
10
fantech
1. Continuous / Ventilation Mode
In this mode of operation both fans are operating and exchanging inside air for outside air. The energy recovery ventilator (ERV) will operate at the selected
rate, either at low or medium speed, and switches to high speed when activated by an optional remote control. The "LOW (reduced)" and "HIGH (Normal)"
fan speed selection will cause the unit to operate in continuous ventilation mode at a reduced exchange rate. Continuous mode is recommended, since
pollutants are slowly but constantly being generated in a building.
2. Intermittent / Standby Mode
The system is always on standby and operates at high speed when activated by an optional remote control (required): "Standby" should be selected if
the user wishes to stop the unit from continuous exchange.
3. Defrost by evacuation
A preset defrost sequence is activated at an outdoor air temperature of 23
°
F (-5
°
C) and lower.
During the defrost sequence, the supply blower shuts down & the exhaust blower continues to ventilate for a preset time. The unit then returns to
the normal operation, and continues the cycle.
Modes of operation
Summary of Contents for SER 450
Page 14: ...14 fantech Wiring Diagram SER 450 ...
Page 15: ...15 fantech Wiring Diagram SER 700 ...
Page 16: ...16 fantech Wiring Diagram SER 1100 and SER 1300 ...
Page 34: ...34 fantech Connexions électriques SER 450 ...
Page 35: ...35 fantech Connexions électriques SER 700 ...
Page 36: ...36 fantech Connexions électriques SER 1100 et SER 1300 ...
Page 45: ...45 fantech Notes ...
Page 46: ...46 fantech Notes ...
Page 47: ...47 fantech Notes ...