Digital Motor Protection Realy

DSP-C Series

 

 

 

 

 

     

 

 

 

 

 

   

 

 

 

 

   

   

 

 

 

   

 

 

 

 

   

 

 

 

 

 

 

   

 

 

   

 

 

 

 

 

   

 

 

   

 

 

 

 

   

   

 

 

   

 

 

   

   

 

 

 

   

 

 

   

   

 

   

 

   

 

 

 

 

   

 

 

 

 

 

   

   

   

 

     

     

 

 

 

 

   

 

 

 

 

 

     

 

 

 

 

 

 

 

 

 

 

 

   

   

 

 

 

   

 

   

     

   

 

 

 

   

 

 

 

 

 

     

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

   

 

 

 

 

 

 

 

   

 

 

 

     

 

 

 

 

 

 

 

   

 

 

 

 

 

   

 

 

   

 

 

 

 

   

 

 

 

 

   

 

 

 

 

 

 

 

   

 

 

 

     

   

 

 

   

   

   

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

   

 

   

 

 

 

     

 

 

   

 

 

 

 

   

 

   

  

   

 

 

 

   

 

 

   

   

 

 

 

 

 

 

 

 

Mode

Function

Description

Factory

2sec

0.1sec

OFF

2sec

50%

OFF

90

6500

5

OFF

OFF

hr

9600

1

1

60

0.1

2400, 9600, 19200, 38400bps/CCM,CCL Type

to decide communication
speed

bPS

Addr

trIP

to put self-address to
communicate with pc

trip information in order:faulty phase and faulty value is
appeared alternatively as controlling "UP" or "DN" key

range of number:#1 ~ #250/CCM,CCL Type

to show latest number of 8 trip
cause

t-AUt

to preset total possible time
available for executing defined
times of auto reset

30min ~ 60min/adjustable

0.1 ,1~ 300sec/adjustable

to preset auto reset time

At

rESEt

to decide how to reset trip
state

*Hr:manual reset/Password input → main trip,

Ec-tb trip(Aux)

*Er:electrical reset : "Reset" key, "CLR" Key, Control

power-off

*AuL-#(n times):Auto reset by followed condition/

max n=9:n=1:possible to do only by entering password

*Password reset : reset is done by comming out from

operating mode after input password

*Auto:only available for "OC" trip

*OFF:3 phase current(L1,L2,L3),GF current
*ON:[3 phase current] ,GF current] + [AWT]
*interval time between each displayed factor : 3sec

to indicate additional factor
besides basic factor to indicate
running operation value in a order

rOtA

tEmP

dC

ALt

AL

to protect over temperature

*8sec, 1~150OC, sensed by PT100, only for CCM-PT/

CCL-PT type

*to transfer maximum current of 3 phase current into 20mA
,and 4mA means zero ampere output/CTM,CTL Type

to decide max current to
change into 20mA

AU-O

to preset a limit of
accumulated working time
necessary to give alarm.

0.1 hr ~6553.5 hr in 0.1 hr step

to preset alarm level
rate(%) to OC

* % range : 65%~100%/adjustable ("AL" is preset in
"Auo" mode)

Edt

EOt

UC

Ut

Ub

to preset a kind of AUX trip
output

*oFF:same as main output

*trip output for AL/Uc/Shoc/Ec is independent from

main trip → this trip output is reset naturally if trip

cause is clear

*Ec-tb: only for ground fault protection ,but reset is not

happened even though trip cause is clear

*trip is stored in “trip” mode as a one of 8 latest event

*formular:[(max-min) /max]*100 [%]
*range:30% ~ 90% *minimum available current:0.3A

to preset current unbalance
rate(%) among 3 phasea

to preset trip delay time to
protect under current

1 ~ 30sec/adjustable

to preset a range to protect
under current

*10 type : 0.4A~under "OC" preset value
*70 type : 4.9A~under "OC"preset value

0.1 ~30sec/adjustable

to preset operating trip delay
time to protect ground fault

to preset starting trip delay time

1 ~ 25sec/adjustable

11

Summary of Contents for DSP VIP-Series

Page 1: ...or Protection Relay Digital Motor Protection Relay D I G I TA L S TA N D A R D P R O T E C T I O N Digital Motor Protection Relay www samwhadsp com New Leader Optimized Preventive Maintenance Solution...

Page 2: ...ing data base DB up based on 485 Modbus network Analyzing and managing DB DATA in order to check the motor condition and to make alarm in case of unstable condition able to preset alarm level for each...

