PAGE 11 of 61 HO-7-1237 & HO-4-1234 OIL-FIRED HEATERS
© SAMUEL JACKSON, INCORPORATED 2003 ALL RIGHTS RESERVED
ERRORS AND ALARMS
HO-7-1237 & HO-4-1234 OIL-FIRED HEATERS
CODE
ERR/ALM
DESCRIPTION
420
E
AIR FLOW SWITCH ON MORE THAN 24 HOURS
421
A
MOMENTARY LOW AIR FLOW POSSIBLE CHOKE
422
E
LOW AIR FLOW FOR MORE THAN 3 SECONDS
425
E
OIL LOW PRESSURE CHECK SUPPLY AND FILTERS
426
E
OIL HIGH PRESSURE
430
E
OIL LOW PRESSURE SWITCH FAILED
431
E
LOW ATOMIZING AIR PRESSURE
432
E
ATOMIZING AIR PRESSURE SWITCH FAILED
433
E
MODULATING MOTOR FAILS TO CLOSE
434
E
MODULATING MOTOR FAILS TO OPEN
435
E
LOW COMBUSTION AIR PRESSURE
436
E
COMBUSTION AIR PRESSURE SWITCH FAILED
441
E
FAN INTERLOCK HAS BEEN BYPASSED
442
E
AIR FLOW SWITCH HAS BEEN BYPASSED
443
E
NO FAN INTERLOCK. IS FAN ON?
444
E
EXCESSIVE FLAME FAILURES
446
A
FLAME NOT ESTABLISHED
451
A
FLAME FAILED IN OPERATION
453
E
FLAME SIGNAL BEFORE SPARK BEFORE FUEL
455
E
FLAME SIGNAL DURING SPARK BEFORE FUEL
456
E
NO SAFETY SWITCH TEST PERFORMED LAST SIX SHUT
DOWNS
457 *
E
GAS LOW PRESSURE (DUAL-FUEL MODEL)
458 *
E
GAS VALVE LEAK, UPSTREAM (DUAL-FUEL MODEL)
459 *
E
GAS VALVE LEAK, DOWNSTREAM (DUAL-FUEL MODEL)
460 *
E
GAS LOW PRESSURE SWITCH NOT WORKING (DUAL-
FUEL MODEL)