E-
6
The transmitter channel for controlling the indoor unit is set according to the
RMC(1) switch of the indoor unit.
Setting
Meaning
Remarks
0
Select transmitter 'channel 0' Control the indoor unit by
using the centralized control
connected to the selected
channel
1
Select transmitter 'channel 1'
2
Select transmitter 'channel 2'
No
Yes
Install the Transmitter MAIN PCB
and the SUB PCB separately.
Is the number
of indoor units over 16?
Install the Transmitter MAIN PCB
only.
Set the Transmitter
address differently.
(DS01, DS02, DS03).
Transmitter Installation (Continued)
Transmitter Classifying Flow Chart
Select and install the transmitter according to the number of
installed indoor units.
If the number of indoor units connected to the outdoor unit is
below 16 : Install the Transmitter MAIN PCB only.
If the number of indoor units connected to one outdoor unit is
over 16 : Install the Transmitter MAIN PCB and the SUB PCB
separately.
Note
When setting the indoor unit address
If the RMC(1) switch is set to '0', the Centralized Controller
should to be connected to 'channel 0'.
If the RMC(1) switch is set to '1', the Centralized Controller
should to be connected to 'channel 1'.
If the RMC(1) switch is set to '2', the Centralized Controller
should to be connected to 'channel 2'.
If the MAIN address is set incorrectly, the communication
error occurs.