S&C PMH Instructions For Operation Manual Download Page 27

S&C ELECTRIC COMPANY 

 

s

INSTRUCTION SHEET

 663-503

Page 27 of 35

August 14, 1995

Components

No routine maintenance is required for the S&C Micro-AT
Source-Transfer Control. However, operational testing
once per year in accordance with S&C Instruction Sheet
663-590 is recommended to verify proper functioning of
the system.

No mechanical maintenance is required for S&C Pad-

Mounted Gear. However, occasional inspection of the
gear and exercising of the Mini-Rupter Switches is rec-
ommended. In addition, inspection and cleaning—of
insulators and cable terminators in particular—should be
performed periodically, at intervals based on environ-
mental conditions.

The stored-energy operators should be given an exer-

cising consisting of five or more operations at least once
every year, unless normal operating duty provides equal
or greater exercise. With the switches decoupled from the
operators, exercising can be accomplished at any conve-
nient time without requiring that the switches themselves
be operated and, therefore, without requiring an interrup-
tion of service.

The nominal operating life of the stored-energy opera-

tors is 1500 operations (complete close-open cycles), pro-
vided that no more than 500 of such operations are
performed while decoupled.

Place dual-purpose front barriers for switch and fuse

compartments into the “slide-in” position. See Figures 10
and 14. This will provide physical isolation for additional
security if it is necessary to work on the cables connected
to the Mini-Rupter Switch or fuse.

Ç

 

WARNING 

Before cleaning, completely de-energize, test, and
ground the pad-mounted gear. Never use pressure-
sprayed abrasives to clean pad-mounted gear. 

Pres-

sure-sprayed abrasives will damage switch and
fuse components.

Ç

 

DANGER 

When access to high-voltage compartments is required
for inspection, service, or repairs, always observe the
precautions below. 

Failure to observe these precau-

tions will result in serious injury or death.

1. Access to pad-mounted gear must be restricted only

to qualified persons. See “Qualified Persons” on
page 2.

2. Always follow safe operating procedures and rules.

3. Before touching any device, alway disconnect

switches, fuses, and other devices from all power
sources (including backfeed) and control sources,
test for voltage, and properly ground.

4. When external voltage is used to test any secondary-

side wiring or devices, disconnect all voltage sen-
sors to avoid energizing the high-voltage conductors
through the voltage sensors. To disconnect the volt-
age sensors, transfer the input plug from the input
receptacle to the shorting receptacle. See Figure 3.

5. Always assume that both sets of power terminals

on any switch or fuse are energized unless proved
otherwise by test, by visual evidence of open-cir-
cuit conditions on both sets of terminals, or by
observing that both sets of terminals are grounded.

6. Test for voltage on both sets of power terminals of

any switch or fuse using proper high-voltage test
equipment.

7. After the gear has been completely disconnected

from all sources of power and tested for voltage,
install suitable grounding cables in all compart-
ments.

8. For maintenance of non-S&C equipment, follow the

manufacturer’s instructions.

9. Make certain the enclosure is properly grounded to

the station or facility ground. Do not return equip-
ment to service unless such grounds are properly
made.

NOTE:

  Occasionally, low-voltage components may

require maintenance. The maintenance of other low-
voltage components isolated from high-voltage com-
partments may be performed under the safety rules for
equipment rated 600 volts or less. If maintenance is to
be performed on devices connected to the secondary
of a voltage sensor, short-circuit the secondary connec-
tions. A separate drawing will be provided with the
replacement part explaining how to properly short-cir-
cuit the secondary connections.

MAINTENANCE

a

a

These recommendations may differ from company operating procedures and rules. Where a discrepancy exists, users should follow their

company’s operating procedures and rules.

Summary of Contents for PMH

Page 1: ...Removing the Fuse 20 INSTRUCTIONS For Operation Section Page Number RE FUSING How to Detect and Replace a Blown Fuse 23 Installing the Fuse in the Mounting 24 FINAL CHECKS BEFORE WALKING AWAY 25 IF OP...

Page 2: ...or the equipment Ratings for this gear are listed on a ratings label on the interior of the doors right hand doors only for double door models Transfer Control For instructions regarding field pro gra...

Page 3: ...out this instruction sheet as well as on labels affixed to the S C Source Transfer PMH Pad Mounted Gear Familiarize yourself with these types of messages and the importance of the various signal words...

Page 4: ...ED TERMINALS Always assume that both sets of power terminals on any Mini Rupter Switch or fuse are energized unless proved other wise by test by visual evidence of open circuit con ditions on both set...

Page 5: ...ng performed v Fuse Side These barriers are intended for tempo rary use to isolate the fuse from the contacts of Uni Rupter while work is being performed 19 CLOSING FUSES Closing a fuse into a faulted...

Page 6: ...ith the various compo nents and locations Figure 1 Low voltage control compartment Bolted cover provides access to input plug and shorting receptacle for Micro AT control Operator target indicates whe...

Page 7: ...Test keys for simulating overcurrent and loss of voltage on right source Right source voltage indicating lamp Manual automatic operation selector switch When in MANUAL prevents an automatic source tra...

Page 8: ...e of S C Micro AT Source Transfer Control Remote indication wiring provided with optional remote indication feature Catalog Number Suffix Y4 leads to a terminal block for user s connections Supervisor...

