S&C PMH Instructions For Operation Manual Download Page 10

S&C Source-Transfer PMH Pad-Mounted Gear

With Micro-AT

®

   

Control

Outdoor Distribution (14.4 kv and 25 kv)

 

S&C ELECTRIC COMPANY

 

s

663-503 

INSTRUCTION SHEET

Page 10 of 35
August 14, 1995

Ç

 

WARNING 

MINI-RUPTER SWITCHES

1. To prevent an automatic operation when decoupling

or coupling an operator to a switch, during manual
charging of an operator, or when manually operat-
ing a switch, place the manual/automatic operation
selector switch located on the faceplate of the
Micro-AT Source-Transfer Control in “MANUAL.”

2. Do not perform any switching operations if the

source-transfer control is in the lockout mode as
indicated by illumination of the “LOCKOUT” lamp.
See Figure 2. For such cases, see “Overcurrent-
Lockout Condition” under the “OPERATING
DESCRIPTION” in S&C Instruction Sheet 515-500.

3. If the gear is energized and paralleling of sources is

not permitted, 

decouple both stored-energy opera-

tors

  (see “Decoupling” below) 

to avoid temporary

service interruptions when manually operating
the gear. Switching operations will result in tem-
porary service interruptions if stored-energy oper-
ators are coupled.

4. Due to operating errors, the stored-energy opera-

tor’s quick-make quick-break mechanism may stall
in a partially discharged state. The conditions which
will cause this mechanism to stall, as well as
instructions for restoring the operator to the normal
latched-open condition after a stall, are listed under
“IF OPERATOR STALLS . . .” on page 26.

5. Do not assume that the operator position neces-

sarily indicates the open or closed position of the

Mini-Rupter Switch. Upon completion of an open-
ing or closing operation, check to be sure that the
following conditions exist:

The operator target (see Figure 1) signals “OPER-
ATOR IN SWITCH-OPEN POSITION” or “OPER-
ATOR IN SWITCH-CLOSED POSITION” to
indicate that the switch operator has moved
through a complete operation.

The switch-position target (see Figure 1) which
signals “SWITCH OPEN” or “SWITCH CLOSED,”
is in agreement with the operator target.

The switch position, as verified by visual check
of the switch-blade position, is in agreement with
the switch-position target. A viewing window is
provided in the switch compartment to allow
positive visual verification of switch-blade posi-
tion (see Figure 4).

The operator target (see Figure 1) signals
“OPERATOR CHARGED” to indicate that the
operator is ready for the next operation.

6. To prevent 

all

 electrical and mechanical operations,

padlock the operation selector in the “LOCK POSI-
TION.” This will also prevent motor charging of the
stored-energy operator if system operating proce-
dures require that the quick-make quick-break
mechanism remain discharged—and source voltage
is present.

Decoupling

Decoupling is accomplished using the decoupler handle.
See Figure 5. When decoupled, the stored-energy operator
may be operated without affecting the position of the
associated Mini-Rupter Switch. Moreover, when decou-
pled, the Mini-Rupter Switch is prevented from moving by
a mechanical device which locks the switch drive-shaft.

To  decouple the stored-energy operators, first place

the manual/automatic operation selector switch on the
faceplate of the S&C Micro-AT Source-Transfer Control
in “MANUAL.” For each stored-energy operator, grasp
the decoupler handle and press down on the coupled-
position latch to release the handle. Then move the
handle upward to the “DECOUPLED” position. Make
sure that the handle is fully latched in the decoupled
position. While an operator is decoupled, the automatic-
transfer “ready” indicating lamp on the faceplate of the
Micro-AT control will not light—a reminder of the decou-
pled condition. See Figure 2.

Coupling

To  couple the stored-energy operators, first place the
manual/automatic operation selector switch on the face-
plate of the Micro-AT control in ”MANUAL.” 

Then make

sure that the stored-energy operators are in the same
position (open or closed) as their associated Mini-
Rupter Switches

  by observing the switch-position and

operator targets. See Figure 1. If required, use the
open/close pushbuttons (provided control power is avail-
able) to reposition the operator(s).

For each operator, grasp the decoupler handle and

press down on the decoupled-position latch to release the
handle. Then move the handle downward to the “COU-
PLED” position. Make sure that the handle is fully latched
in the coupled position. An attempt to operate a switch
that is not completely coupled (or decoupled) will cause
the operator mechanism to stall.

Summary of Contents for PMH

Page 1: ...Removing the Fuse 20 INSTRUCTIONS For Operation Section Page Number RE FUSING How to Detect and Replace a Blown Fuse 23 Installing the Fuse in the Mounting 24 FINAL CHECKS BEFORE WALKING AWAY 25 IF OP...

Page 2: ...or the equipment Ratings for this gear are listed on a ratings label on the interior of the doors right hand doors only for double door models Transfer Control For instructions regarding field pro gra...

Page 3: ...out this instruction sheet as well as on labels affixed to the S C Source Transfer PMH Pad Mounted Gear Familiarize yourself with these types of messages and the importance of the various signal words...

Page 4: ...ED TERMINALS Always assume that both sets of power terminals on any Mini Rupter Switch or fuse are energized unless proved other wise by test by visual evidence of open circuit con ditions on both set...

Page 5: ...ng performed v Fuse Side These barriers are intended for tempo rary use to isolate the fuse from the contacts of Uni Rupter while work is being performed 19 CLOSING FUSES Closing a fuse into a faulted...

Page 6: ...ith the various compo nents and locations Figure 1 Low voltage control compartment Bolted cover provides access to input plug and shorting receptacle for Micro AT control Operator target indicates whe...

