background image

San Telequip Private Limited., 
504/505 Deron Heights, Baner Road, Baner 
Pune 411045, Mah, India 
Phone: +91-20-27293455,9764027070,8390069393               Connecting. Converting. Leading! 

email:

[email protected]

_______________________________________________ 

Page 10 of 65,  

 

3.4  Network Configuration 

 
In  this  section,  IP,  Subnet  Mask  and  overall  connectivity  settings  can  be  accessed.  When  on 

Redundancy Mode

 the  device  will  have  the two LAN ports connected

1

 to the Network, but the signal 

will  flow  through  one  of  them.  In  the  case  one  line  is  out  due  to  any  reason  there  will  still  be  another 
route so the signal can keep flowing.  
 

 

Fig. 3. 4

 

 
 

 

 

Note

1

you  can  still  connect  only  one  LAN  port  to  the  device,  though  you  can  still  change  the  settings  in  it,  there  won’t  be  a 

Redundancy

 function. 

 

Summary of Contents for SC10E4IM Series

Page 1: ... 4 2 2 Factory Default Settings 5 3 Configuration and Setup 6 3 1 Locating and IP configuring using Utility 6 3 2 Configuration using Web Interface 7 3 2 1 Configure Automatic IP Assignment with DHCP 9 3 3 Web Overview 9 3 4 Network Configuration 10 3 5 Basic Settings 12 3 5 1 COM Settings 12 3 5 2 Operation Mode 13 3 5 3 Serial Settings 13 3 5 4 VCOM Settings 14 3 5 5 TCP Settings 17 3 5 6 Slave ...

Page 2: ..._____________________ ii 3 8 1 Log Settings 38 3 8 2 System Log 39 3 8 3 Data Log 40 3 8 4 Modbus Statistic 41 3 8 5 Time 43 3 8 6 Security 44 3 8 7 Import Export 45 3 8 8 Factory Default 45 3 9 Restart 47 4 Applications and Examples 48 4 1 Using ID offset range mapping 48 4 2 Using Alias ID mapping 49 5 Specifications 49 5 1 Hardware 50 5 2 Software 52 Appendix Configuration using Telnet Interfac...

Page 3: ...CP the Modbus Gateway offers a convenient solution to connect existing devices or controllers running Modbus serial protocol Modbus ASCII or Modbus RTU to an Ethernet network The SC10E4IM Series are standard Modbus Isolated gateways that convert between Modbus TCP and Modbus RTU ASCII protocols The SC10E4IM Series support 16 simultaneous TCP master and 32 simultaneous requests for each TCP master ...

Page 4: ...re selectable RS 485 RS 422 interface Dual 10 100 Mbps Ethernet ports for network redundancy Convert between Modbus TCP and Modbus RTU ASCII 2 Ethernet port and 4 RS 422 485 ports Easy hardware setup and configuration 2 Getting Started 2 1 Inside the Package Inside the purchased you will find the following items Table 2 1 Item Quantity Description SC10E4IM Series 1 Modbus Gateway Din Rail 1 Panel ...

Page 5: ...ettings Network Defaults Note that the Modbus Gateway comes with one IP address for redundant Ethernet interfaces Table 2 2 Interface Device IP Subnet mask Gateway IP LAN 1 10 0 50 100 255 255 0 0 10 0 0 254 Modbus Default Table 2 3 Parameter Default Values Modbus Master TCP Settings TCP Master Mode TCP Master Port 502 Modbus Slave SC10E4I M Mode RTU Slave Serial Configuration RS 485 422 9600 bps ...

Page 6: ...on SysContact of SNMP Contact SNMP Enable Read Community Public Write Community Private SNMP Trap Server 0 0 0 0 Note you can press the Reset button on the front panel for 5 seconds see Sec 3 8 8 and 3 9 to restore the server to factory default settings 3 Configuration and Setup 3 1 Locating and IP configuring using Utility First please install our configuration utility program that comes with the...

