Table 1. Field adjustable items in the Configure menu.

Field Adjustable Item

CONFIG:

Description

Displayed If

Operating State

or Range

SELECT PREFERRED

Assignment of “Left” Or “Right” as preferred source

CONFIG: SELECT BUS TYPE has been

factory set for “COMMON,” “PAD MNT,” 

“VISTA COM,” or “SPLT COM” bus type

LEFT, RIGHT

UNBALANCE DETECT

Selection of 

Unbalance Detection feature “On” or “Off”

CONFIG: UNBALANCE INSTALL has 

been factory-set for the 

In setting

ON, OFF

SELECT RETURN

Selection of 

Hold, Auto, or Window option as the means 

by which return-of-source transfer will be effected 

Displayed at all installations

HOLD, 

AUTO

WINDOW

SELECT TRANSITION

Selection of 

Open or Closed option as the type of 

transition by which automatic return-of-source transfer will 

be effected

CONFIG: SELECT RETURN has been 

set for the 

Auto or the Window return 

setting

OPEN,CLOSED

RESTORE VALUES

②③

Sets all numeric field-adjustable items back to the factory-

settings

Displayed at all installations

PRESS ENTER

DWELL TIMER

Selection of transition-dwell time delay “IN” or “OUT”

Displayed at all installations

IN,

 OUT

NORMALIZE LEFT

Means of compensating for any output-voltage magnitude 

unbal ance and/or phase-angle unbalance between  

voltage-sensing devices on the left source

CONFIG: VOLTAGE SENSING has  

been factory-set for the 

4 Wire voltage 

sensing setting

PRESS ENTER

NORMALIZE RIGHT

Means of compensating for any output-voltage magnitude 

unbal ance and/or phase-angle unbalance between  

voltage-sensing devices on the right source

CONFIG: VOLTAGE SENSING has been

factory set for the 

4 Wire voltage 

sensing setting

PRESS ENTER

SET BASE LEFT

Means of calibrating control to a known voltage on Phase 2 

of the left source

Displayed at all installations

105-130 VOLTS

(120 VOLTS)

SET BASE RIGHT

Means of calibrating control to a known voltage on Phase 2 

of the right source

Displayed at all installations

105-130 VOLTS

(120 VOLTS)

ACCESS CODES

Selection of alternative access code

Displayed at all installations

4 DIGITS MIN ., 

7 DIGITS MAX .

COM Ø BIT RATE

Selection of communication port data transfer bit rate

Optional communications card has  

been installed

2400, 4800,

 9600, 19200,

or 38400 BPS 

(19200 BPS)

  Factory settings are shown in boldface type .

 Always normalize the left and right sources and set the base volt-

ages on Phase 2 of the left and right sources after executing a 

Config: 

Restore Values command . The following parameters (even if the dis-
play shows correct values) also must be manually configured: Loss of 

Source, Return of Source, Over Voltage, and Unbalance . Failure to do 
so may result in erratic operations .

 The 

Config: Restore Values command has been removed from 

firmware version 2 .6 .1 and subsequent releases .

Quick-Start Programming

6    S&C Instruction Sheet 515-530

Summary of Contents for Micro-AT

Page 1: ...uction Sheet 2 Proper Application 2 Warranty 2 Safety Information Understanding Safety Alert Messages 3 Following Safety Instructions 3 Replacement Instructions and Labels 3 Safety Precautions 4 Quick...

Page 2: ...gnate a location where it can be easily retrieved and refer to Proper Application WARNING The equipment in this publication is only intended for a specific application The application must be within t...

Page 3: ...ecautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If...

Page 4: ...h clothing in accordance with safe operating procedures and rules 4 SAFETY LABELS Do not remove or obscure any of the DANGER WARNING CAUTION or NOTICE labels 5 OPERATING MECHANISMS Do not remove or di...

Page 5: ...Next item key before the Quit key NOTICE When changing the Select Bus Type or Select Preferred settings in the Configure menu the Micro AT control will power down and reboot A System Startup event wi...

Page 6: ...n factory set for the 4 Wire voltage sensing setting PRESS ENTER NORMALIZE RIGHT Means of compensating for any output voltage magnitude unbal ance and or phase angle unbalance between voltage sensing...

Page 7: ...EEEEEEEEECHANGE The other field adjustable items of the Configure menu can be changed in the same manner Procedures for normalizing the left and right sources setting the base voltages on the left and...

Page 8: ...ll now look like this ECONFIG ESETEBASEELEFT E120E VOLTSEEEEEEEEE_____ Enter the desired left source base voltage If for example 117 volts is the desiredvalue the 1 1 and 7 keyswouldbepressed followed...

Page 9: ...th the communi cations card proceed to Step 3 Here s the display for CONFIG COM BIT RATE with its factory setting 19200 BITS PER SECOND CONFIG ECOME0EBITERATE E19200EEEEEEEEEEEEECHANGE Ifadifferentdat...

Page 10: ...ear which if equaled or exceeded will result in control initiating auto matic transfer Also if the Hold return setting has been selected unbal ance level on alternate source or unbalance level on sour...

Page 11: ...f the lockout level is to be set to some other value press the Change key If the display prompts that the access code number to be reentered do so The display will now look like this CURRENT LOCKOUT L...

Page 12: ...a time window in which an automatic return of source transfer can occur the window is adjustable from 1 minute to 3 hours Transfer will take place after the return of source time delay has expired pr...

Reviews: