18
English
Installation
Installation
Sensor Installation
1) EVA IN sensor should be attached after the distributor, on the coldest part of the heat exchanger pipe.
2) EVA Out sensor should be attached on the middle of inlet and outlet ports.
3) EVA IN/OUT sensor should be insulated for optimized system performance.
4) Room temperature sensor should be basically installed where room air enters(A), It could be also installed at the supplay air
side(B), especially with outdoor fresh air conditioning application.
In that case, installation option 05 series SEG15 and SEG16 function setting should be considered. (Refer to page 28)
• Please check sensor usage in label.
Example of room temperature sensor installation
Select EVA IN/OUT sensor location
2 (EVA OUT sensor)
1 (EVA IN sensor)
Header
Distributor
Cooling Mode
Heating Mode
०
Refrigerant flow
Return
Air
Exhaust
Air
Outdoor Air
Supply Air
A or B : Room temperature sensor location
A
B
• Braze the sensor holder at location suggested above and fix the sensor with sensor clip.
• EVA IN/OUT sensor should be installed where temperature of heat exchanger can be measured accurately.
CAUTION
NOTE