching mechanism.
STEP 3.
On the right-hand side of the switchgear
enclosure, while pushing up on the hinged roof,
release the latch on the “hold-open” mechanism.
See Figure 23. Allow hinged roof to sag against
the right-hand “hold-open” mechanism. At the
other end of the enclosure, push up on the hinged
roof just enough to allow the left-hand “hold-
open” mechanism latch to be released, ensuring
the right-hand “hold-open” latching mechanism
does not re-engage. Lower the hinged roof into
the closed position.
STEP 4.
Insert a pentahead socket wrench or tool (or a
hexhead socket wrench or tool if catalog number
suffi x “-H1” is specifi ed) into the hinged roof
latching mechanism. Rotate wrench or tool 360°
clockwise
to fully latch the hinged roof. See
Figure 24.
STEP 5.
Insert padlock shackle through the hole in
padlock recess and lock the padlock.
Figure 22. Lift the door-holder mechanism up to allow the
door to swing closed.
Figure 24. To fully latch the hinged roof, rotate the pentahead
socket wrench or tool 360° clockwise.
Figure 23. While pushing up on the hinged roof, release the
latch on the “hold-open” mechanism.