Page 7: ...Leading email info santelequip com_______________________________________________ Page 7 of 65 3 2 Configuration using Web Interface Every SC10E4IM Modbus Gateway device is equipped with a built in Web server in the firmware Therefore it can be accessed by using a browser for configuration by entering the device s IP see Sec 2 4 for default value Fig 3 1 ...

Page 8: ...069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 8 of 65 Fig 3 2 This type of configuration is the most user friendly most recommended and most common method used on your SC10E4IM Modbus Gateway Please go to its corresponding section for a detailed explanation ...

Page 9: ...tarted it will be automatically configured 3 3 Web Overview In this section only current information on the device s status and settings will be displayed Fig 3 3 Model Name as its name implies shows the device s model Device Information displays information on the Kernel version as well as the AP Network Information here you may find the Mode in which the device is currently working on Dual Subne...

Page 10: ... In this section IP Subnet Mask and overall connectivity settings can be accessed When on Redundancy Mode the device will have the two LAN ports connected1 to the Network but the signal will flow through one of them In the case one line is out due to any reason there will still be another route so the signal can keep flowing Fig 3 4 Note1 you can still connect only one LAN port to the device thoug...

Page 11: ...764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 11 of 65 When the device is set on Dual Subnet Mode a set of two IP addresses can be used without having Redundancy This is especially useful when using two different networks Fig 3 5 ...

Page 12: ...one 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 12 of 65 3 5 Basic Settings 3 5 1COM Settings This section is responsible for settings on your physical ports may them be COM or serial Fig 3 6 ...

Page 13: ...fer is under an RTU format ASCII Slave when working as a slave node the device will wait and accept request from its own master data transfer is under an ASCII format ASCII Master when working as a master node the device will issue commands to the slave node data transfer is under an ASCII format 3 5 3Serial Settings This section has the following selections RS 422 RS 485 Software Selectable Defau...

Page 14: ...ce to set your device as either a Master or a Slave in your network You will need a VCOM setting proceed to go to Basic Settings VCOM Settings and tick on the VCOM s Enable box to allow configuration on the port selected The options for Master are similar the only difference being on the device s function Fig 3 7 Choose whether your device conforms as an RTU or ASCII which is the VCOM Mode VCOM Po...

Page 15: ...________ Page 15 of 65 Fig 3 8 VCOM inactivity s Time Out can be set as well which is the period of time allowed between actions with a maximum of 600 minutes or 10 hours If no action has been taken after this period VCOM connection will be automatically interrupted by the system It is important to note that alternatively these settings can be chosen to be applied to All VCOMs if needed by checkin...

Page 16: ...r Road Baner Pune 411045 Mah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 16 of 65 Fig 3 9 Click on Save Configuration to keep all changes made ...

Page 17: ...oceed to choose whether to enable TCP ticking on the Enable box Fig 3 10 TCP Slave When on this mode the device will run on Slave mode and wait to receive Modbus requests from the Master data transmission is done under a Modbus TCP format Remote IP Address shows the device s slave node IP address TCP Port shows the device s slave node TCP port VCOM inactivity s Time Out can be set as well which is...

Page 18: ...Operation Mode choose whether the device is going to be a Slave or a Master Remote IP Address refers to the IP belonging to the device that is going to be controlled from SC10E4IM this option is not available when the device is set as a Master TCP Port is the port through which the signal is going to be relayed upon And again there is a TCP Inactivity Time Out with the same 10 hours maximum value ...

Page 19: ...e ID Map The system uses the Modbus ID to route Modbus request commands from the master node to the respective slave node it is paramount to define ID maps for each slave node For every slave node there must be a correct Virtual ID Alias ID and Real ID defined in the maps Offset mode can be used when device IDs to be mapped for Modbus master and slaves are sequential whereas Alias mode can be used...

