Confidential
Chapter 3 Connecting Cables
MTP02P Series Installation Manual v1.0
77
Copyright © 2018, All Rights Reserved.
Connecting Power Cable
To connect Power cable
1
Make sure you have the following items:
Table 26. Parts and Tools for connecting Power Cable
Category
Description
Installation Section
Rectifier~MMU Power Input Port
Cable
Distance
Cable
The color of the core wire can be
changed according to the specification
of the cable used.
~20 m (75 ft)
8 AWG × 2C
~35 m (115 ft)
6 AWG × 2C
Minimum Cable bend
Radius
Dynamic bend radius: 8 × OD
Static bend radius: 12 × OD
Connector
Rectifier
Check specifications of rectifier output terminal per site and
prepare fasteners.
MMU
JONHON, Push Pull Type, CT48J-2102TSCBM-08A
Working Tools
Cable Cutter
Wire Stripper
Compressor
Heating Gun
Nipper
Table 27. Power Cable/Connector Pin Map
Power Connector Pin No. Description
Color
Pin 1
-48 V DC
The color of the core wire can be
changed according to the specification
of the cable used.
Pin 2
RTN
2
Install a DC power cable from the rectifier to the MMU.
[Cable side Connector]
Bump
Bump
Groove
Pin 1
Pin 2
Pin 1
Pin 2