Page 9: ...Viewing window for visible verifica tion of switch position is removable for phasing To remove window loosen wing head screws and lift window off alignment bolts Current sensors furnished for attach m...

Page 10: ...dow is provided in the switch compartment to allow positive visual verification of switch blade posi tion see Figure 4 The operator target see Figure 1 signals OPERATOR CHARGED to indicate that the op...

Page 11: ...ges when voltage is present on the associated source The charging operation takes approximately 25 seconds If Control Power Is Lost and Operator Is Charged To manually operate the stored energy operat...

Page 12: ...ing the front barriers refer to the DANGER on pages 4 and 5 and the WARNING on page 10 Place the dual purpose front barrier in the slide in position whenever the Mini Rupter Switch is open When the ba...

Page 13: ...rator will stall in a par tially closed position To correct this condition follow the directions under IF OPERATOR STALLS on page 26 To restore the dual purpose front barrier to the normal suspended p...

Page 14: ...oor Distribution 14 4 kv and 25 kv S C ELECTRIC COMPANY s 663 503 INSTRUCTION SHEET Page 14 of 35 August 14 1995 MINI RUPTER SWITCHES Continued Figure 11 Alternate method of replacing front barrier us...

Page 15: ...urrent limiting fuse holders refer to S C Instruction Sheet 660 500 WARNING When selecting current limiting fuses the voltage rating of the fuses must conform to the recommendations in Appendix E Fail...

Page 16: ...nto which the fuse is to be installed See Figure 13 Insert the barrier into the slide in position using the Grappler as illustrated in Figure 14 Note that the barrier is supported on the Grappler pron...

Page 17: ...g the contacts will close the circuit which can cause a flashover and serious injury Always place the dual purpose front barrier in the slide in position whenever a fuse is open or is being removed fr...

Page 18: ...o carry and interrupt rated current 6 With the Grappler prongs pointed downward insert the longer prong into the pull ring of the fuse See inset of Figure 18 Then with one s face turned away close the...

Page 19: ...T 663 503 Page 19 of 35 August 14 1995 SWITCHING WITH UNI RUPTER Continued Figure 18 Closing the fuse Inset on right shows close up of Grappler in position to close the fuse Top inset shows close up o...

Page 20: ...positioned for opening stroke with longer prong inserted in the fuse pull ring WARNING A Note on Single Pole Switching In single pole switching of ungrounded primary three phase transformers or banks...

Page 21: ...ous injury or death 6 Place the dual purpose front barrier associated with the fuse to be removed in the slide in position Use the Grappler for this as illustrated in Figure 21 Note that the barrier i...

Page 22: ...ing the fuse from its hinge Touching the contacts will close the circuit which can cause a flashover and serious injury Always place the dual purpose front barrier in the slide in position whenever a...

Page 23: ...The blown fuse target retracts within the end fitting or holder when the blown fuse unit or interrupting module is replaced SML 4Z Power Fuse A fluorescent orange target in the translucent SML 4Z Hol...

Page 24: ...t current should also be replaced For instructions on replacing current limiting fuses in S C Holders refer to S C Instruction Sheet 660 500 S C Holders will accommodate the current limiting fuses lis...

Page 25: ...p is not lighted NOTE A lighted READY lamp indicates that the status of associated components is normal but an absence of illumination does not necessarily mean that the control is inoperative For exa...

Page 26: ...on See Figure 25 Restore the stored energy operator to a normal latched open condition after such an occurrence as follows 1 Make sure that the manual automatic operation selector switch is in MANUAL...

Page 27: ...serious injury or death 1 Access to pad mounted gear must be restricted only to qualified persons See Qualified Persons on page 2 2 Always follow safe operating procedures and rules 3 Before touching...

Page 28: ...ali fied persons Enclosure Finish The responsibility for ensuring that a finish protects the enclosure lies with both the manufacturer and the user S C Source Transfer PMH Pad Mounted Gear is finished...

Page 29: ...ast two min utes after the stored energy operators are charged before initiating a transfer operation APPENDIX A Dielectric Testing When high voltage dielectric tests are to be performed on S C Source...

Page 30: ...ities shown for S C Power Fuses with Uni Rupter represent the fault closing capabilities of the fuse with Uni Rupter when the fuse is closed with a purposeful thrust without hesitation Following the s...

Page 31: ...luded see ACCESSORIES on page 33 C11 Mounting Provisions for a Fault Indicator in each switch compartment Note Accommodates three phase indicator with single phase sensors Without viewing window in do...

Page 32: ...specified cable termination options suffixes U2 and U3 cannot be accommodated In addition when optional features M1 and M2 are both specified only one cable guide is provided at each switch terminal...

Page 33: ...T control communications card see optional feature Y8 on page 32 to user furnished personal computer For personal computers having 25 pin serial communication port TA 2320 For personal computers havin...

Page 34: ...5 15 5 6 30 40 100 6 30 40 50 65 100 3142 A3 3142 A1 3142 A2 3142 A1 3142 Cooper Power Systems McGraw Edison NX 8 3 8 3 15 5 15 5 1 5C 40C 50C 100C 1 5C 40C 1 5C 100C 3142 A3 3142 A1 3142 A2 3142 RTE...

Page 35: ...gs appropriate for system line to ground voltage i e fuses with a voltage rating lower than line to line voltage but greater than or equal to maxi mum system line to ground voltage S C can only recom...

Reviews: