Air conditioner
Installation manual
Slim 1 Way cassette
• Thank you for purchasing this Samsung air conditioner.• Before operating this unit, please read this installation manual carefully and retain it for future
reference.
Page 1: ...ioner Installation manual Slim 1 Way cassette Thank you for purchasing this Samsung air conditioner Before operating this unit please read this installation manual carefully and retain it for future r...
Page 2: ...Purging the Unit 10 Connecting the Refrigerant Pipe 11 Cutting Flaring the Pipes 12 Performing LeakTest Insulation 13 Drain pipe and Drain Hose Installation 15 Bushing Bracket Installation 17 WiringWo...
Page 3: ...oner contains a refrigerant that has to be disposed of as special waste At the end of its life cycle the air conditioner must be disposed of in authorized centers or returned to the retailer so that i...
Page 4: ...onditioner may be out of order The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet The copper pipe or connection pipe may corrode and refrigerant may le...
Page 5: ...pping from the drain hose runs away correctly and safely X The indoor unit must be installed in this way that they are out of public access Not touchable by the users X Rigid wall without vibration X...
Page 6: ...6 Selecting the Installation Location Space Requirements for Indoor Unit 150 5 9 or more 150 5 9 or more 150 5 9 or more 1500 59 or more Unit mm inch...
Page 7: ...he indoor unit Unit mm inch Suspension position Ceiling opening Ceiling Drainhole Ceiling opening Suspension position 1150 45 28 1035 8 40 78 249 9 80 440 17 32 21 0 83 77 3 03 52 2 05 50 1 97 85 3 35...
Page 8: ...mensions between the markings Note 2 Insert bolt anchors use existing ceiling supports or construct a suitable support as shown in figure 3 Install the suspension bolts depending on the ceiling type X...
Page 9: ...leaks 6 Adjust the height of the indoor unit by using the gauge of dimensions X You should adjust the gauge of dimensions and the pattern sheet to fit the cutting dimensions of ceiling X Make sure tha...
Page 10: ...arge of nitrogen gas insert gas Therefore all insert gas must be purged before connecting the assembly piping Unscrew the pinch pipe at the end of each refrigerant pipe Result All inert gas escapes fr...
Page 11: ...5 Must apply refrigerant oil on the flaring area to prevent a leak Note 3 Be sure that there must be no crack or kink on the bended area X Connecttheindoorandoutdoorunitsusingpipeswithflared connectio...
Page 12: ...inch 6 35 1 4 0 0 5 0 0 02 1 0 1 5 0 04 0 06 1 5 2 0 0 06 0 08 9 52 3 8 0 0 5 0 0 02 1 0 1 5 0 04 0 06 1 5 2 0 0 06 0 08 12 7 1 2 0 0 5 0 0 02 1 0 1 5 0 04 0 06 1 5 2 0 0 06 0 08 15 88 5 8 0 0 5 0 0 0...
Page 13: ...n the system you can insulate the piping and hose 1 To avoid condensation problems place T13 0 1 2 or thicker Acrylonitrile Butadien Rubber separately around each refrigerant pipe Note Always make the...
Page 14: ...sand Operation purpose condition Restaurant ceiling sauna swimming pool etc Building construction condition The ceiling frequently exposed to moisture and cooling is not covered e g The pipe installed...
Page 15: ...lled on the drain hose port X Drain hose port location differs depending on the unit types 3 Install the drain pipe as shortly as possible X Give a slightly slant to the drainpipe for proper drainage...
Page 16: ...1 1 5m 3 28 4 92 ft 200 7 87 ormore 20 0 79 ormore Ceiling Hanger Centralized Drainage 1 Install main air vent at the front of the farthest indoor unit from the main drain when installed indoor units...
Page 17: ...k drain water drops at the end of the drainpipe Drainpipe Drain water drops 5 Make sure there is no water leak at the drainage 6 When you finished the test close the coverside Whenmaintainingtheaircon...
Page 18: ...talling the wired remote Control Power and communication cable connection Norminaldimensionsforcable mm2 inch2 1 5 0 002 2 5 0 003 4 0 006 Norminaldimensionsforscrew mm inch 4 0 15 4 0 15 4 0 15 4 0 1...
Page 19: ...Distance among each indoor unit m Ak Power cable specification mm2 inch2 ik Running current of each unit A Coef 35 6 Lk ik 10 of input voltage V 1000 Ak n k 1 Example of Installation Total power cabl...
Page 20: ...connection from the power supply must be incorporated in the fixed wiring 3mm 1 8 X You must keep the cable in a protection tube X Keep distances of 50mm 2 or more between power cable and communicatio...
Page 21: ...ethod 2 Twist the wire cores together and push it into the sleeve Connection sleeve Connection sleeve X Ifcablewiresareconnectedwithoutusingconnectingsleeves theircontactarea becomesreduced orcorrosio...
Page 22: ...h the insulation tape to finish Three or more layers of insulation are required X Method 1 X Method 2 Insulation tape Insulation tape X Make sure that the connection parts are not exposed to outside X...
Page 23: ...dure of option setting After entering the option setting status select the option as listed below Option setting is available from SEG1 to SEG 24 X SEG1 SEG7 SEG13 SEG19 are not set as page option X S...
Page 24: ...to enter SEG8 value Each time you press the button will be selected in rotation SEG6 SEG8 6 Setting Fan mode Press Mode button to be changed to FAN mode in the ON status 7 Setting SEG9 SEG10 option Pr...
Page 25: ...enter SEG21 value Press High Fan button to enter SEG22 value Each time you press the button will be selected in rotation SEG21 SEG22 18 Setting Heat mode Press Mode button to be change to HEAT mode in...
Page 26: ...it Theunitdigitofan indoorunit Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 0 A 0 No Main address 0 9 100 dig...
Page 27: ...However if the central control is not connected but it doesn t indicate an error message you need to set the central control option as 0 Disuse to exclude the indoor unit from the central control X Th...
Page 28: ...ing CoolingUltraLow Fan 2 Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE Useofdrainpump Useofhotwaterheater EEVStepwhen heatingstops Indication andDetails Indication Details Indication Detai...
Page 29: ...installtheModeSelectswitch MCM C200 ontheoutdoorunitandfixitasCOOLmode Ifthe CoolingPriority optionissetintheHeatPumpoutdoorunit theindoorunitcanoperateintheHeatmodeowingtothewaterheater eveniftheout...
Page 30: ...rLongpipeorheight differencebetweenindoor units MTFC 4 Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details 1 0 1 C 0 5min 0 Default 0 D...
Page 31: ...Nodelay D 6 0 C 10minutes E 6 0 C 20minutes Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 Explanation PAGE ForcingFANOperation forHeatingandCooling Indication andDetails Indication Details Indication Det...
Page 32: ...ture setintheAutoChangeOverscreenafterenteringtheUsermode bypressingthe buttononthewiredremotecontrol theairconditionerchangesintotheautomaticheatingmode 2 Heightdifference Thedifferenceoftheheightbet...
Page 33: ...e each digit of set option Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Explanation PAGE MODE Theoptionmode youwanttochange Thetens digitofan optionSEGyouwill change Theunitdigitofan optionSEGyouwill change C...
Page 34: ...X Setting the main indoor unit in the S net pro2 a b c d a Select an emergency temperature output ETO mode b Select the main indoor unit c Set the duration used as a reference for generating emergency...
Page 35: ...r unit c Set the operation mode fan speed and set temperature X Operation when the external contact settings and the ETO settings overlap Mainindoorunit EnableofETO Enableofexternalcontact Errorportou...
Page 36: ...ect operation follow the steps below After finishing the installation of the air conditioner you should explain the fol lowing to the user Refer to appropriate pages in the User s Manual 1 How to star...
Page 37: ...for 2 minutes 2 Communication error received from the outdoor unit 3 3 miniute tracking error on outdoor unit 4 Communication error after tracking due to unmatching number of installed units 5 Error...
Page 38: ...re on discharged air on outdoor unit 2nd detection 6 Indoor operation stop due to unconfirmed error on outdoor unit 7 Error due to reverse phase detection 8 Comp stop due to freeze detection 6th detec...
Page 39: ...39 ENGLISH MEMO...
Page 40: ...DB68 03806A 05...