Setting an indoor unit address and installation option
Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Explanation
PAGE
MODE
Use of Auto Change Over
for HR only in Auto mode /
Use of Cooling only indoor
unit of HR
(When setting SEG3)
Standard heating temp.
Offset
(When setting SEG3)
Standard cooling temp.
Offset
(When setting SEG3)
Standard for mode change
Heating
→
Cooling
Indication
and Details
Indication Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
0
5
0
Follow
product
option
0
0 °C
0
0 °C
0
1 °C
1
0.5 °C
1
0.5 °C
1
1.5 °C
1
Use Auto
Change Over
for HR only
2
1 °C
2
1 °C
2
2 °C
3
1.5 °C
3
1.5 °C
3
2.5 °C
4
2 °C
4
2 °C
4
3 °C
2
Use Cooling
only indoor
unit for HR
5
2.5 °C
5
2.5 °C
5
3.5 °C
6
3 °C
6
3 °C
6
4 °C
7
3.5 °C
7
3.5 °C
7
4.5 °C
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Explanation
PAGE
(When setting SEG3)
Standard for mode
change Cooling
→
Heating
(When setting SEG3)
Time required for mode
change (*1)
Compensation option
for Long pipe or height
difference between indoor
units
MTFC (*4)
-
Indication
and Details
Indication Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
-
1
0
1 °C
0
5min
0
Default
0
Default
1
1.5 °C
1
7min
1
(*2) Height
difference is
more than
30m or (*3)
Distance is
longer than
110m
2
2 °C
2
9min
3
2.5 °C
3
11min
4
3 °C
4
13min
2
(*2) Height
difference is
15~30m or
(*3) Distance is
50~110m
2
Use
5
3.5 °C
5
15min
6
4 °C
6
20min
7
4.5 °C
7
30min
Q
05 series installation option (Detailed)
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
5
Use of Auto Change Over
for HR only in Auto mode
/ Use of Cooling only
indoor unit of HR
(When setting SEG3)
Standard heating temp.
Offset
(When setting SEG3)
Standard cooling temp.
Offset
(When setting SEG3)
Standard for mode change
Heating
→
Cooling
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
(When setting SEG3)
Standard for mode change
Cooling
→
Heating
(When setting SEG3)
Time required for mode
change
(*1)
Compensation option
for Long pipe or height
difference between indoor
units
MTFC (*4)
-
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
2
-
-
-
-
Control variables when
using hot water / external
heater (*5)
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
3
-
-
-
Forced FAN Operation for
Heating and Cooling
-
Q
05 series installation option