32_
Operating advanced function
Operating advanced function
FIELD SETTING MODE
Field Setting Value(FSV) Table
• Code 40
✴✴
: User’s options for heating devices including internal backup heater and external boiler
401
✴
: Space/DHW heating priority and control variables
402
✴
: Backup/Booster heater priority and control variables
403
✴
: Additional backup boiler operating variables
• Code 50
✴✴
: User’s options for extra functions
501
✴
: New target temperatures of each mode by “Outgoing” hot key of remote controller
5021 : Temperature difference between before & after values in “Economic” DHW mode
503
✴
: Time-division multi(TDM) variables for combining operation b/w A2A and A2W
Field Setting Value
Main Menu &
Code
Sub Menu Function
Description
Sub
Code
Default
Min
Max
Step Unit
Heating
Code 40
✴✴
Heat Pump
Heating/DHW Priority
✴✴
11 0(DHW)
0
1(Heating)
-
-
Outdoor Temp for Priority
✴✴
12
0
-15
20
1
˚C
Heating Off
✴✴
13
25
14
35
1
˚C
Overshoot
✴✴
14
2
1
4
1
˚C
Backup Heater
Application
✴✴
21
1(On)
0(Off)
1
-
-
BUH/BSH Priority
✴✴
22
0(Both)
0
2(BSH)
1
-
For back-up use only
✴✴
23
1(On)
0(Off)
1
-
-
Threshold Temp
✴✴
24
0
-15
35
1
˚C
Backup Boiler
Application
✴✴
31
0(No)
0
1(Yes)
-
-
Boiler Priority
✴✴
32
0(Off)
0
1(On)
-
-
Threshold Temp
✴✴
33
-15
-20
5
1
˚C
Others
Code 50
✴✴
Outing
Water Out Temp for
Cooling
✴✴
11
25
5
25
1
˚C
Room Temp for Cooling
✴✴
12
30
18
30
1
˚C
Water Out Temp for
Heating
✴✴
13
25
15
55
1
˚C
Room Temp for Heating
✴✴
14
16
16
30
1
˚C
Auto Cooling WL1 Temp
✴✴
15
25
5
25
1
˚C
Auto Cooling WL2 Temp
✴✴
16
25
5
25
1
˚C
Auto Heating WL1 Temp
✴✴
17
15
15
55
1
˚C
Auto Heating WL2 Temp
✴✴
18
15
15
55
1
˚C
Target Tank Temp
✴✴
19
30
30
70
1
˚C
DHW Saving Mode
Temp Difference
✴✴
21
5
0
40
1
˚C
TDM Variable
A2A Max Operation Time
✴✴
31
30
5
60
5
min
A2W Min Operation Time
✴✴
32
3
0
10
1
min