35
13. Installation
AF50MS3AF50MS3MCEEXHC, AF50MV3AF50MV3MCEEXHC
Refrigerant piping work
1. Cut the pipe with a pipe cutter ensuring that the cut edge remains flat and then remove all the burrs.
2. Make sure that the flared pipe doesn’t have uneven thickness, damaged and cracked surfaces, or any other defects.
3. You must use torque wrench when connecting pipes or flare nut.
❶
❷
Pipe
Reamer
Flare bar
❸
Outer Diameter [D, mm]
Fastening torque [N·m]
Depth [A, (mm)]
6.35
14~18
1.3
9.52
34~42
1.8
12.70
49~61
2.0
15.88
68~82
2.2
19.05
100~120
2.2
• When installing, make sure there is no leakage. When collecting the refrigerant, stop the compressor
first before removing the connection pipe.
If the refrigerant pipe is not properly connected and the compressor works with the service valve open, the
pipe inhales the air and it makes the pressure inside of the refrigerant cycle abnormally high which may
lead to explosion and injury.
WARNING