<8> Specifications
CWFL- 3000
Model
CWFL-3000BT
CWFL-3000ET
Voltage
AC 1P 220
AC 3P 380 V
Frequency
60 Hz
50 Hz
Current
6.8~30 A
3~12.3 A
Compressor power
2.70 KW
2.65 KW
3.67 HP
3.61 HP
Nominal cooling
capacity
1706 Btu/h+26136 Btu/h
1706 Btu/h+25726 Btu/h
0.5 KW+7.66 KW
0.5 KW+7.54 KW
430 Kcal/h+6586 Kcal/h
430 Kcal/h+6483 Kcal/h
Refrigerant
R-22 / R-410a
Refrigerant charge
2100 g
2450 g
Precision
±1
℃
Reducer
Capillary
Protection
Overcurrent protection for compressor, flow alarm, over temperature
alarm
Pump power
0.55W+0.75 KW
0.37 KW+0.75 KW
Tank capacity
6 L+34 L
Inlet and outlet
Rp1/2”+Rp1”
Max. lift
41 M+55 M
43 M+53 M
★
Max. flow
50 L/min+83 L/min
40 L/min+70 L/min
N.W
180 Kgs
G.W
230 Kgs
Dimension
102X65X117 cm (L X W X H)
Package dimension
111X85X140 cm (L X W X H)
★
The max. flow is obtained by testing the pump individually on test