Page 20: ... port then select Alias Mode or Offset Mode to modify the range and offset as you needed Alias Mode maps a virtual ID to a real ID each at the time Alias ID which refers to a Virtual ID for the reading Master node Real ID which is the real ID from the slave node Offset Mode which refers to a range of defined ID maps Slave ID Start Virtual ID s start number Slave ID End Virtual ID s end number Slav...

Page 21: ... Connecting Converting Leading email info santelequip com_______________________________________________ Page 21 of 65 4 Applied Modes of Multiple Protocols 4 1 Assign different IP to each serial device Serial side devices is Master Modbus TCP side device is slave Configuration SC10E4NIM can support maximum up to 16 TCP connections ...

Page 22: ...4 505 Deron Heights Baner Road Baner Pune 411045 Mah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 22 of 65 COM Settings ...

Page 23: ...eron Heights Baner Road Baner Pune 411045 Mah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 23 of 65 VCOM Settings TCP Settings ...

Page 24: ... 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 24 of 65 Slave ID MAP 4 2 The same IP but different I O Ports SC10E4NI M Modbus TCP side is Master Serial side is slave SC10E4NI M to listen TCP port 501 502 503 ...

Page 25: ...Deron Heights Baner Road Baner Pune 411045 Mah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 25 of 65 COM Setting VCOM Setting ...

Page 26: ...Deron Heights Baner Road Baner Pune 411045 Mah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 26 of 65 TCP Settings Slave ID MAP ...

Page 27: ...45 Mah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 27 of 65 4 3 The same IP and the same Port no Modbus TCP side is Master Serial side devices are Slave COM Setting ...

Page 28: ...Deron Heights Baner Road Baner Pune 411045 Mah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 28 of 65 VCOM Setting TCP Setting ...

Page 29: ...oad Baner Pune 411045 Mah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 29 of 65 Slave ID MAP 4 4 Configuration for Virtual Serial Port COM Setting ...

Page 30: ...Deron Heights Baner Road Baner Pune 411045 Mah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 30 of 65 VCOM Settings TCP Setting ...

Page 31: ...ad Baner Pune 411045 Mah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 31 of 65 Slave ID MAP VCOM Port Mapping in Serial Manager COM2 COM4 COM7 COM8 ...

Page 32: ...ited 504 505 Deron Heights Baner Road Baner Pune 411045 Mah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 32 of 65 ...

Page 33: ...tact information If you wish to make the information available for public viewing by a Read Community simply check the Enable SNMP box and fill in Public_viewers in Read Community field If you wish to allow a group of people called Power_users to change the information enter Power_users in Write Community If you allow a trap server to collect device information please fill in SNMP Trap Server with...

Page 34: ...ts Baner Road Baner Pune 411045 Mah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 34 of 65 Fig 3 15 Trap received in MIB Browser Fig 3 16 ...

Page 35: ...____________________________________________ Page 35 of 65 5 2 Modbus In Modbus settings you could select whether to enable Modbus Exception or not If the Modbus slave produces no response timeout occurs it may then be necessary for the gateway to return an Exception and setting the Response timeout as follows Configure timeout for each COM port Configure timeout for TCP VCOM port Fig 3 157 ...

Page 36: ...ication password is changed Fig 3 168 When enabled an E mail alert would be sent to the designated E mail address in the E Mail Settings To setup an email alert function you first need to configure the recipient s email address and the mail server Please check the following 1 Your email server should be valid check with your system Admin 2 Your system is Internet enabled else you will not receive ...

Page 37: ... 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 37 of 65 Fig 3 179 Note Before configure the Email warning function you must set a Mail Server Test Mail Password change Event Mail Received Fig 3 20 ...

Page 38: ...o santelequip com_______________________________________________ Page 38 of 65 5 1 System 5 1 1 Log Settings This section lets you change the way your report will be shown on your Log Enable syslog server Enabling this option would allow sending log events to a Syslog server Syslog Server IP Enter your PC IP address Syslog Server Service Port Specify the PC port Fig 3 21 ...

