S&C PMH Inspection Manual Download Page 10

10

    S&C Instruction Sheet 663-590

Table 3

Table 3. Inspection and Maintenance Procedures for the Enclosure and for  

Components in High-Voltage Compartments

 WARNING

When access to high-voltage compartments is required, 
it should be restricted to qualified persons who observe 
the following procedures:
1 .  Adhere to prescribed safety rules at all times .
2 .  Be certain fuses, Mini-Rupter Switches, their 

mechanisms, and any other devices are disconnected 
from all power sources and are grounded before that 
device is inspected, serviced, or repaired .

3 .  Discharge all stored-energy switch operators by using 

the manual operating handle .

4 .  Always assume both sets of terminals on any Mini-

Rupter Switch or fuse are energized unless proven 
otherwise by test, by visual evidence of open-circuit 
conditions on both terminal ends, or by grounding .

5 .  All voltage sensors must be disconnected when 

external voltage is used to test any secondary-side 
wiring or devices to avoid energizing the high-voltage 
conductors through the voltage sensors . To disconnect 
the voltage sensors, transfer the input plug from the 
input receptacle to the shorting receptacle .

6 .  Test for voltage . Qualified persons should be certain 

they have and know how to operate the correct test 
equipment for determining the voltage on both sets of 
terminals on any fuse or interrupter switch .

7 .  After the gear has been completely disconnected from 

all sources of power and tested, properly connect 
suitable grounding leads to both sides of the 
equipment, that is, to the incoming and outgoing 
phases of the equipment to be maintained .

8 .  Install dual-purpose front barriers, if furnished, in the 

“slide-in” position .

 If a contact on either side of a 

barrier is energized, do not leave the barrier in the 
“slide-in” position for longer than one week . These 
barriers are intended for temporary use only to isolate 
the blades of the switch from the main contacts while 
work is being performed . If the barriers are left in the 
“slide-in” position for extended periods of time, there 
is the possibility of corona discharge to the barriers . 
Prolonged exposure to corona discharge may damage 
the barriers and result in a flashover .

9 .  When the equipment to be inspected is not of S&C 

manufacture, follow instructions supplied by the 
manufacturer of the equipment .

10 .  Make certain the enclosure is properly grounded to 

the station or facility ground . No equipment should be 
returned to service unless such grounds are properly 
made .

Note: Occasionally, low-voltage components may 
require maintenance . The maintenance of low-voltage 
components isolated from high-voltage compartments 
may be performed under the safety rules for equipment 
rated 600 Volts or less . If maintenance is to be performed 
on devices connected to the secondary of a voltage 
sensor, short-circuit the secondary connections . A sepa-
rate drawing will be provided with any replacement part 
explaining how to properly short-circuit the secondary 
connections .
When returning the equipment to service, the following 
procedures should be observed:
1 .    

Withdraw any dual-purpose front barriers, if fur-
nished, from the “slide-in” position and return them 
to their normal, suspended position .

2 .    Make sure that fuses (or switch blades instead of 

fuses) are closed and securely latched .

3 .   Make sure any grounding means are removed before 

energizing the associated Mini-Rupter Switch or 
fuse .

4 .   Close each door permitting access to high voltage 

and make sure that the associated door latching 
mechanisms are securely latched before energizing 
the circuit or operating any switching device .

5 .  Make certain the input plug is in the input receptacle .
6 .   Make certain the Mini-Rupter Switches are in the cor-

rect positions (Open or Closed) as dictated by the 
electric power system design .

7 .   Padlock all doors before leaving the installation site, 

even momentarily . Observe this procedure even in 
those cases where the gear is accessible only to 
qualified persons .

 

■ 

Dual-purpose front barriers for switches and fuses are 

optional on units shipped before September 1994 . They 
became standard after September 1994 .

Summary of Contents for PMH

Page 1: ...Retain this Instruction Sheet 2 Proper Application 2 Warranty 2 Warranty Qualifications 2 Safety Information Understanding Safety Alert Messages 3 Following Safety Instructions 3 Replacement Instructi...

Page 2: ...is a permanent part of your S C Source Transfer PMH Pad Mounted gear Designate a location where you can easily retrieve and refer to it Proper Application CAUTION The equipment in this publication mu...

Page 3: ...commended recautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Inst...

Page 4: ...y to authorized persons so that the key interlock scheme will not be comprised Key interlocks are not security locks and are not substi tutes for padlocks 5 Opening Doors Do not apply any undue force...

Page 5: ...ctory and in the field These settings are entered into the control by means of a keypad on the front panel and may be reviewed via a liquid crystal display CAUTION When following the inspection proced...

Page 6: ...ile still in the text menu press the Next item key one more time The Enable Test Keys item will appear on the display Press the Change key Then select On mode by pressing the Enter key The test keys a...

Page 7: ...hen press the Next item key The date time and event ID for the last control operation will appear on the display Confirm the event ID on the display is 218 enter manual software Press the key to view...

Page 8: ...loss of source and return of source 62P 62A and 2P Timers 1 Place the MANUAL AUTOMATIC operation selector switch in the Automatic position and note the position of the AUTOMATIC HOLD RETURN selector...

Page 9: ...ch in the Manual position and press the OVERCURRENT LOCKOUT RESET pushbutton to cancel the lockout condition Confirm the OVERCURRENT LOCKOUT lamp extinguishes Then close the preferred source operator...

Page 10: ...barriers are left in the slide in position for extended periods of time there is the possibility of corona discharge to the barriers Prolongedexposuretocoronadischargemaydamage the barriers and resul...

Page 11: ...face imperfections can be burnished out Clean the blades and apply a thin layer of lubricant as necessary b Clean rotating hinge contacts and apply a thin layer of lubricant as necessary c Check conta...

Reviews: