46
Charging refrigerant
f
The R-410A refrigerant is blended refrigerant. Add only liquid refrigerant.
f
Measure the quantity of the refrigerant according to the length of the liquid side pipe. Add quantity of the refrigerant
using a scale.
Important information regulation regarding the refrigerant used
This product contains fluorinated greenhouse gases. Do not vent gases into the atmosphere.
t
Inform user if system contains 5 tCOe or more of fluorinated greenhouse gases. In this case, it has to be checked
for leakage at least once every 12 months, according to regulation n°517/2014. This activity has to be covered
by qualified personnel only. In case situation above (5 tCOe or more of R-410A), installer (or recognized person
which has responsibility for final check) has to provide a maintenance book, with all the information recorded
according to REGULATION (EU) No 517/2014 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 April
2014 on fluorinated greenhouse gases.
CAUTION
Please fill in the following with indelible ink on the refrigerant charge label supplied with this product and on this
manual.
f
①
: The factory refrigerant charge of the product.
f
②
: The additional refrigerant amount charged in the field.
f
①
+
②
: The total refrigerant charge.
Refrigerant type
GWP value
R-410A
2088
t
GWP=Global Warming Potential
t
Calculating tCO2e : kg x GWP / 1000
d
Indoor unit
Outdoor unit
②
①
a Factory refrigerant charge of the product: see unit name plate.
b Additional refrigerant amount charged in the field. (Refer to the above information for the quantity of
refrigerant replenishment.)
c Total refrigerant charge.
d Refrigerant cylinder and manifold for charging.
NOTE
t
The filled-out label must be adhered in the proximity of the product charging port.
(ex. onto the inside of the stop valve cover.)
CAUTION
Unit
kg
tCO2e
①
, a
②
, b
①
+
②
, c