Centralized 

control

Outdoor unit 

Controls 16 indoor units 
with the RMC(1) switch  
set to '1'.

Channel 2

Channel 1

Channel 0

Centralized 

control

Controls 16 indoor units 
with the RMC(1) switch  
set to '0'.

DIP 1

OFF : 12V, 5V Supply

  Transmitter ADDRESS switch  

setting should be set respectively.

Transmitter

Transmitter Installation (Continued)

To install 32 indoor units for 1 outdoor unit 

(Individual control of indoor units)

Power cable(DC 12V)
Power cable(DC 5V)
Communication Cable

Note

 

When setting the indoor unit address 

 

 

 

If the RMC(1) switch is set to '0', the Centralized Controller 

should to be connected to 'channel 0'. 

 

 

 

If the RMC(1) switch is set to '1', the Centralized Controller 

should to be connected to 'channel 1'. 

 

 

 

If the RMC(1) switch is set to '2', the Centralized Controller 

should to be connected to 'channel 2'. 

 

  

If the MAIN address is set incorrectly, the communication 

error occurs.

MIM-B13A_IM_E_29494-1.indd   10

2008-03-19   ソタネト 12:22:21

Summary of Contents for MIM-B13A

Page 1: ...Transmitter MIM B13A MIM B13AC MIM B13B Air Conditioner installation manual DB98 29543A 4 C E K imagine the possibilities ThankyouforpurchasingthisSamsungproduct ...

Page 2: ...use the centralized control consult authorized installation center WARNING CAUTION Do not use inflammable gases near the centralized control Do not install the centralized control in a location where it will come into contact with the combustible gases machine oil sulphide gas etc Avoid a location where acid alkali solution or special spray is used Do not spill water into the transmitter Do not gi...

Page 3: ...mitter to the left side of the electrical component box in the outdoor unit then connect the power and communication cable between the transmitter and the outdoor unit refer to the figure in page 4 2 If you install a transmitter to an outdoor unit every indoor unit which is connected to an outdoor unit can be controlled simultaneously 3 If the number of installed indoor units connected to the outd...

Page 4: ...the wires are installed inside the wall Caution Transmitter ADDRESS Seting Switch Communication Cable between transmitter Terminal board Transmitter ADDRESS Setting Switch Channel 0 Channel 1 Channel 2 DC 12V supply DC 5V supply Control panel Outdoor unit Transmitter MAIN PCB Transmitter SUB PCB 12V BLU 5V BLK Outdoor unit PCB ...

Page 5: ...units Refer to the table below RMC 2 Address 0 1 2 3 4 5 6 7 8 9 A B C D E F Button No 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Note Individual control means a centralized controller controls only 1 indoor unit In this case you should assign the RMC address to the indoor unit Group control means a centralized controller controls more than 2 indoor units In this case you should assign the RMC address ...

Page 6: ...ransmitter Classifying Flow Chart Select and install the transmitter according to the number of installed indoor units If the number of indoor units connected to the outdoor unit is below 16 Install the Transmitter MAIN PCB only If the number of indoor units connected to one outdoor unit is over 16 Install the Transmitter MAIN PCB and the SUB PCB separately Note When setting the indoor unit addres...

Page 7: ...ransmitter should be 1000 meters or less Transmitter Centralized control Outdoor unit 1 Indoor unit Transmitter Transmitter Outdoor unit 2 Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit MAIN 0 RMC 1 0 RMC 2 0 MAIN 1 RMC 1 0 RMC 2 1 MAIN 2 RMC 1 0 RMC 2 2 MAIN 3 RMC 1 0 RMC 2 3 MAIN 4 RMC 1 0 RMC 2 4 MAIN 5 RMC 1 0 RMC 2 5 Channel 0 Channel 0 Channel 0 ...

Page 8: ... Cable Transmitter Transmitter Installation Continued If the number of installed indoor units connected to one outdoor unit is over 16 To install 48 Indoor units for 1 Outdoor unit Individual control of indoor units Note When setting the indoor unit address If the RMC 1 switch is set to 0 the Centralized Controller should to be connected to channel 0 If the RMC 1 switch is set to 1 the Centralized...

