S&C PMH Inspection Manual Download Page 6

6

    S&C Instruction Sheet 663-590

Table 1

Table 1.  Inspection Procedures for Pad-Mounted Gear Equipped with Micro-AT Source-Transfer Control

Item

Procedures

Switch operators

1 .  Place the MANUAL/AUTOMATIC operation selector switch on the Micro-AT control in the 

Manual position and decouple both 

operators from their associated Mini-Rupter Switches . (Switching operations will result in temporary service interruptions if the 

operators are coupled .)

2 .  Open the preferred-source operator by pressing the appropriate OPEN pushbutton . After opening, the operator should recharge in 

less than 35 seconds .

3 .  Close the alternate-source operator by pressing the appropriate CLOSE pushbutton . This operator should also recharge in less 

than 35 seconds .

4 .  Each switch operator should be given an exercise consisting of five or more power-operated operations unless normal operating 

duty provides equal or greater exercise .

5 .  Return both operators to their original positions (preferred closed; alternate open) .

Clock

1 .  Press the <Time> menu key on the Micro-AT control . Then, press the <Last> item key . The “HH:MM:SS” (hour:minute:second) 

item will appear on the display . If necessary, reset the time as directed below .

2 .  To reset the time, first press the <Change> key . After that, press each digit of the access-code number and the <Enter> key . 

Press the number keys corresponding to the desired value, and press the <Enter> key again .

Lamps, display, and 

keypad

1 .  Press the <Test> menu key on the Micro-AT control . Then, press the <Next> item key . The 

Test Lamps item will appear on the 

display . Press the <Enter> key and confirm the lamps on the control flash a total of five times .

2 .  Press the <Next> item key again . The 

Test Display item will appear on the display . Press the <Enter> key, and confirm all dot 

segments comprising the characters of the display alternately appear black and then disappear a total of five times .

3 .  Press the <Next> item key again . This time the 

Test Keypad item will appear on the display . Press the <Enter> key . Now 

individually press all the keys on the control and verify the value or name of each key pressed appears on the display . When 

finished, press the <Quit> key .

Transfer on loss of 

source and return of 

source

1 .  While still in the text menu, press the <Next> item key one more time . The 

Enable Test Keys item will appear on the display . 

Press the <Change> key . Then, select 

On mode by pressing the <Enter> key . The test keys are now enabled for 15 minutes .

2 .  Place the MANUAL/AUTOMATIC operation selector switch in the 

Automatic position .

3 .  If the Micro-AT control has been programmed for automatic return:

a .  Simulate a prolonged loss of preferred-source voltage by pressing and holding in the <Loss of Voltage> key for the left source 

or right source, as appropriate . Verify the time to initiate transfer is the same as the loss-of-source time delay programmed into 

the control for the preferred source . Also confirm the associated source voltage lamp extinguishes and that the switch operator 

targets correctly indicate an 

Open or Closed position .

b .  Now, release the <Loss of Voltage> key to simulate a return of the preferred-source voltage . Verify the time to initiate back 

transfer is the same as the return-of-source time delay programmed into the control . Confirm the associated source voltage 

lamp relights . Verify the switch operator targets’ positions .

4 .  If the Micro-AT control has been programmed for 

Hold Return mode:

a .  Simulate a prolonged loss of preferred-source voltage by pressing and holding in the <Loss of Voltage> key for the left source 

or the right source, as appropriate . Verify the time to initiate transfer is the same as the loss-of-source time delay programmed 

into the control for the preferred source . Also confirm the associated source voltage lamp extinguishes and that the switch 

operator targets correctly indicate an 

Open or Closed position .

b .  Release the <Loss of Voltage> key to simulate a return of the preferred-source voltage, and wait a sufficient length of time to 

verify back transfer does not occur . Confirm the associated source voltage lamp relights .

c .  Now, simulate a loss of alternate-source voltage by pressing and holding in the <Loss of Voltage> key for the left source or the 

right source, as appropriate . Verify the time to initiate back transfer is the same as the loss-of-source time delay programmed 

into the control for the alternate source . Confirm the associated source voltage lamp extinguishes, and then release the <Loss 

of Voltage> key . Verify the switch operator targets’ positions .

5 .  Return the MANUAL/AUTOMATIC operation selector switch to the 

Manual position .

TABLE CONTINUED 

Summary of Contents for PMH

Page 1: ...Retain this Instruction Sheet 2 Proper Application 2 Warranty 2 Warranty Qualifications 2 Safety Information Understanding Safety Alert Messages 3 Following Safety Instructions 3 Replacement Instructi...

Page 2: ...is a permanent part of your S C Source Transfer PMH Pad Mounted gear Designate a location where you can easily retrieve and refer to it Proper Application CAUTION The equipment in this publication mu...

Page 3: ...commended recautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Inst...

Page 4: ...y to authorized persons so that the key interlock scheme will not be comprised Key interlocks are not security locks and are not substi tutes for padlocks 5 Opening Doors Do not apply any undue force...

Page 5: ...ctory and in the field These settings are entered into the control by means of a keypad on the front panel and may be reviewed via a liquid crystal display CAUTION When following the inspection proced...

Page 6: ...ile still in the text menu press the Next item key one more time The Enable Test Keys item will appear on the display Press the Change key Then select On mode by pressing the Enter key The test keys a...

Page 7: ...hen press the Next item key The date time and event ID for the last control operation will appear on the display Confirm the event ID on the display is 218 enter manual software Press the key to view...

Page 8: ...loss of source and return of source 62P 62A and 2P Timers 1 Place the MANUAL AUTOMATIC operation selector switch in the Automatic position and note the position of the AUTOMATIC HOLD RETURN selector...

Page 9: ...ch in the Manual position and press the OVERCURRENT LOCKOUT RESET pushbutton to cancel the lockout condition Confirm the OVERCURRENT LOCKOUT lamp extinguishes Then close the preferred source operator...

Page 10: ...barriers are left in the slide in position for extended periods of time there is the possibility of corona discharge to the barriers Prolongedexposuretocoronadischargemaydamage the barriers and resul...

Page 11: ...face imperfections can be burnished out Clean the blades and apply a thin layer of lubricant as necessary b Clean rotating hinge contacts and apply a thin layer of lubricant as necessary c Check conta...