Page 7: ...Test keys for simulating overcurrent and loss of voltage on right source Right source voltage indicating lamp Manual automatic operation selector switch When in MANUAL prevents an automatic source tra...

Page 8: ...e of S C Micro AT Source Transfer Control Remote indication wiring provided with optional remote indication feature Catalog Number Suffix Y4 leads to a terminal block for user s connections Supervisor...

Page 9: ...Viewing window for visible verifica tion of switch position is removable for phasing To remove window loosen wing head screws and lift window off alignment bolts Current sensors furnished for attach m...

Page 10: ...dow is provided in the switch compartment to allow positive visual verification of switch blade posi tion see Figure 4 The operator target see Figure 1 signals OPERATOR CHARGED to indicate that the op...

Page 11: ...ges when voltage is present on the associated source The charging operation takes approximately 25 seconds If Control Power Is Lost and Operator Is Charged To manually operate the stored energy operat...

Page 12: ...ing the front barriers refer to the DANGER on pages 4 and 5 and the WARNING on page 10 Place the dual purpose front barrier in the slide in position whenever the Mini Rupter Switch is open When the ba...

Page 13: ...rator will stall in a par tially closed position To correct this condition follow the directions under IF OPERATOR STALLS on page 26 To restore the dual purpose front barrier to the normal suspended p...

Page 14: ...oor Distribution 14 4 kv and 25 kv S C ELECTRIC COMPANY s 663 503 INSTRUCTION SHEET Page 14 of 35 August 14 1995 MINI RUPTER SWITCHES Continued Figure 11 Alternate method of replacing front barrier us...

Page 15: ...urrent limiting fuse holders refer to S C Instruction Sheet 660 500 WARNING When selecting current limiting fuses the voltage rating of the fuses must conform to the recommendations in Appendix E Fail...

Page 16: ...nto which the fuse is to be installed See Figure 13 Insert the barrier into the slide in position using the Grappler as illustrated in Figure 14 Note that the barrier is supported on the Grappler pron...

Page 17: ...g the contacts will close the circuit which can cause a flashover and serious injury Always place the dual purpose front barrier in the slide in position whenever a fuse is open or is being removed fr...

Page 18: ...o carry and interrupt rated current 6 With the Grappler prongs pointed downward insert the longer prong into the pull ring of the fuse See inset of Figure 18 Then with one s face turned away close the...

Page 19: ...T 663 503 Page 19 of 35 August 14 1995 SWITCHING WITH UNI RUPTER Continued Figure 18 Closing the fuse Inset on right shows close up of Grappler in position to close the fuse Top inset shows close up o...

Page 20: ...positioned for opening stroke with longer prong inserted in the fuse pull ring WARNING A Note on Single Pole Switching In single pole switching of ungrounded primary three phase transformers or banks...

Page 21: ...ous injury or death 6 Place the dual purpose front barrier associated with the fuse to be removed in the slide in position Use the Grappler for this as illustrated in Figure 21 Note that the barrier i...

Page 22: ...ing the fuse from its hinge Touching the contacts will close the circuit which can cause a flashover and serious injury Always place the dual purpose front barrier in the slide in position whenever a...

Page 23: ...The blown fuse target retracts within the end fitting or holder when the blown fuse unit or interrupting module is replaced SML 4Z Power Fuse A fluorescent orange target in the translucent SML 4Z Hol...

Page 24: ...t current should also be replaced For instructions on replacing current limiting fuses in S C Holders refer to S C Instruction Sheet 660 500 S C Holders will accommodate the current limiting fuses lis...

Page 25: ...p is not lighted NOTE A lighted READY lamp indicates that the status of associated components is normal but an absence of illumination does not necessarily mean that the control is inoperative For exa...

Page 26: ...on See Figure 25 Restore the stored energy operator to a normal latched open condition after such an occurrence as follows 1 Make sure that the manual automatic operation selector switch is in MANUAL...

Page 27: ...serious injury or death 1 Access to pad mounted gear must be restricted only to qualified persons See Qualified Persons on page 2 2 Always follow safe operating procedures and rules 3 Before touching...

Page 28: ...ali fied persons Enclosure Finish The responsibility for ensuring that a finish protects the enclosure lies with both the manufacturer and the user S C Source Transfer PMH Pad Mounted Gear is finished...

Page 29: ...ast two min utes after the stored energy operators are charged before initiating a transfer operation APPENDIX A Dielectric Testing When high voltage dielectric tests are to be performed on S C Source...

Page 30: ...ities shown for S C Power Fuses with Uni Rupter represent the fault closing capabilities of the fuse with Uni Rupter when the fuse is closed with a purposeful thrust without hesitation Following the s...

Page 31: ...luded see ACCESSORIES on page 33 C11 Mounting Provisions for a Fault Indicator in each switch compartment Note Accommodates three phase indicator with single phase sensors Without viewing window in do...

Page 32: ...specified cable termination options suffixes U2 and U3 cannot be accommodated In addition when optional features M1 and M2 are both specified only one cable guide is provided at each switch terminal...

Page 33: ...T control communications card see optional feature Y8 on page 32 to user furnished personal computer For personal computers having 25 pin serial communication port TA 2320 For personal computers havin...

Page 34: ...5 15 5 6 30 40 100 6 30 40 50 65 100 3142 A3 3142 A1 3142 A2 3142 A1 3142 Cooper Power Systems McGraw Edison NX 8 3 8 3 15 5 15 5 1 5C 40C 50C 100C 1 5C 40C 1 5C 100C 3142 A3 3142 A1 3142 A2 3142 RTE...

Page 35: ...gs appropriate for system line to ground voltage i e fuses with a voltage rating lower than line to line voltage but greater than or equal to maxi mum system line to ground voltage S C can only recom...

Reviews: