TY-JS-220607-001
13
changing is available. If the password is incorrect, it will return to temperature display. If
there is no button pressed in 20 seconds, the temperature controller will automatically exit
from the data setting status. Press “RST” button to save the data and exit.
7. Restore factory setting:
Press and hold
and
buttons for 3 seconds and it indicates “rE” and the supplier
data and user data will restore to default value. Continue to press those buttons for
another 3 seconds, it will return to temperature display.
8. Parameter setting table
Data
Function
Range
Default
value
Description
Remark
F0
Setting temperature of
low temperature circuit
-20~40. 0
℃
25.0
℃
Setting
menu of low
temperature
circuit
F1
Temperature difference
coefficient
-15.0- 05.
-02.0
F2
Refrigeration return
difference
0.1~3.0
℃
0.8
℃
F3
Control mode
00~01
00
01=intelligent control mode
00=constant temperature
control mode
F4
Setting temperature of
high temperature circuit
-20~40.0
℃
30.0
℃
Setting
menu of
high
temperature
circuit
F5
Temperature difference
coefficient
-15.0~5.0
-0.20
F6
Refrigeration return
difference
0.1~3.0
℃
0.8
℃
F7
Control mode
00~01
01
01=intelligent control mode
00=constant temperature
control mode
F8
Ultrahigh water
temperature alarm
1.0~60.0
℃
10.0
℃
Shared by
high & low
temperature
circuit
F9
Ultralow water
temperature alarm
1.0~20.0
℃
15.0
℃
F10
Ultrahigh room
temperature alarm
40.0~50.0
℃
45.0
℃
F11
Highest water
temperature under
intelligent control mode
F12~40.0
℃
30.0
℃
Intelligent control mode
valid
F12
Lowest water temperature
under intelligent control
mode
1.0
℃
~F11
20.0
℃
F13
Password
00~99
08
00=cancel
password
function
F14
Water flow alarm of low
temperature circuit
0.0~20.0
2.0L/min
F15
Water flow alarm of high
temperature circuit
0.0~20.0
0.5L/min
F16
Communication address
1~247
1