Page 9: ... 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 RMC 1 1 RMC 2 0 1 2 3 4 5 6 7 8 9 A B C D E F Indoor unit ADDRESS MAIN TEN 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 MAIN ONE 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 RMC 1 2 RMC 2 0 1 2 3 4 5 6 7 8 9 A B C D E F Indoor unit 1 Indoor unit 2 Indoor unit 13 Indoor unit 14 Indoor unit 15 Indoor unit 31 Indoor unit 30 Indoor unit 29 Indoor unit 18 Indoor unit 17 Indoor unit 16 Indoor unit ...

Page 10: ...To install 32 indoor units for 1 outdoor unit Individual control of indoor units Power cable DC 12V Power cable DC 5V Communication Cable Note When setting the indoor unit address If the RMC 1 switch is set to 0 the Centralized Controller should to be connected to channel 0 If the RMC 1 switch is set to 1 the Centralized Controller should to be connected to channel 1 If the RMC 1 switch is set to ...

Page 11: ...MAIN ONE RMC 1 RMC 2 When setting the indoor unit address Indoor unit ADDRESS MAIN TEN 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 MAIN ONE 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 RMC 1 1 RMC 2 0 1 2 3 4 5 6 7 8 9 A B C D E F Indoor unit 1 Indoor unit 2 Indoor unit 13 Indoor unit 14 Indoor unit 15 Indoor unit 31 Indoor unit 30 Indoor unit 29 Indoor unit 18 Indoor unit 17 Indoor unit 16 Indoor unit 3 12 Indoor unit 19...

Page 12: ...or unit Individual control of indoor units Power cable DC 12V Power cable DC 5V Communication Cable Note When setting the indoor unit address If the RMC 1 switch is set to 0 the Centralized Controller should to be connected to channel 0 If the RMC 1 switch is set to 1 the Centralized Controller should to be connected to channel 1 If the RMC 1 switch is set to 2 the Centralized Controller should to...

Page 13: ... 0 0 0 1 1 1 1 1 1 MAIN ONE 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 RMC 1 0 RMC 2 0 1 2 3 4 5 6 7 8 9 A B C D E F Indoor unit 0 MAIN TEN MAIN ONE RMC 1 RMC 2 When setting the indoor unit address Indoor unit 1 Indoor unit 2 Indoor unit 13 Indoor unit 14 Indoor unit 15 Indoor unit 3 12 RMC 1 ...

Page 14: ...s for 1 outdoor unit Group control of indoor units Power cable DC 12V Power cable DC 5V Communication Cable Note When setting the indoor unit address If the RMC 1 switch is set to 0 the Centralized Controller should to be connected to channel 0 If the RMC 1 switch is set to 1 the Centralized Controller should to be connected to channel 1 If the RMC 1 switch is set to 2 the Centralized Controller s...

Page 15: ...5 5 5 6 6 6 6 MAIN ONE 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 RMC 1 0 RMC 2 0 1 2 3 4 5 6 7 8 9 A B C D E F Outdoor unit ADDRESS MAIN TEN 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 MAIN ONE 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 RMC 1 0 RMC 2 0 1 2 3 4 5 6 7 8 9 A B C D E F Indoor unit 0 Indoor unit 1 Indoor unit 2 Indoor unit 13 Indoor unit 14 Indoor unit 15 Indoor unit 3 12 Indoor unit 31 Indoor unit 30 Indoor unit 29 I...

Page 16: ... set to 0 DIP 1 Transmitter ADDRESS switch setting should be set respectively Controls 13 indoor units connected to DVM PLUS outdoor unit have the indoor unit RMC switch set to 0 C Controls 3 indoor units connected to DVM PLUS II outdoor unit which have the indoor unit RMC switch set to 1 Transmitter Centralized control DVM PLUS Outdoor unit Transmitter MIM B04A Power cable DC 12V Power cable DC 5...

Page 17: ...unit 2 Indoor unit 10 Indoor unit 11 Indoor unit 12 Indoor unit 3 12 Indoor unit 3 9 RMC 1 Indoor unit ADDRESS MAIN TEN 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 MAIN ONE 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 RMC 1 0 RMC 2 0 1 2 3 4 5 6 7 8 9 A B C D E F Indoor unit ADDRESS MAIN TEN 1 1 1 MAIN ONE 6 7 8 RMC 1 1 RMC 2 D E F Indoor unit ADDRESS MAIN 0 1 2 3 4 5 6 7 8 9 10 11 12 RMC 0 1 2 3 4 5 6 7 8 9 A B C MAIN RM...