Warning to service personnel:
CAUTION: Double pole/neutral fusing
4.
Telephone line cord:
CAUTION: To reduce the risk of fire, use only No. 26 AWG or larger
(e.g., 24 AWG) UL Listed or CSA Certified Telecommunication Line
Cord
5.
Leakage currents due to ringing voltage - Earthing installation
instructions: 1. A supplementary equipment earthing conductor is to be
installed between the product or system and earth, that is, in addition to
the equipment earthing conductor in the power supply cord.
2. The supplementary equipment earthing conductor may not be smaller
in size than the unearthed branch-circuit supply conductors.
The equipment earthing conductor is to be connected to the product at
the terminal provided, and connected to earth in a manner that will retain
the earth connection when the power supply cord is unplugged.
The connection to earth of the supplementary earthing conductor shall be
in compliance with the appropriate rules for terminating bonding
jumpers in Part K of Article 250 of the National Electrical Code,
ANSI/NFPA 70 and Article 10 of Part 1 of the Canadian Electrical Code,
Part 1, C22.1. Termination of the supplementary earthing conductor is
permitted to be made to building steel, to a metal electrical raceway
system, or to any earthed item that is permanently and reliably connected
to the electrical service equipment earthed.
3. Bare, covered, or insulated earthing conductors are acceptable.
A covered or insulated conductor must have a continuous outer finish
that is either green, or green with one or more yellow stripes.
6.
Safety Instructions-Rack Mount ‘Rack Mount Instructions-
The following or similar rack-mount instructions are included with the
installation instructions:
A) Elevated Operating Ambient-If installed in a closed or multi-unit rack
assembly, the operating ambient temperature of the rack environment
may be greater than room ambient. Therefore, consideration should be
given to installing the equipment in an environment compatible with the
maximum ambient temperature (Tma) specified by the manufacturer.