Page 39: ...___________________________________________ Page 39 of 65 5 1 2 System Log This section merely shows a list of system running events currently with every event s properties displayed as well as the option to clear them all Fig 3 22 Click on Last Page to go to the last page Click on Show All Events to show all events in one page Click on Clear All Event to clear the events stored in the device ...

Page 40: ...verting Leading email info santelequip com_______________________________________________ Page 40 of 65 5 1 3 Data Log Event filtering is available in this section for analysis a number of options are available for a customized analysis Traffic in the system can be done here as well Fig 3 183 Filtering on Slave ID only Select device ID1 Fig 3 194 ...

Page 41: ...une 411045 Mah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 41 of 65 Filter by Function code only Selected 03 holding Resister Fig 3 25 5 1 4 Modbus Statistic ...

Page 42: ...r Road Baner Pune 411045 Mah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 42 of 65 All ports information is available in this section Fig 3 206 ...

Page 43: ...____________ Page 43 of 65 5 1 5 Time Date and time can be set manually or using Network Time Protocol NTP to automatically synchronizes with a Time Server For auto synching check the box below NTP Server Settings Obtain date time automatically proceeding then to fill the IP address or hostname for it If a hostname is entered the DNS server must be configured properly a Time Zone can be selected a...

Page 44: ... 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 44 of 65 5 1 6 Security Password settings are available at this section as well as device s console configuration settings allowing users to limit the way they are able to configure the device Fig 3 228 ...

Page 45: ...configurations are set and the device is working properly you may want to backup Export your configuration Backup can be used when the new firmware is uploaded and it is reset to a factory default settings it is done to prevent accidental loading of incompatible old settings The backup file could also be used to efficiently deploy multiple Modbus Gateways of similar settings by restoring the setti...

Page 46: ...ner Pune 411045 Mah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 46 of 65 A simple return to Factory Default is available in our SC10E4IM Series Fig 3 30 ...

Page 47: ...d Baner Pune 411045 Mah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 47 of 65 5 2 Restart Restart is just a click away in our Modbus Series Fig 3 31 ...

Page 48: ...p com_______________________________________________ Page 48 of 65 6Applications and Examples On your device two different ID mapping definitions are given by the system both using Modbus ID to route the requesting command from the Master to the Slave node 6 1 Using ID offset range mapping If the Slave ID is continuous it is recommended to use the Offset mode Fig 4 1 Fig 4 1 Fig 4 2 ...

Page 49: ...ndia Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 49 of 65 6 2 Using Alias ID mapping This is only recommended if the ID is not continuous Fig 4 3 Fig 4 3 Fig 4 4 7 Specifications ...

Page 50: ...02 3 Compliance Dual Port 10 100Mbps Auto Detection Connection RJ 45 Auto MDI MDI X No Protection Built in 1 5 KV Magnetic Isolation Protocol ICMP TCP IP UDP HTTP Telnet DNS DHCP Client SNMP SMTP NTP ARP Serial Serial Interface RS 422 RS 485 Software Selectable Default RS 485 Isolated 2 5KV Serial Connector Terminal Block 5 Pin Connector type Serial Port Communication Baud rate 300 bps 921600 bps ...

Page 51: ...peration SC10E4IM 40oC 80oC Storage 40oC 85oC Humidity 5 95 Non condensing 5 Pin Terminal Block for RS 485 RS 422 connections Pin RS 422 4 Wire RS485 Full Duplex 2 Wire RS 485 Half Duplex 1 SG Signal Ground SG Signal Ground 2 RX D DATA 3 RX D DATA 4 TX N A 5 TX N Ag For RS485 4 Wire RS422 For RS485 2 Wire Signal of SC10EIM Will Connect to TX RX of your device TX RX of your device RX TX of your dev...

