49
ENGLISH
How to put the refrigerant into the refrigerant container before pump down operation
❋
When the amount of refrigerant charged in the system exceeds maximum receptive capacity, collect the refrigerant into
the refrigerant container at first and then perform the pump down.
f
Prepare the exclusive refrigerant container that can be recharged, scale, and manifold gage that can be recharged.
f
Check the current amount of refrigerant within the system.
f
After connecting the refrigerant container to an outdoor unit, operate 50% of all indoor units as cooling mode.
f
Check the pressure of high pressure side for manifold gage after 10 minutes from cooling operation. When the pressure
of high pressure side is above 30kg/cm²,g decrease the number of operating indoor unit and make the pressure below
30kg/cm²,g.
f
After checking that the pressure of high pressure side went below 30kg/cm²,g, open the manifold gage side valve(2) that
is connected to the liquid pipe and refrigerant container valve. Then run the refrigerant from liquid pipe to refrigerant
container.
f
Check whether the proper amount of refrigerant are put into the container using a scale, turn off the valve and remove
the manifold gage.
f
The amount of refrigerant that can be put into the refrigerant container should be about 50% of all refrigerant of the
whole system.
f
Do not collect too much refrigerant in one refrigerant container.
Gas side
Scale
Liquid side
Manifold gage
Service valve
Outdoor unit
R-410A
Refrigerant
container valve
Valve(2)
Valve(1)