Operating Instructions and Installation
4-10
Samsung Electronics
Wired remote controller (cont.)
- If an error occurs is displayed on the wired remote controller.
- To see an error code, please press the test button.
Error mode
Content
Measures
Product operation
status in case of error
Error type
Outdoor unit compressor/
outdoor unit fan
Non-connection error of indoor
and outdoor Communication wire
(connected to the power terminal)
Check the status of power connection
Check the connection status of the
communication line
Operation-off
Self-diagnosis
error
Outdoor fan 1 error
Check the input power connection status
Check the connection status between the
motor and PCB in outdoor unit
Check the fuse of indoor/outdoor units
Operation-off
Self-diagnosis
error
[inverter] Compressor operation
error
Check the connection status of the compressor
Check the resistance between different
phases in compressor
Operation-off
Outdoor unit
protection control
error
Discharge current error/
PFC over-current error
Check the input power
Check refrigerant is filled
Check outdoor fan operates normally
Operation-off
Outdoor unit
protection control
error
[inverter] IPM over current error
Check refrigerant is filled
Check the connection status of compressor
and if it operates normally
Check for any obstacles around indoor/
outdoor units
Operation-off
Outdoor unit
protection control
error
[inverter] Compressor rotation
error
Check the connection status of the
compressor
Check the resistance between different
phases in compressor
Operation-off
Outdoor unit
protection control
error
[inverter] Current sensor error
Check PCB operates normally
Operation-off
Outdoor unit
protection control
error
[inverter] DC link voltage sensor
error
Check the connection of input power
Check the status of RY21 and R2000 of
Inverter PCB
Operation-off
Outdoor unit
protection control
error
[inverter] OTP error
Check PCB operates normally
Operation-off
Outdoor unit
protection control
error
Outdoor fan 2 error
Check the connection status of input power
Check the connection status of motor and
outdoor PCB
Check the fuse of indoor/outdoor unit
Operation-off
Self-diagnosis
error
Gas leakage error
Check refrigerant is filled
Check the indoor EVA sensor
Operation-off
Self-diagnosis
error
Inconsistent volume
Check the indoor unit’s option code
Operation-off
Outdoor unit
protection control
error
Troubleshooting