Screw eight nuts to the suspension bolts making space for hanging the
indoor unit.
You must install the suspension bolts more than four when
installing the indoor unit.
5
Check the level of the indoor unit by using a leveler.
X
A tilt of the indoor unit may cause malfunction of a built-in float switch
and water leaks.
6
Adjust the height of the indoor unit by using the gauge of dimensions.
X
You should adjust the gauge of dimensions and the pattern sheet to fit
the cutting dimensions of ceiling.
X
Make sure that the indoor unit is installed at a level if the indoor unit
slants too much, there can be water leaks.
7
Tighten the upper part nuts.
8
Remove the gauge of dimensions after installing the indoor unit.
Level
Nut
Washer
Rubber
Fasten the nut
Side view
Air inlet
Air outlet
15(5/8)
15(5/8)
Gauge of Dimensions
Ceiling
Unit : mm(inch)