Page 52: ...g Telnet Interface The SC10E4IM Modbus Gateway device also has a built in Telnet server program such that users can also configure the device using Telnet console software To start the device configuration using Telnet console please go to Windows Command software Start Run and use telnet command to access the device In the Run window enter telnet device_IP_address For example telnet 10 0 50 100 i...

Page 53: ...info santelequip com_______________________________________________ Page 53 of 65 described below On your Desktop go to Start All Programs Accessories Communications HyperTerminal Apx 1 Fill the Name entry with a name of your choice and select your favorite icon The Connect to window will pop out Apx 2 Select TCP IP Winsock on Connect using then check OK Here Session 1 ...

Page 54: ...ah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 54 of 65 Hyperterminal will appear and then type telnet 10 0 XXX XXX device s IP to get into the device s login menu Apx 3 ...

Page 55: ...ndia Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 55 of 65 Once the correct username and password are entered you will see the configuration menu of the device on the display Apx 4 ...

Page 56: ...steps before mentioned are for Win XP in order to enable telnet in Win 7 follow the steps below 1 Go to Start and on the Run box type cmd Fig Apx 5 2 A pop out window will appear as follows type pkmgr iu TelnetClient and press Enter your Telnet must be configured by now If you wish to confirm if it is working follow the next step Apx 6 3 Go to Control Panel under Programs and Features press Turn W...

Page 57: ...91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 57 of 65 Apx 7 After these steps are completed telnet can be accessed by typing the device s IP using the Run command window on the Start programs Apx 8 ...

Page 58: ...________ Page 58 of 65 Apx 9 Its main menu is a command driven interface it will look as follows Apx 10 Most options appear the same as the ones in web browsing mode the difference being that they have to be accessed by entering the number corresponded to that option For accessing each function please follow the steps described below On the Main Screen 1 Overview a more detailed description of thi...

Page 59: ...045 Mah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 59 of 65 Apx 11 Main Screen 2 Networking a more detailed description of this section is given on Sec 3 4 Apx 12 ...

Page 60: ...______________________________________________ Page 60 of 65 Main Screen 2 Networking 1 LAN 1 Settings a more detailed description of this section is given on Sec 3 4 Apx 13 Main Screen 2 Networking 2 DNS Settings a more detailed description of this section is given on Sec 3 4 Apx 14 Main Screen 2 Networking 3 SNMP Settings a more detailed description of this section is given on Sec 3 6 1 ...

Page 61: ... email info santelequip com_______________________________________________ Page 61 of 65 Apx 15 COM Port Configuration telnet Main Screen 3 COM Port Setting a more detailed description of this section is given on Sec 3 5 1 Apx 16 Main Screen 3 COM Port Setting 1 16 Select Port 3 COM Port Settings a more detailed description of this section is given on Sec 3 5 1 ...

Page 62: ...045 Mah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 62 of 65 Apx 17 Main Screen 4 Security a more detailed description of this section is given on Sec 3 8 6 Apx 18 ...

Page 63: ...onverting Leading email info santelequip com_______________________________________________ Page 63 of 65 Main Screen 4 Security 1 Change Password a more detailed description of this section is given on Sec 3 8 6 Apx 19 Reset to Factory Defaults Main Screen 5 Set to Default a more detailed description of this section is given on Sec 3 8 8 Apx 20 ...

Page 64: ...1045 Mah India Phone 91 20 27293455 9764027070 8390069393 Connecting Converting Leading email info santelequip com_______________________________________________ Page 64 of 65 Restart Main Screen 6 Restart a more detailed description of this section is given on Sec 3 9 Apx 21 ...

Page 65: ...the result of SAN s activities The warranty doesn t cover however equipment which has been damaged due to accident misuse abuse such as Use of incorrect power supply connectors or maintenance procedures Use of accessories not sanctioned by us Improper or insufficient ventilation Improper or unauthorized repair Replacement with unauthorized parts Failure to follow Our operating Instructions Fire fl...

Reviews: