37
Indoor Unit Control (Continued)
3
Tap [Operate mode limits
].
If you select Exclusive Cooling(Fan/Cool), will be
displayed in current status of indoor unit control
display.
If you select Exclusive Heating(Fan/Heat), will be
displayed in current status of indoor unit control
display.
If you select No limits, or will be gone in the
current status of indoor unit control display.
Exclusive
Cooling
(Fan)
Forces indoor units to operate Exclusive Cooling only.
In Exclusive Cooling(Fan) mode, if the user select Auto Heat or
Heat mode with wired/wireless remote control, the operation
mode of indoor unit will be changed to Fan mode.
Exclusive
Cooling
(Cool)
Forces indoor units to operate Exclusive Cooling only.
In Exclusive Cooling(Cool) mode, if the user select Auto Heat or
Heat mode with wired/wireless remote control, the operation
mode of indoor unit will be changed to Cool mode.
Exclusive
Heating
(Fan)
Forces indoor units to operate Exclusive Heating only.
In Exclusive Heating(Fan) mode, if the user select Auto Cool,
Cool or Dry mode with wired/wireless remote control, the
operation mode of indoor unit will be changed to Fan mode.
Exclusive
Heating
(Heating)
Forces indoor units to operate Exclusive Heating only.
In Exclusive Heating(Heating) mode, if the user select Auto Cool,
Cool or Dry mode with wired/wireless remote control, the
operation mode of indoor unit will be changed to Heat mode.
No limits
No limit on indoor unit operation.
ERV does not support Operate mode limits setup.
Since ERV+ does not support Fan mode,
it will operate in Exclusive Cooling (Cool)/Exclusive
Heating (Heating) when Exclusive Cooling (Fan)/
Exclusive Heating (Fan) is selected.