Page 3: ...4 20mA output for load current insulation resistance measureemnt vibrated frequency detection through 4 20mA output from sensor RS485 or Ethernet communication Especially Current Resistance type can m...

Page 4: ...r current Phase loss load current Reverse phase load current Current unbalance Pre alarm Protection Locked rotor Shock Stall Short Circuit Ground fault Temperature Control ON OFF Load current Standard...

Page 5: ...Under current Protection Phaseloss load current Reverse phase load current Current unbalance Pre alarm Locked rotor Shock Stall Short Circuit Ground fault Temperature Control ON OFF Indication Load cu...

Page 6: ...put main 95 96 b 98 a aux 05 06 b 08 a b is selected in out mode factory default Control power is on unchanged output state 95 96 b 98 a aux 05 06 b 08 a TRIP operation state 95 96 a 98 b 05 06 a 08 b...

Page 7: ...ux trip output alarm RS 485 Modbus RTU External ZCT embedded if Z1 Z2 is not marked Input Output DSP COM DSP CCM E DSP CCM DSP CTM DSP CCTM DSP CSM Power Trip LED Test Reset 9Pin D sup to connect mete...

Page 8: ...han preset value is sensed Ground fault EC to ptotect over temperature sensed by PT100 8sec only for CCM PT CCL PT type Technical Specification DIV Description Load Current range 10 Type 70 Type With...

Page 9: ...EC 60255 5 Circuit Ground Circuit Circuit 1 2 50uS 5KV Control Circuits 1 2 50uS 5KV Power Realy output Level 4 4KV 1 MHz Burst Immunity Test IEC 61000 4 18 2 5KV Positive Negative under 2sec Electros...

Page 10: ...for preset data is completed by pressing both SET and CLR key in the same time 6 CLR key While each factor is rotated one of rotated factor is fixed by pressing CLR key After fixing a operating factor...

Page 11: ...eset a range to protect over current OC dt to preset starting trip delay time dEF dEF definite Inv inverse OtC to select time current chracteristics for Ot to preset operating trip delay time definite...

Page 12: ...ate additional factor besides basic factor to indicate running operation value in a order rOtA tEmP dC ALt AL to protect over temperature 8sec 1 150OC sensed by PT100 only for CCM PT CCL PT type to tr...

Page 13: ...Digital Motor Protection Realy DSP C Series T I Characteristic to protect over current Inverse Definite Samwha DSP 12...

Page 14: ...customer not used for external CT type Accessory External CT Cable ZCT DSP CABLE 12 DSP C1 DSP CC DSP C2 DSP C3 DSP C4 DSP CABLE 18 DSP CABLE 30 DSP CABLE 50 DSP ZCT XX 100mA 1 5mA XX Inner diameter...

Page 15: ...C Series wha Sam DSP Ltd ktTpp L1 L2 L3 65 70 75 80 85 90 95 100 Amp Ec Sec wha Sam DSP Ltd ktTpp L1 L2 L3 65 70 75 80 85 90 95 100 Amp Ec Sec Application Sequence Diagram Embedded ZCT Type External...

Page 16: ...Samwha DSP 15 Digital Motor Protection Realy DSP C Series 76 00 69 00 14 50 23 50 16 50 50 00 76 00 69 00 CUTTING HOLE SIZE 65 Wire Through Type Dimension Terminal Type Meter...

Page 17: ...Order CT Ratio Dimension Burden VA Class 1 0 3 0 3CT ithDSP Specification DSP 3CT Model CT Ratio 100 5A 150 5A 200 5A 300 5A 400 5A Class Burden VA Maximum Voltage Withstand Voltage Cable Length Max I...

Page 18: ...mA 100 250 600 1000 25 C 70 C 35 C 80 C AC 2000V 1min DC 500V 10MOhm 50 60Hz 10 Screw Fix 170 215 345 700 Order Form Item Reference Code Inner Diameter mm ZCT 30 50 80 120 DSP ZCT 30N DSP ZCT 50N DSP...

Page 19: ...18 DSP ZCT DSP ZCT Zero Phase Current Transformer 120 Zero Phase Current Transformer...

Page 20: ...m Optimized Preventive Maintenance Solution D I G I TA L S TA N D A R D P R O T E C T I O N DSP 91 69 693 2 3 TEL 031 454 3551 FAX 031 454 3552 HEAD OFFICE 69 LS ro 91beon gil Gunpo si Gyeonggi do Tel...

Reviews: