23
Samsung Electronics
Troubleshooting
1. Check the assembly condition of the sensor connector(CN43) on the indoor unit Main PCB and if not assembled, reassemble the
connector accurately.
2. Detach the room pipe sensor connector(CN43) and check the resistance between connector 3 and 4.
If the above data is not met, replace the room pipe sensor.
3. Assemble the room pipe sensor to PCB, plug in, and check the voltage of connector 3 and 4. If the resistance is below 0.5V or
over 4.9V, replace the indoor Main PCB. (short or disconnected in the PCB board)
Temperature(˚C)
15
20
25
Temperature(˚C)
30
35
40
Resistance Value(Kohm)
8.31
6.94
5.83
Resistance Value(Kohm)
14.68
12.09
10
Others
The data tolerance
is ±3%.
6-2-3 Room Pipe sensor failure
Indoor unit heat exchanger temperature sensor error
(open or short)
Description
LAMP
OPERATION
TIMER
TURBO
7-segment
Display
: Lamp flickering
: Lamp off
DB98_16693A(2)_1 3/19/04 2:11 PM Page 23
Summary of Contents for SH07ZS2
Page 36: ...MEMO 35 Samsung Electronics...
Page 42: ...41 Samsung Electronics 9 PCB Diagram 9 1 ASS Y MAIN PCB 7K 9K 12K DB93 02447A TOP...
Page 43: ...Samsung Electronics 42 PCB Diagram BOTTOM...
Page 51: ...MEMO Samsung Electronics 50...
Page 52: ...MEMO 51 Samsung Electronics...
Page 53: ...MEMO Samsung Electronics 52...