Table 1. Field adjustable items in the Configure menu.
Field Adjustable Item
CONFIG:
Description
Displayed If
Operating State
or Range
①
SELECT PREFERRED
Assignment of “Left” Or “Right” as preferred source
CONFIG: SELECT BUS TYPE has been
factory set for “COMMON,” “PAD MNT,”
“VISTA COM,” or “SPLT COM” bus type
LEFT, RIGHT
UNBALANCE DETECT
Selection of
Unbalance Detection feature “On” or “Off”
CONFIG: UNBALANCE INSTALL has
been factory-set for the
In setting
ON, OFF
SELECT RETURN
Selection of
Hold, Auto, or Window option as the means
by which return-of-source transfer will be effected
Displayed at all installations
HOLD,
AUTO,
WINDOW
SELECT TRANSITION
Selection of
Open or Closed option as the type of
transition by which automatic return-of-source transfer will
be effected
CONFIG: SELECT RETURN has been
set for the
Auto or the Window return
setting
OPEN,CLOSED
RESTORE VALUES
②③
Sets all numeric field-adjustable items back to the factory-
settings
Displayed at all installations
PRESS ENTER
DWELL TIMER
Selection of transition-dwell time delay “IN” or “OUT”
Displayed at all installations
IN,
OUT
NORMALIZE LEFT
Means of compensating for any output-voltage magnitude
unbal ance and/or phase-angle unbalance between
voltage-sensing devices on the left source
CONFIG: VOLTAGE SENSING has
been factory-set for the
4 Wire voltage
sensing setting
PRESS ENTER
NORMALIZE RIGHT
Means of compensating for any output-voltage magnitude
unbal ance and/or phase-angle unbalance between
voltage-sensing devices on the right source
CONFIG: VOLTAGE SENSING has been
factory set for the
4 Wire voltage
sensing setting
PRESS ENTER
SET BASE LEFT
Means of calibrating control to a known voltage on Phase 2
of the left source
Displayed at all installations
105-130 VOLTS
(120 VOLTS)
SET BASE RIGHT
Means of calibrating control to a known voltage on Phase 2
of the right source
Displayed at all installations
105-130 VOLTS
(120 VOLTS)
ACCESS CODES
Selection of alternative access code
Displayed at all installations
4 DIGITS MIN .,
7 DIGITS MAX .
COM Ø BIT RATE
Selection of communication port data transfer bit rate
Optional communications card has
been installed
2400, 4800,
9600, 19200,
or 38400 BPS
(19200 BPS)
①
Factory settings are shown in boldface type .
②
Always normalize the left and right sources and set the base volt-
ages on Phase 2 of the left and right sources after executing a
Config:
Restore Values command . The following parameters (even if the dis-
play shows correct values) also must be manually configured: Loss of
Source, Return of Source, Over Voltage, and Unbalance . Failure to do
so may result in erratic operations .
③
The
Config: Restore Values command has been removed from
firmware version 2 .6 .1 and subsequent releases .
Quick-Start Programming
6 S&C Instruction Sheet 515-530