SINGLE
Technical
Data Book
SINGLE PAC for IRAN
(R410A, 50Hz, HP/CO)
Model : AF50MS3MCEENHC, AF50MV3MCEENHC (Indoor Unit)
AF50MS3MCEEXHC, AF50MV3MCEEXHC (Outdoor Unit)
Page 1: ...SINGLE Technical Data Book SINGLE PAC forIRAN R410A 50Hz HP CO Model AF50MS3MCEENHC AF50MV3MCEENHC Indoor Unit AF50MS3MCEEXHC AF50MV3MCEEXHC Outdoor Unit...
Page 2: ...2 History Version Modification Date Remark Ver 1 0 Release Single PAC TDB for Iran 17 02 07 Ver 1 1 Revised Compressor Oil type of outdoor unit 18 10 30...
Page 3: ...4 J 2015 K 2016 M 2017 4 Product Type S InverterHP V InverterCO 5 Feature 1 1 220V 2 3 220V 3 3 380V 4 3 380V Virus doctor 6 Series MC Mirage 7 Color EE Santorini beige 8 Mode N Indoorunit X Outdoorun...
Page 4: ...1 Classification AR RAC AF FAC PAC AW WAC 2 Capacity X1000 Btu h 3 Version H 2014 J 2015 K 2016 M 2017 4 Product Type S InverterHP V InverterCO 5 Feature 1 1 220V 2 3 220V 3 3 380V 4 3 380V Virus doc...
Page 5: ...Touch Display Panel You need not find Remote controller anymore It lets you control the temperature and air flow more easily Full HD Filter MAX60 The full high density filter collects up t0 60 of dus...
Page 6: ...4 Capacity Table 11 5 Capacity Correction 13 6 Dimensional Drawing 15 7 Center of Gravity 17 8 Electrical Wiring Diagram 19 9 Sound Data 21 10 Temperature and airflow distribution 23 11 Operation Rang...
Page 7: ...7 1 Line up 1 Line up 1 1 Indoorunit Model Capacity kW 13 4 HP 13 4 CO PAC 1 2 OutdoorUnit Model Type Capacity kW 13 4 HP 13 4 CO 3...
Page 8: ...n Both liquid and gas pipes Both liquid and gas pipes Pipinglength ODU IDU Standard m 5 5 Max m 75 75 Elevation m 30 30 Chargeless m 5 5 Wiring connections Communication Min mm Min 0 75 Min 0 75 Remar...
Page 9: ...nch 37 x 47 5 8 x13 37 x 47 5 8 x13 ShippingDimensions WxHxD mm 995 x1388 x 426 995 x1388 x 426 inch 39 3 16 x 54 5 8 x16 3 4 39 3 16 x 54 5 8 x16 3 4 Casing Material Body EGI steel plate EGI steel pl...
Page 10: ...Pressure Level dBA Cooling Heating 13 4 AF50MS3MCEEXHC 940 x1210 x 330 85 110 53 54 13 4 AF50MV3MCEEXHC 940 x1210 x 330 84 5 110 53 NOTE Sound data is based on cooling operation Electrical Characteris...
Page 11: ...10 0 3 89 11 6 9 9 3 93 12 2 9 8 3 97 12 8 9 6 4 05 48 8 9 8 3 3 46 9 4 8 5 3 53 9 7 8 8 3 60 10 1 9 1 3 67 10 3 9 0 3 71 10 8 8 9 3 75 11 3 8 7 3 82 52 7 7 7 6 3 25 8 1 7 8 3 32 8 4 8 0 3 39 8 7 8 3...
Page 12: ...10 9 3 35 16 6 10 6 3 42 21 12 4 9 6 3 25 13 1 9 9 3 32 13 6 10 2 3 39 14 1 10 6 3 46 14 4 10 4 3 49 15 1 10 3 3 53 15 8 10 1 3 60 35 11 9 9 2 4 07 12 5 9 5 4 15 13 0 9 7 4 23 13 4 10 1 4 32 13 7 9 9...
Page 13: ...7 0 97 0 96 0 95 0 94 0 93 0 92 0 91 0 91 0 90 0 89 0 88 5 0 99 0 98 0 97 0 97 0 96 0 95 0 94 0 93 0 92 0 91 0 91 0 90 0 89 0 88 0 1 00 0 99 0 98 0 97 0 97 0 96 0 95 0 94 0 93 0 92 0 91 0 91 0 90 0 89...
Page 14: ...91 0 90 0 89 0 88 0 86 0 84 25 0 94 0 93 0 93 0 92 0 91 0 90 0 89 0 87 0 86 0 83 30 0 93 0 92 0 91 0 90 0 89 0 88 0 87 0 85 0 82 Heating Pipe Length m 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 Level...
Page 15: ...it AF50MS3MCEENHC AF50MV3MCEENHC Unit mm inches 400 1 3 3 4 1850 6 0 3 4 610 2 No Name Description 1 Liquid pipe connection 9 52 3 8 2 Gas pipe connection 15 88 5 8 3 Drain pipe connection 4 Power sup...
Page 16: ...ing 16 Outdoorunit AF50MS3MCEEXHC AF50MV3MCEEXHC Unit mm inches No Name Description 1 Liquid pipe connection 9 52 3 8 2 Gas pipe connection 15 88 5 8 3 Drain pipe connection 4 Power supply Communicati...
Page 17: ...17 7 Centerof Gravity Indoorunit AF50MS3MCEENHC AF50MV3MCEENHC Units mm inches 1851 940 400 200 306 613 910 1850...
Page 18: ...erof Gravity 18 Outdoorunit AF50MS3MCEEXHC AF50MV3MCEEXHC Units mm inches 1210 47 5 8 530 20 7 8 328 12 7 8 620 24 3 8 Hold location of foundation bolt Hold location of foundation bolt 160 6 5 16 210...
Page 19: ...rint circuit board DISPLAY L R STEPMOTOR Left Right louverDC Motor NOTE This wiring diagram applies only to the indoor unit Colors blk black red red blu blue wht white yel yellow brn brown sky skyblue...
Page 20: ...rd EMI OLP TEMP ThermistorOLP COND TEMP ThermistorCONDENSOR NOTE This wiring diagram applies only to the outdoor unit Colors blk black red red blu blue wht white yel yellow brn brown sky skyblue When...
Page 21: ...ter Frequency Hz High Low NC 50 NC 70 NC 60 NC 55 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 63 125 250 500 1000 20...
Page 22: ...r Frequency Hz Cooling NC 50 Heating NC 70 NC 60 NC 55 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80...
Page 23: ...23 10 Temperature and airflow distribution AF50MS3MCEENHC 1 Cooling airvelocity distribution 2 Cooling temperature distribution 3 Heating AirVelocity distribution 4 Heating temperature distribution...
Page 24: ...10 Temperature and airflow distribution 24 AF50MV3MCEENHC 1 Cooling airvelocity distribution 2 Cooling temperature distribution...
Page 25: ...25 11 Operation Range Mode IndoorTemperature OutdoorTemperature IndoorHumidity COOLING 18 C 32 C 15 C 52 C Relative humidity 80 orless HEATING 30 C orless 20 C 24 C DRYING 18 C 32 C 15 C 52 C...
Page 26: ...alve Main E_M Thermistor Discharge pipe T_D Thermistor Compressor Top T_CT Heat Exchanger Main Outdoor unit HX_M Thermistor Ambient T_A Thermistor CondOut T_CO Thermistor IDU Heat Exchanger IN T_II Ou...
Page 27: ...mistor Compressor Top T_CT Heat Exchanger Main Outdoor unit HX_M SolenoidValve 4Way V_4W Thermistor CondOut T_CO Thermistor IDU Heat Exchanger IN T_II OutdoorFanMotor2 OFM2 OutdoorFanMotor1 OFM1 Heat...
Page 28: ...ubject to sulfide gas hot spring zone When installing the unit at such special environmental conditions it may cause machine trouble When it is unavoidable to use such places It requires special maint...
Page 29: ...towards the wall 300 or more 300 ormore 600 ormore 1500 or more 2000 ormore When 3 sides of the outdoor unit are blocked by the wall The upper part of the outdoor unit and the air outlet is towards th...
Page 30: ...600 ormore When 3 sides of the outdoorunit are blocked by the wall 300 or more 1500 or more 600 ormore 600 ormore 500 or more 500 or more 300 ormore 300 ormore When front and rearside of the outdoorun...
Page 31: ...s than 20 Opening ratio criteria greater than 80 WARNING Outdoorunit base mount and anchorbolt position Fix the outdoorunit with anchorbolts The anchor bolt must be 20mm or higher from the base surfac...
Page 32: ...Protection wall should be constructed with a solid material such as concrete to block the sea breeze and the height and the width of the wall should be 1 5 times larger than the size of the outdoor u...
Page 33: ...ammable Install the railing around the outdoor unit to prevent falling when the unit is installed at high place of roof on the building Avoid installing the units in places such as an exhaust pipe and...
Page 34: ...pipe with no gap orcracks and use adhesive between the connection part of the insulatorto prevent moisture from entering f f Make sure that the thickness of the insulatordoesn t get thinneron the bend...
Page 35: ...pipes orflare nut Pipe Reamer Flare bar OuterDiameter D mm Fastening torque N m Depth A mm 6 35 14 18 1 3 9 52 34 42 1 8 12 70 49 61 2 0 15 88 68 82 2 2 19 05 100 120 2 2 When installing make sure th...
Page 36: ...d range and make sure that they don t get loosened f f Please connect ground wire Please install the powerwire with it length shorterthan 50 m If the length of the powerwire exceeds 50 m inevitably pr...
Page 37: ...nstalled in a place with high temperature If the ambient temperature is high allowable current of the wire will decrease and current reduction factorwill occur Please install the auxiliary power switc...
Page 38: ...cable Thick cable Cable tie Connecting thewires f f Product uses 3 phase 4 wires 380 415V powersupply f f When connecting indoorand outdoorunit connection cable make sure to match the numbers orlette...
Page 39: ...re Ground wire Communication cable Indoor Outdoor unit connection cable Outdoorunit Electrical panel Indoorunit Powersupply cable Communication cable f f Powerwiring diagram Powersupply cable 3 phase...
Page 40: ...peeling off cable wires from the pre installed tube insert a contraction tube CAUTION Unit mm 120 60 20 20 20 180 Powercable 20 Pre installed tube forthe powercable 3 Insert both sides of core wire of...
Page 41: ...Contraction tube 7 Aftertube contraction work is completed wrap it with the insulation tape to finish Insulation tape Make sure that the connection parts are not exposed to outside Be sure to use insu...
Page 42: ...able The earthing wire for the telephone line cannot be used to ground the air conditioner NOTE Carbon plastic 50 cm 30 cm To grounding screw Steel core Terminal M4 PVC insulated green yellowwire 3 Fi...
Page 43: ...pressure using a pressure regulator 3 Check forleakage at connection part and brazed part by using soap water 4 When there s no leakage open the manifold gage to discharge nitrogen and connect the va...
Page 44: ...aining refrigerant by pressing the cooling trial operation button 4 After charging the refrigerant completely open the spindle of the service valve in counter clockwise direction on gas side pipe and...
Page 45: ...0 15 13 10 24 3630 3400 3100 7 2840 2670 2400 5 2650 2470 2200 20 2060 1890 1620 Pressure foreach temperature was measured at gas side service valve Fixing and insulating the connection part of the pi...
Page 46: ...insulator Drain hose Insulation 2 Connect the drain hose by pushing the extension drain hose to the insulated drain pipe 3 Tightly insulated the connection part of the extension drain hose to the insu...
Page 47: ...Therefore be sure to remove the foreign substance inside after installation Do not use the drain hose that is connected by number of hoses together Water may leak from the connection part therefore i...
Page 48: ...Press K1 button twice Start Defrost test mode Press K1 button Stop Defrost test mode 7 seg display Condition of Defrost test mode Condition 1 The outdoor temperature is under10 C Condition 2 All the t...
Page 49: ...ds digit Tens digit Unit digit C 11 EEV B Hundreds digit Tens digit Unit digit step 12 The capacity sum of indoorunits C Tens digit Unit digit The first place of decimals kW 13 Protective control D 0...
Page 50: ...ention control Switch 3 Silence Mode option Switch 4 When snow prevention mode is in use eco mode standby mode will not be functional f f DIP switch SW508 option On default Off Switch1 Auto Silence Mo...
Page 51: ...ror Check Cond sensorOpen Short E231 6 MAIN Discharge temp sensorerror Check Discharge sensorOpen Short E251 7 MAIN OLP SensorError Check OLP sensorOpen Short E320 8 MAIN Detection of OutdoorFreezing...
Page 52: ...s match between indoorand outdoor Check indoorand outdoorunit model E556 27 MAIN Errordue to not using Smart Install Check Indooroption code E508 28 MAIN OutdoorEEPROM error checksum Check OutdoorEEPR...
Page 53: ...Module MIM D00AN DMS 2 0 MIM B17N BACnet Gateway MIM B18N LonWorks Gateway CENTRALIZED CONTROLLER MCM A202DN CENTRALIZED ON OFF Contoller MST P3P S NET 3 PROGRAM MCM A300N Centralized Touch Screen Co...
Page 54: ...PM SE Head Office Suwon Korea 129 Samsung Ro Yeongtong Gu Suwon City Gyeonggi Do Korea 16677 Website www samsung com http btsp samsunggsbn com Email airconditioner samsung com Images and data in this...