background image

S&C Instruction Sheet 663-500    15

Installation

 WARNING

Low-voltage wiring routed inside the pad-mounted 
gear enclosure must be a minimum of 6 inches 
(152 mm) at 14 .4 kV and 7½ inches (191 mm) at 
25 kV away from components that will be energized 
at high voltage . Do not place wiring where it might 
fall onto a component that will be energized at high 
voltage, such as the bus, or where it will be in the 
way of moving parts .
Failure to maintain proper clearance can result in a 
flashover, injury, and equipment damage .

NOTICE

Openings made into the low-voltage control 
compartment must be sealed with a suitable 
compound to prevent the entry of moisture or 
animals . Failure to properly seal the openings can 
result in damage to the electronic components .

NOTICE

Do not install the current sensors on unshielded 
cables or on cables where the insulation is exposed 
but ungrounded (for example, where dielectric tape 
or heatshrink tubing is used) . These current sensors 
are intended for application at ground potential and 
can be damaged by the voltage gradient between 
the cable insulation and ground .

NOTICE

Twelve current sensors are required for source-
transfer pad-mounted gear furnished with optional 
switch-terminal adapters (catalog number suffix 
“-M1”) that permit two cables per phase . Install 
the current sensors in accordance with the wiring 
diagram provided .
The automatic source-transfer scheme will not 
operate properly when only six current sensors are 
installed .

S&C Current Sensors

STEP  7.  

Six S&C Current Sensors (packed separately) 
are provided for units furnished with the 
optional 

Overcurrent Lockout 

feature 

(catalog number suffi x “-Y2”). The leads from 
the current sensors in each switch compartment 
must be connected to a terminal block located 
in the associated terminal-block compartment, 
behind the bolted panel labeled “Terminal 
Blocks.” See Figure 9.

The bottom plate in each terminal-block 

compartment is removable to facilitate drill-
ing an entrance hole for the lead wires. When 
conduit is not used, protect the lead wires from 
abrasion against the knockout opening with 
a rubber grommet or by taping. Then, apply a 
suitable compound to fill the space between the 
lead wires and the opening to prevent entry of 
moisture or animals.

Figure 9. The left side of the low-voltage control compartment 
showing the left terminal-block compartment (the right 
terminal-block compartment is similar) for connection of 
leads from S&C Current Sensors furnished with the optional 
Overcurrent Lockout feature (option suffix “-Y2”); and for 
customer connections when optional auxiliary switches (suffix 
“-C9” or “C10”), the Remote Indication feature (option suffix 
“-Y4”), or the Supervisory Control feature (option suffix “-Y6”) 
is furnished. Terminal blocks for options “-Y4” and “-Y6” are in 
the left terminal-block compartment only.

Termination-block

compartment

Summary of Contents for PMH

Page 1: ...nstruction Sheet 2 Retain this Instruction Sheet 2 Proper Application 2 Warranty 2 Safety Information Understanding Safety Alert Messages 3 Following Safety Instructions 3 Replacement Instructions and...

Page 2: ...C Source Transfer PMH Pad Mounted Gear Designate a location where you can easily retrieve and refer to this publication Proper Application WARNING The equipment in this publication is only intended f...

Page 3: ...autions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If y...

Page 4: ...COMPANY S C 6601 NORTH RIDGE BOULEVARD CHICAGO ILLINOIS AND NEITHER RECEIPT NOR POSSESSION THEREOF INFERS OR TRANSFERS ANY RIGHT IN OR LICENSE TO USE THIS DOCUMENT THE SUBJECT MATTER THEREOF OR ANY D...

Page 5: ...l circuits and component parts live until completely de energized tested grounded and tagged or properly identified Do not work on or near this equipment unless you 1 Know and obey your employer s wor...

Page 6: ...ng any device that is to be inspected replaced serviced or repaired in the high voltage compartments 9 MAINTAINING PROPER CLEARANCE Always maintain proper clearance from energized components 10 SWITCH...

Page 7: ...ons about field programming and opera tion of the Micro AT control refer to S C Instruction Sheet 515 500 These instruction sheets along with a catalog dimensional drawing showing cable locating and a...

Page 8: ...ed by the packing materials and will also prevent wind induced abrasion from loose cardboard Storage S C Source Transfer PMH Pad Mounted Gear should installed and energized immediately When the gear i...

Page 9: ...socket wrench or tool when catalog number suffix B1 or B2 is specified to unlatch the Penta Latch Mechanism by rotating the actuator counterclockwise approximately 60 degrees against spring resistanc...

Page 10: ...latched a padlock may be inserted into the hasp Placement STEP 2 At the installation site remove all separately packaged components shipped in the pad mounted gear enclosure and set them aside in a p...

Page 11: ...the saddle of the bracket or install the cable wrap until instructed to do so in Step 5 on page 13 Figure 5 Side view of the switch showing the interphase barrier attachment points terminal pad conne...

Page 12: ...or 14 4 kV 2 57 for 25 kV Minimum clearance from energized parts to barriers 13 for 14 4 kV 1 32 for 25 kV Minimum clearance from energized parts to electrical ground 6 152 for 14 4 kV 7 191 for 25 kV...

Page 13: ...taping it with a suitable material Two position cable terminator adapters are provided at the fuse hinge assemblies See Figure 7 These adapters can be placed in their alternate positions when require...

Page 14: ...elleville washers are flat Then back off one half turn Do not use lockwashers with Belleville washers For tinned copper or tinned bronze connectors Use inch galvanized steel hardware with one Bellevil...

Page 15: ...n accordance with the wiring diagram provided The automatic source transfer scheme will not operate properly when only six current sensors are installed S C Current Sensors STEP 7 Six S C Current Sens...

Page 16: ...alog number suffix C9 or C10 optional Remote Indication feature catalog number suffix Y4 or optional Supervisory Control feature catalog number suffix Y6 are also located in the terminal block compart...

Page 17: ...ier support angle at the front of the switch compartment Make sure the clearance from the barriers to energized parts and from the barriers to terminator skirts conforms to the minimum dimensions spec...

Page 18: ...barriers Prolonged exposure to corona discharge can damage the barriers and result in a flashover injury and equipment damage f Store spare SMU 20 Fuse Units or SM 4 Refill Units as applicable in the...

Page 19: ...Testing When high voltage dielectric tests will be performed on S C Source Transfer PMH Pad Mounted Gear special precautions should be taken to prevent damage to the voltage sensors and voltage limit...

Reviews: